YORK INSTALLATION & OWNER’S MANUAL (
EN
) 035M80090-000
18000 Btu/h
220-240V - 50Hz
30/25A
3 x 2.5 mm
2
208-230V - 60Hz
24000 Btu/h
220-240V - 50Hz
40/25A
3 x 2.5 mm
2
208-230V - 60Hz
48000 Btu/h
380V 3N - 50Hz
42/27A
5 x 2.5 mm
2
460V 3N - 60Hz
WIRING DIAGRAM
Wiring
Prepare the power source for exclusive with the air conditioner.
The supply voltage must comply with the rated voltage of the air conditioner. The plug socket shall be accessible after
installation.
Remark:
All the wiring must be based on the wiring nameplate which is shown on the model.
CAUTIONS
• Perform the wiring with sufficient capacity. Installation places legally require a short circuit isolator to be attached
to prevent electrical shock.
• Do not extend the power cable code by cutting.
• Power voltage should be in the range of 90%-110% of rated voltage.
• The plug of the air conditioner takes a grounding leg, and clients should use a grounding socket so that the air
conditioner can be grounded efficiently.
• If the power cord is damaged, replacement should be conducted by qualified technician or a serviceman.
Remark per EMC Directive 89/336/EEC
To prevent flicker impressions during the start of the compressor (technical process), the following installation conditions do
apply.
1. The power connection for the air conditioner has to be done at the main power distribution.
The distribution has to be of an low impedance, normally the required impedance reaches at a 32A fusing point.
2. No other equipment has to be connected with this power line.
3. For detailed installation acceptance, please refer to your contract with the power supplier if restrictions do apply
for products like washing machines, air conditioners or electrical ovens.
4. For power details of the air conditioner, refer to the rating plate of the product.
5. For any question, contact your local dealer.
CAUTIONS
• Never modify the unit by removing any of the safety guards or by bypassing any of the safety interlock switches.
• Connect the connecting cable correctly and connect the connecting cable to terminal as identified with their
respective marks.
• Do not scratch the conductive core & inner insulator of power supply cables and do not deform or smash on the surface
of cables.
NOTE
NOTE
The supply voltage must be consistent with the rate
voltage of the air conditioner.
Electrical work
Model 18 Cooling and Heating
T3
E
1
N 3
4
5
Indoor Unit
Outdoor Unit
T3
E
1
N 3
4
5
Model 18 Cooling only
Power Supply
208-230V/1Ph/60Hz
220-240V/1Ph/50Hz
L N
Power Supply
208-230V/1Ph/60Hz
220-240V/1Ph/50Hz
L N
1
N
3
4
Indoor Unit
1
N
3
4
Outdoor Unit
5
Model
Power source
Circuit
breaker/fuse
Wiring size
Model 24 Cooling only
Model 24 Cooling and Heating
Power Supply
208-230V/1Ph/60Hz
220-240V/1Ph/50Hz
L N
L1
N1
1 2 3 4
5
6
6
Indoor Unit
L
N
1
2
3 4
5
Outdoor Unit
Power Supply
208-230V/1Ph/60Hz
220-240V/1Ph/50Hz
L N
L1
N1
1 2 3 4
Indoor Unit
L
N
1
2
3 4
Outdoor Unit
Model 48 Cooling only
Model 48 Cooling and Heating
Power Supply
380-415V/3Ph/50Hz
460V/3Ph/60Hz
A
B
C
N
1
2
3
4
5
6
Indoor Unit
A
B
C
N
1
2
3
4
Outdoor Unit
Power Supply
380-415V/3Ph/50Hz
460V/3Ph/60Hz
A
B
C
N
1
2
3
4
5
6
Indoor Unit
A
B
C
N
1
2
3
4
Outdoor Unit