30
P01432Q-rev.1
(4) Capacity Code Setting (DSW3)
No setting is required, due to setting before shipment. This switch is utilized for setting the capacity
code which corresponds to the capacity of the indoor unit.
(3) Unit No. Setting (RSW1 and DSW6)
Setting is not required.
Indoor unit numbers are set by the auto-address
function. If an indoor unit number setting is
required, set the unit number of all indoor units
respectively and sequentially by following
setting position. It is recommended that you
assign a number to each indoor unit from “1”.
A maximum of 64 indoor units per refrigerant
cycle can be connected to an H-LINK ll System.
Though the available numbers range from zero
to 63, the applicable number for the 64
th
indoor
unit in theory supplants the number "zero".
For the centralized control, this setting is
required.
1 2 3 4
ON
OFF
Setting Position
72
Indoor Unit Capacity
(MBH)
96
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
(5) Unit Model Code Setting (DSW4)
No setting is required. It is for setting the model code of the indoor unit.
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
DSW6 (Tens Digit)
Unit No. Setting
RSW1 (Units Digit)
Setting
Position
Set by inserting
slotted screwdriver
into the groove.
Ex.) Set at No.16 Unit
DSW6
RSW1
Set No.1 Pin at ON side
Set at "6"
34
1
0
89
2
56
7
34
1
0
89
2
56
7
Before shipment, DSW6 and RSW1 are set at "0".
For the units supporting H-LINK II,
the unit No. can be set for Max. 64 indoor units
(No.0~63).
8.5 DIP Switch Settings
(1) Turn OFF the power supply to both indoor and outdoor units before adjusting DIP switch settings.
Otherwise, the setting will be invalidated and not take effect.
(2) Positions of DIP switches are shown below.