background image

 

29 

 

ΔT=T1-Ts 

Running mode 

ΔT

2

 

Cooling 

-

2≤ΔT≤2

 

Fan-only 

ΔT<-2

 

Heating 

Indoor fan will run at auto fan of the relevant 

mode. 

The louver operates same as in relevant mode. 

If the machine switches mode between heating 

and cooling, the compressor will keep stopping 

for 15 minutes and then choose mode 

according to T1-Ts. 

If the setting temperature is modified, the 

machine will choose running function again. 

 

8.4.5 Drying mode 

Indoor fan speed is fixed at breeze and can’t be 

changed. The louver angle is the same as in 

cooling mode. 

All protections are active and the same as that 

in cooling mode. 

 

8.4.6 Forced operation function 

Forced cooling mode: 

The compressor and outdoor fan keep running 

and the indoor fan runs at low speed. After 

running for 30 minutes, AC will turn to auto 

mode with 24

 setting temperature. 

Forced auto mode: 

The action of forced auto mode is the same as 

normal auto mode with 24

 

setting 

temperature. 

When AC receives signals, such as switch on, 

switch off, timer on, timer off, mode setting, fan 

speed setting, sleeping mode setting, follow me 

setting, it will quit the forced operation. 

 

8.4.7 Timer function 

8.4.7.1 Timing range is 24 hours. 

8.4.7.2 Timer on. The machine will  turn on 

automatically when reaching the setting time. 

8.4.7.3 Timer off.  The machine will turn off 

automatically when reaching the setting time. 

8.4.7.4 Timer on/off. The machine will turn on 

automatically when reaching the setting “on” 

time, and then turn off automatically when 

reaching the setting “off” time. 

8.4.7.5 Timer off/on. The machine will turn off 

automatically when reaching the setting “off” 

time, and then turn on automatically when 

reaching the setting “on” time. 

8.4.7.6  The timer function  will not change the 

AC current operation mode. Suppose AC is off 

now, it will not start up firstly after setting the 

“timer off”  function. And when reaching the 

setting time, the timer LED will be off and the 

AC running mode has not been changed. 

8.4.7.7 The setting time is relative time. 

8.4.7.8 The AC will quit the timer function when 

it has malfunction. 

 

8.4.8 Sleep function 

8.4.8.1 The sleep function is available in 

cooling, heating or auto mode. 

8.4.8.2. Operation process in sleep mode is as 

follow: 

When cooling, the setting temperature rises 1

 

(be lower than 30

) every one hour, 2 hours 

later the setting temperature stops rising and 

the indoor fan is fixed at low speed.     

When heating, the setting temperature 

decreases 1

  (be higher than 17

) every one 

hour, 2 hours later the setting temperature 

stops rising and indoor fan is fixed at low speed. 

(Anti-cold wind function has the priority). 

8.4.8.3 Operation time in sleep mode is 7 hours. 

After 7 hours the AC quits this mode and turns 

off. 

8.4.8.4 Timer setting is available 

 

8.4.9 Auto-Restart function 

The indoor unit is equipped with auto-restart 

function, which is carried out through an 

auto-restart module. In case of a sudden power 

failure, the module memorizes the setting 

conditions before the power failure. The unit will 

resume the previous operation setting (not 

including  swing function) automatically after 3 

minutes when power returns. 

Содержание YHKE09XEEAMH-RX

Страница 1: ...SPLIT TYPE ROOM AIR CONDITIONER Pyrenees Series All Model Numbers Service Manual M Pyrenees 160929 New Released Sep 29 2016 Issue Date...

Страница 2: ...he first time 16 5 5 Adding the refrigerant after running the system for many years 17 5 6 Re installation while the indoor unit need to be repaired 17 5 7 Re installation while the outdoor unit need...

Страница 3: ...s could cause injury be especially careful of the case edges and the fins on the condenser and evaporator For installation always contact the dealer or an authorized service center Do not install the...

Страница 4: ...vels may cause failure of product Install the drain hose to ensure that water is drained away properly A bad connection may cause water leakage Keep level even when installing the product It can avoid...

Страница 5: ...he all batteries in the remote control with new ones of the same type Do not mix old and new batteries or different types of batteries There is risk of fire or explosion Do not recharge or disassemble...

Страница 6: ...KE18YEEAMHO X 24k YHKE24XEEAMH RX YHKE24YEEAMHO X Cold catalyst filter Silver Ico Filter O Vitamin C Filter O 3M HAM Filter O Bio Filter O Golden Fin O Super Ionizer O Compressor Crankcase Heater O Se...

Страница 7: ...5 3 Dimension 3 1 Indoor Unit Model W D H 7K INDOOR 722 187 290 YHKE09XEEAMH RX 722 187 290 YHKE12XEEAMH RX 802 189 297 YHKE18XEEAMH RX 965 215 319 YHKE24XEEAMH RX 1080 226 335...

Страница 8: ...6 For 7K INDOOR YHKE09XEEAMH RX For YHKE12XEEAMH RX For YHKE18XEEAMH RX...

