JOHNSON CONTROLS
15
FORM 160.76-PW5
ISSUE DATE: 09/06/2019
PRESSURE TEMPERATURE CHART
TABLE 1 -
PRESSURE TEMPERATURE CHART
Application
Device
Units
Operating Point
Chilled
Water
Brine
On Rise
On Fall
HDT
Deg.F/Deg.C
220/104.4
219/103.9
HOT
Deg.F/Deg.C
180/82.2
179/81.7
OP
psid/kPa
25/172
15/104
HP (R-134a)
psig/kPa
For further information, see
Form 160.54-O1
LEP (R-134a)
psig/kPa
Cut-Out
180/1241
Inhibit PRV
Opening *
162.5/1120
Allow PRV
Opening *
160/1103
Cut-In
120/827
1LEP
psig
Cut-In
25.1/173
Allow PRV
Opening
28.0/193
Inhibit PRV
Opening
27.0/186
Cut-Out
25.0/172
HOP
psid/kPa
FDTS
Deg.F/Deg.C
90/620.6
<90/620.6
LWT
Deg.F/Deg.C
30.0/-1.10
29.9/-1.20
LWT
Deg.F/Deg.C
Programmable as outlined in
Operations Manual Form
160.54-O1
LOT
Deg.F/Deg.C
71.0/21.7
55.0/12.8
LOTD†
Deg.F/Deg.C
30/16.7
29.9/16.6
LOTD††
Deg.F/Deg.C
40/22.2
39.9/22.1
* - Function provided by condenser transducer default valves shown on table, actual values as programmed.
† - Applicable if unit was shut down for 30 min or less.
†† - Applicable if unit was shut down for greater than 30 min.