Note:
The weights provided in the following table are intended to be a general reference only.
The weights are based on the heaviest anticipated unit combinations as of December 2020.
There are numerous factors that can impact these values based on the chiller options selected
at the time of the final unit rating. The actual weights may vary. If specific weight measures are
required for load distribution calculations, etc., then all weights must be verified using the unit
submittal data, the Bill of Lading from the plant shipment, or other reliable means.
Table 7: Approximate unit weight including motor for hybrid falling film evaporator units
Unit shell
codes
Compressor
Shipping weight,
lb (kg)
Operating weight,
lb (kg)
Est. refrigerant charge,
lb (kg)
2-2
Q3, Q4
12659 (5742)
14099 (6395)
690 (313)
4-4
Q3, Q4, Q5, Q6, Q7
14733 (6683)
17047 (7733)
914 (415)
6-6
Q5, Q6, Q7
17280 (7838)
20358 (9234)
1357 (616)
A-A
Q3, Q4
12390 (5620)
13833 (6275)
555 (252)
B-B
Q3, Q4
13022 (5907)
14033 (6365)
652 (296)
C-C
Q3, Q4, Q5, Q6, Q7, Q8
14080 (6387)
16120 (7312)
805 (365)
D-D
Q3, Q4, Q5, Q6, Q7, Q8
14874 (6747)
17195 (7800)
945 (429)
E-C
Q5, Q6, Q7, Q8
15487 (7025)
17988 (8159)
927 (420)
E-E
Q5, Q6, Q7, Q8
16448 (7461)
19222 (8719)
1020 (463)
F-D
Q5, Q6, Q7, Q8
16440 (7457)
19171 (8696)
980 (445)
F-F
Q5, Q6, Q7, Q8
17387 (7887)
20431 (9268)
1080 (490)
G-E
Q5, Q6, Q7, Q8, P8, P9
21758 (9869)
24762 (11232)
1090 (494)
H-F
P8, P9, H9
22525 (10217)
26591 (12061)
1377 (625)
J-J
Q5, Q6, Q7, Q8
19853 (9005)
24101 (10932)
1396 (633)
K-K
P8, P9, H9, K1
31026 (14073)
36201 (16421)
1811 (821)
L-L
H9, K1
32802 (14879)
38593 (17506)
2181 (989)
M-K
K1, K2
33315 (15112)
38659 (17536)
1919 (870)
N-L
K1, K2
35214 (15973)
41215 (18695)
2322 (1053)
O-O
H9, K1, K2
37877 (17181)
44062 (19987)
2338 (1060)
P-P
H9, K1, K2
39606 (17965)
46549 (21115)
2849 (1292)
Q-Q
K1, K2
39145 (17756)
46531 (21106)
2800 (1270)
R-R
K1, K2, K3
47325 (21467)
55926 (25368)
3305 (1499)
S-S
K3, K4
58004 (26311)
69858 (31688)
3267 (1482)
T-T
K3, K4
58127 (26366)
69895 (31704)
3701 (1679)
U-U
K3, K4
62109 (28173)
74901 (33975)
3417 (1550)
V-V
K3, K4
65806 (29850)
79920 (36252)
3870 (1755)
V-W
K4, K7
71989 (32654)
87232 (39568)
4396 (1994)
W-W
K7
74336 (33719)
90413 (41011)
4598 (2086)
Y-Z
K7
82614 (37474)
101999 (46267)
5677 (2575)
X-W
K7
77550 (35177)
95000 (43092)
5014 (2274)
X-Y
K4, K7
85185 (38639)
108946 (49417)
5114 (2320)
Note:
Refrigerant charge quantity and weights will vary based on tube count and
configuration. Use for reference only.
31
Model YK Chillers (Style H) Field Reassembly for Form 3, 7, 9, and 10 Shipment