Страница 9: ...7 For YHKE24XEEAMH RX...

Страница 10: ...8 3 2 Outdoor Unit More than 30cm More than 60cm More than 200cm More than 30cm More than 60cm Service space Fence or obstacles...

Страница 11: ...9 For 7K OUTDOOR YHKE09YEEAMHO X 487 W1 70 W2 298 555 300 D H 12 60 93 H1 H2 D1 770 W 779 W3 322 D2 25 B1 90 B2 61 5 A2 12 A1 R 6 286 D3...

Страница 12: ...10 For YHKE12YEEAMHO X MOB32 12HFN1 QRD0GW YHKE18YEEAMHO X 800 W 514 W1 554 60 85 5 340 12 0 311 815 W3 365 333 D 70 W2 H H1 H2 D1 D2 D3 62 B1 106 B2 20 A1 R20 R6 61 6 A2...

Страница 13: ...11 For YHKE24YEEAMHO X MOCA30 24HFN1 QRC8GW...

Страница 14: ...YHKE18YEEAMHO X YHKE24YEEAMHO X LIQUID SIDE GAS SIDE HEAT EXCHANGE EVAPORATOR HEAT EXCHANGE CONDENSER COMPRESSOR 2 WAY VALVE 3 WAY VALVE 4 WAY VALVE COOLING HEATING T2 Evaporator temp sensor T1 Room t...

Страница 15: ...ID SIDE GAS SIDE HEAT EXCHANGE EVAPORATOR HEAT EXCHANGE CONDENSER Compressor 2 WAY VALVE 3 WAY VALVE 4 WAY VALVE COOLING HEATING T2 Evaporator temp sensor T1 Room temp sensor INDOOR OUTDOOR Accumulato...

Страница 16: ...4 6500 663kgf cm 6700 683kgf cm 5 2 Connecting the cables The power cord of connect should be selected according to the following specifications sheet Rated current of appliance Nominal cross section...

Страница 17: ...3 8 9 52 1 4 6 35 5 10 25 15 YHKE09XEEAMH RX YHKE09YEEAMHO X 3 8 9 52 1 4 6 35 5 10 25 15 YHKE12YEEAMHO X YHKE12XEEAMH RX 3 8 9 52 1 4 6 35 5 10 25 15 YHKE18XEEAMH RX YHKE18YEEAMHO X 1 2 12 7 1 4 6 3...

Страница 18: ...3 Connect the charge hose of handle hi connection to the vacuum pump 4 Fully open the handle Lo of the manifold valve 5 Operate the vacuum pump to evacuate 6 Make evacuation for 30 minutes and check w...

Страница 19: ...2 way valve and the 3 way valve Connect the charge hose to the valve at the bottom of the cylinder If the refrigerant is R410A make the cylinder bottom up to ensure liquid charge 2 Purge the air from...

Страница 20: ...hi connection to the vacuum pump 4 Fully open the handle Lo of the manifold valve 5 Operate the vacuum pump to evacuate 6 Make evacuation for 30 minutes and check whether the compound meter indicates...

Страница 21: ...e air be careful of the liquid refrigerant 3 Put the charging cylinder onto the electronic scale and record the weight 4 Open the valves Low side on the charge set and charge the system with liquid re...

Страница 22: ...20 6 Wiring Diagram 6 1 Indoor Unit 7K INDOOR YHKE09XEEAMH RX YHKE12XEEAMH RX YHKE18XEEAMH RX YHKE24XEEAMH RX...

Страница 23: ...21 6 2 Outdoor Unit YHKE09YEEAMHO X YHKE12YEEAMHO X...

Страница 24: ...22 YHKE18YEEAMHO X YHKE24YEEAMHO X...

Страница 25: ...itioner is used beyond the above conditions certain safety protection features may come into operation and cause the unit to operate abnormally 2 The room relative humidity should be less than 80 If t...

Страница 26: ...ode Displays the self diagnostic codes Dispalys for three seconds when Timer ON Fresh Swing Turbo or Silence feature is activated Dispalys for three seconds when Fresh Swing Turbo or Silence feature i...

Страница 27: ...rking 8 3 6 Indoor fan delayed open function When the unit starts up the louver will be active immediately and the indoor fan will open 7s later If the unit runs in heating mode the indoor fan will be...

Страница 28: ...is more than setting value the current protection function will be activated and the compressor will stop 8 4 2 2 Outdoor fan running rules The outdoor unit will be run at different fan speed accordin...

Страница 29: ...sor will be on T is the programmed parameter of temperature compensation When the AC run in mute mode the compressor will run with low frequency When the current is more than setting value the current...

Страница 30: ...5 minutes in defrosting mode For YHKE18XEEAMH RX YHKE24XEEAMH RX models AC will enter the defrosting mode according to the value of temp of T3 and the value range of temp change of T3 and also the com...

Страница 31: ...off automatically when reaching the setting off time 8 4 7 5 Timer off on The machine will turn off automatically when reaching the setting off time and then turn on automatically when reaching the s...

