25
Indoor Troubleshooting:
YSM3F (10-18) AAS
Board LED display
Wired controller display
①
Troubleshooting
Possible reasons
E0
E0
Malfunction of drain system
Pump motor disconnected
or at wrong position, or
the float switch broken
down, or the float switch
disconnected or at wrong
position.
E1
E1
Faulty ambient
temperature sensor
Sensor disconnected,
or broken, or at wrong
position, or short circuit.
E2
E2
Faulty coil temperature
sensor
Sensor disconnected,
or broken, or at wrong
position, or short circuit.
E8
E8
Abnormal communication
between indoor wired
controller and indoor unit
PCB
Wrong connection, or
the wired controller be
disconnected, faulty PCB.
F2
F2
EEPROM error
Loss of data EEPROM.
FC
FC
Indoor coil temperature too
high in cooling mode
Refrigerant leakage or
indoor coil sensor falling
off or failure on 3 phases
outdoor unit.
①
: Optional equipment
Outdoor toubleshooting
LED flash times of outdoor control board
Troubleshooting
Possible reasons
4
Protection of discharging temp.
too high or sensor abnormal
After compressor starts up, if TD
is over 120°C, 10seconds later
compressor stop.
5
Phase sequence abnormal
Power supply phase sequence
wrong.
6
Pressure abnormal
High/Low pressure switch acts
abnormal.
After compressor running for 3
minutes, if switch is detected
unconnected for 30 seconds, it
alarms, if it occurs 3 times in 30
minutes, confirm this failure.
Trouble Shooting
TD: discharging temperature