![York YHJD24S41S7 Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/york/yhjd24s41s7/yhjd24s41s7_technical-manual_4236172030.webp)
30
Johnson Controls Unitary Products
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO
YHJD42S41S7
AIR TEMP.
ENTERING
OUTDOOR UNIT (°F)
IDCFM
1150
1350
1550
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
38.3
40.5
40.4
44.3
48.5
40.0
41.5
41.5
45.4
49.6
41.8
42.5
42.6
46.4
50.8
S.C.
38.3
35.3
30.1
29.8
24.0
40.0
38.8
32.3
31.8
25.2
41.8
42.3
34.4
33.9
26.4
KW
2.33
2.34
2.37
2.43
2.46
2.45
2.45
2.47
2.52
2.54
2.56
2.56
2.57
2.60
2.62
75
T.C.
36.8
38.6
38.6
42.3
46.3
38.5
39.5
39.6
43.3
47.3
40.3
40.5
40.5
44.2
48.3
S.C.
36.8
34.5
29.3
29.0
23.2
38.5
37.4
31.5
31.0
24.3
40.3
40.4
33.6
33.0
25.5
KW
2.64
2.66
2.65
2.68
2.71
2.73
2.73
2.73
2.77
2.79
2.81
2.81
2.82
2.85
2.88
85
T.C.
35.4
36.7
36.9
40.3
44.2
37.0
37.6
37.6
41.1
45.0
38.7
38.4
38.4
42.0
45.9
S.C.
35.4
33.7
28.5
28.1
22.3
37.0
36.1
30.6
30.1
23.5
38.7
38.4
32.7
32.1
24.6
KW
2.95
2.97
2.94
2.94
2.97
3.01
3.02
3.00
3.02
3.05
3.07
3.06
3.06
3.10
3.13
95
T.C.
34.0
34.9
35.1
38.3
42.0
35.5
35.6
35.7
39.0
42.7
37.1
36.3
36.3
39.7
43.4
S.C.
34.0
32.9
27.7
27.3
21.5
35.5
34.7
29.8
29.3
22.6
37.1
36.3
31.8
31.2
23.7
KW
3.13
3.13
3.13
3.13
3.13
3.29
3.30
3.27
3.21
3.30
3.33
3.31
3.31
3.29
3.38
105
T.C.
32.3
32.6
32.8
35.8
39.2
33.6
33.6
33.3
36.4
39.8
35.0
34.5
33.8
37.0
40.4
S.C.
32.3
31.7
26.7
26.3
20.5
33.6
33.2
28.7
28.2
21.5
35.0
34.5
30.7
30.2
22.6
KW
3.58
3.59
3.56
3.56
3.60
3.64
3.64
3.62
3.64
3.68
3.70
3.70
3.69
3.72
3.76
115
T.C.
30.6
30.4
30.4
33.3
36.5
31.7
31.6
30.9
33.9
36.9
32.9
32.8
31.3
34.4
37.4
S.C.
30.6
30.4
25.6
25.2
19.4
31.7
31.6
27.6
27.2
20.5
32.9
32.8
29.7
29.1
21.6
KW
3.90
3.89
3.90
3.93
3.97
3.99
3.99
3.98
4.02
4.06
4.08
4.08
4.06
4.10
4.14
125
T.C.
29.0
28.2
28.1
30.9
33.7
29.8
29.6
28.5
31.3
34.1
30.7
31.1
28.9
31.7
34.4
S.C.
29.0
28.2
24.6
24.2
18.4
29.8
29.6
26.6
26.1
19.4
30.7
31.1
28.6
28.1
20.5
KW
4.22
4.20
4.24
4.31
4.35
4.34
4.33
4.34
4.39
4.43
4.46
4.46
4.44
4.48
4.52
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Green
shaded cells are ACCA (TVA) conditions.
Blue
shaded cells are AHRI conditions.
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Some of the combinations shown in these multiplier tables are not valid for use in the U.S.A. Please see the Capacity
Tables in the front of this Technical Guide for US matches, and verify matchups in the online AHRI directory at
www.ahridirectory.org
before sale. The matches shown at the end of this Technical Guide are for use in Canda Only.
Air Handlers
Coils
T.C.
S.C.
KW
–
FC/MC/PC48
1.04
1.08
1.15
–
FC/MC/PC60
1.04
1.09
1.15
AHE42D
–
1.08
1.08
1.09
AHE48D
–
1.05
1.16
1.11
AHV42D
–
1.06
1.09
1.08
AHV48D
–
1.01
1.09
1.07
MV16C
FC/MC48C
1.06
1.09
1.08
MV20D
FC/MC48D
1.08
1.12
1.09
Air Handlers
Coils
T.C.
S.C.
KW
MV20D
FC/MC60D
1.08
1.09
1.09
MX16CN21
FC/MC48C
1.05
1.09
1.06
MX16CN21
FC60C
1.03
1.12
1.10
MX20DN21
FC/MC48D
1.06
1.08
1.08
MX20DN21
FC/MC60D
1.04
1.09
1.05
571209-YTG-F-0615