Страница 32: ...function can keep the inside of indoor unit dry and prevent breeding of mold 8 4 14 Follow me optional 1 If the indoor PCB receives the signal which results from pressing the FOLLOW ME button on remot...

Страница 33: ...code Meaning T1 T1 Indoor room temp T2 T2 Indoor coil mid temp T3 T3 Outdoor coil temp T4 T4 Outdoor temp T2B Tb Indoor coil outlet temp TP TP Compressor discharge temp TH TH IPM modular temp Targete...

Страница 34: ...d1 d9 130 131 139 E0 E1 E9 140 141 149 F0 F1 F9 150 151 159 Indoor fan speed Outdoor fan speed 0 OFF 1 2 3 4 Low speed Medium speed High speed Turbo For some big capacity motors 14 FF Actual fan spee...

Страница 35: ...electricity power in capacitor Electrolytic Capacitors HIGH VOLTAGE CAUTION For other models please connect discharge resistance approx 100 40W or soldering iron plug between terminals of the electrol...

Страница 36: ...pen circuit or short circuit 4 times O F3 Compressor discharge temperature sensor T5 open circuit or short circuit 5 times O F4 Outdoor unit EEPROM parameter error 6 times O F5 Outdoor fan speed has b...

Страница 37: ...nstallation mistake PCB faulty Trouble shooting Yes Replace the indoor outdoor main PCB Power off then restart the unit 2 minutes later EEPROM a read only memory whose contents can be erased and repro...

Страница 38: ...25V to 25V Vs is the voltage between S and N of outdoor unit Red pan S Black pan N Yes Power off then restart the unit 2 minutes later Power off then restart the unit 2 minutes later No Replace the ou...

Страница 39: ...off the power supply and turn it on 2 minutes later Is it still displaying the error code Shut off the power supply rotate the fan by hand Does it rotate properly The unit operates normally Find out t...

Страница 40: ...NO Color Signal Voltage 1 Red Vs Vm 280V 380V 2 3 Black GND 0V 4 White Vcc 14 17 5V 5 Yellow Vsp 0 5 6V 6 Blue FG 14 17 5V 2 Outdoor DC Fan Motor control chip is in outdoor PCB Power on and check if t...

Страница 41: ...oor PCB faulty System problems such as leakage or blocking Trouble shooting Is there cool air blowing out from indoor air outlet Yes Yes Check if T2 sensor is well fixed Correct the installation or re...

Страница 42: ...is lower than 0 06V or higher than 4 94V the LED will display the failure Supposed causes Wiring mistake Sensor faulty Trouble shooting Check the connections between temperature sensor and main PCB Ar...

Страница 43: ...lems System blockage PCB faulty Wiring mistake Compressor malfunction Trouble shooting Check the power supply Is it normal Check the connections and wires Is it well connection Stop the unit Check the...

Страница 44: ...n PCB and compressor If the wires and connectors are broken Correct the connection or replace the wires and connectors Yes No IPM continuity check Check if the IPM terminal resistance values are unifo...

Страница 45: ...ytic capacitors discharge completely and dismount the IPM Use a digital tester to measure the resistance between P and UVWN UVW and N Digital tester Normal resistance value Digital tester Normal resis...

Страница 46: ...connections and wires are good Disconnect the unit with power supply and try to restart the unit when power supply gets normal No Yes No Correct the connections or replace the wires Yes Power on and w...

Страница 47: ...the PCB and IPM radiator are fixed tightly For other models Check if the air flow system of indoor and outdoor units are obstructed Clear up the air inlet and outlet or the heat exchanger of indoor an...

Страница 48: ...onnected well Correct the connection or replace the wires and connectors No Yes Check if the IPM installed correctly Correct the installation tighten the screws and apply silicon grease No IPM continu...

Страница 49: ...from PCB measure the resistance value with a tester Temperature Sensors Room temp T1 sensor Indoor coil temp T2 sensor Outdoor coil temp T3 sensor Outdoor ambient temp T4 sensor Compressor discharge t...

Страница 50: ...29078 117 243 0 38991 2 28 39 8239 38 100 5 62961 78 172 1 25423 118 244 0 37956 1 30 37 1988 39 102 5 39689 79 174 1 2133 119 246 0 36954 0 32 35 2024 40 104 5 17519 80 176 1 17393 120 248 0 35982 1...

Страница 51: ...2 422 4 25 222 8 36 97 34 32 76 169 7 82 116 241 2 357 3 27 211 4 37 99 32 94 77 171 7 566 117 243 2 294 2 28 200 7 38 100 31 62 78 172 7 321 118 244 2 233 1 30 190 5 39 102 30 36 79 174 7 086 119 246...

Страница 52: ...cking Measure the resistance value of each winding by using the tester Position Resistance Value ASK89D53UEZ ASN98D22UFZ ASM135D23UFZ ATF235D22UMT Blue Red 2 35 20 68 1 57 20 68 1 75 20 68 0 75 20 68...

Страница 53: ...2016 Johnson Controls Inc www johnsoncontrols com Doc No M Pyrenees 160929...

Отзывы: