29
ΔT=T1-Ts
Running mode
ΔT
>
2
℃
Cooling
-
2≤ΔT≤2
℃
Fan-only
ΔT<-2
℃
Heating
Indoor fan will run at auto fan of the relevant
mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating
and cooling, the compressor will keep stopping
for 15 minutes and then choose mode
according to T1-Ts.
If the setting temperature is modified, the
machine will choose running function again.
8.4.5 Drying mode
Indoor fan speed is fixed at breeze and can’t be
changed. The louver angle is the same as in
cooling mode.
All protections are active and the same as that
in cooling mode.
8.4.6 Forced operation function
Forced cooling mode:
The compressor and outdoor fan keep running
and the indoor fan runs at low speed. After
running for 30 minutes, AC will turn to auto
mode with 24
℃
setting temperature.
Forced auto mode:
The action of forced auto mode is the same as
normal auto mode with 24
℃
setting
temperature.
When AC receives signals, such as switch on,
switch off, timer on, timer off, mode setting, fan
speed setting, sleeping mode setting, follow me
setting, it will quit the forced operation.
8.4.7 Timer function
8.4.7.1 Timing range is 24 hours.
8.4.7.2 Timer on. The machine will turn on
automatically when reaching the setting time.
8.4.7.3 Timer off. The machine will turn off
automatically when reaching the setting time.
8.4.7.4 Timer on/off. The machine will turn on
automatically when reaching the setting “on”
time, and then turn off automatically when
reaching the setting “off” time.
8.4.7.5 Timer off/on. The machine will turn off
automatically when reaching the setting “off”
time, and then turn on automatically when
reaching the setting “on” time.
8.4.7.6 The timer function will not change the
AC current operation mode. Suppose AC is off
now, it will not start up firstly after setting the
“timer off” function. And when reaching the
setting time, the timer LED will be off and the
AC running mode has not been changed.
8.4.7.7 The setting time is relative time.
8.4.7.8 The AC will quit the timer function when
it has malfunction.
8.4.8 Sleep function
8.4.8.1 The sleep function is available in
cooling, heating or auto mode.
8.4.8.2. Operation process in sleep mode is as
follow:
When cooling, the setting temperature rises 1
℃
(be lower than 30
℃
) every one hour, 2 hours
later the setting temperature stops rising and
the indoor fan is fixed at low speed.
When heating, the setting temperature
decreases 1
℃
(be higher than 17
℃
) every one
hour, 2 hours later the setting temperature
stops rising and indoor fan is fixed at low speed.
(Anti-cold wind function has the priority).
8.4.8.3 Operation time in sleep mode is 7 hours.
After 7 hours the AC quits this mode and turns
off.
8.4.8.4 Timer setting is available
8.4.9 Auto-Restart function
The indoor unit is equipped with auto-restart
function, which is carried out through an
auto-restart module. In case of a sudden power
failure, the module memorizes the setting
conditions before the power failure. The unit will
resume the previous operation setting (not
including swing function) automatically after 3
minutes when power returns.
Содержание YHKE09XEEAMH-RX
Страница 8: ...6 For 7K INDOOR YHKE09XEEAMH RX For YHKE12XEEAMH RX For YHKE18XEEAMH RX...
Страница 9: ...7 For YHKE24XEEAMH RX...
Страница 13: ...11 For YHKE24YEEAMHO X MOCA30 24HFN1 QRC8GW...
Страница 22: ...20 6 Wiring Diagram 6 1 Indoor Unit 7K INDOOR YHKE09XEEAMH RX YHKE12XEEAMH RX YHKE18XEEAMH RX YHKE24XEEAMH RX...
Страница 23: ...21 6 2 Outdoor Unit YHKE09YEEAMHO X YHKE12YEEAMHO X...
Страница 24: ...22 YHKE18YEEAMHO X YHKE24YEEAMHO X...
Страница 53: ...2016 Johnson Controls Inc www johnsoncontrols com Doc No M Pyrenees 160929...