5455359-YTG-A-1217
Johnson Controls Unitary Products
69
PERFORMANCE DATA - 5 TON
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
CONDENSER-ONLY DATA (OUTDOOR UNIT)
MODEL
SATURATED SUCTION
@ COMPRESSOR
Outdoor Ambient Temperature
65 °F
75 °F
85 °F
95 °F
105 °F
115 °F
125 °F
T (°F)
P (PSIG)
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
YHE60B22S
35
107
54.6
3.17
52.1
3.55
49.6
3.93
47.1
4.32
44.6
4.70
42.2
5.08
39.7
5.46
40
119
61.4
3.67
58.0
4.03
54.7
4.39
51.3
4.75
47.9
5.10
44.6
5.46
41.2
5.82
45
130
68.2
4.18
64.0
4.51
59.7
4.84
55.5
5.18
51.2
5.51
47.0
5.84
42.7
6.17
50
143
75.0
4.69
69.9
4.99
64.7
5.30
59.6
5.60
54.5
5.91
49.4
6.22
44.2
6.52
55
156
81.8
5.19
75.8
5.47
69.8
5.75
63.8
6.03
57.8
6.31
51.8
6.60
45.8
6.88
Notes:
1. For Outdoor Unit (Condenser) performance only. Data does not include the effects of air handler power or heat.
2. Performance based on 15°F subcooling and 15°F superheat at the Outdoor Unit base valves.
a. Increase capacity by 1% for each 2°F increase in subcooling.
b. Decrease capacity by 1% for each 2°F decrease in subcooling.
3. Maximum recommended condensing temperature is 140°F.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
YHE60B22S
AIR TEMP.
ENTERING
OUTDOOR UNIT (°F)
IDCFM
1600
1850
2100
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
54.3
57.6
57.5
61.2
64.3
55.4
57.6
57.5
60.7
63.3
56.4
57.7
57.5
60.1
62.3
S.C.
53.2
47.6
40.9
39.0
30.1
56.0
50.7
43.5
40.8
30.9
58.9
53.8
46.1
42.5
31.7
KW
3.45
3.49
3.47
3.51
3.50
3.55
3.59
3.57
3.60
3.59
3.65
3.69
3.67
3.69
3.68
75
T.C.
52.8
55.8
55.7
60.6
65.5
54.2
56.0
55.9
60.5
64.9
55.7
56.2
56.1
60.4
64.4
S.C.
51.8
47.4
40.4
39.6
31.0
54.5
51.1
43.3
42.1
32.3
57.1
54.7
46.2
44.5
33.7
KW
3.74
3.81
3.77
3.82
3.81
3.84
3.91
3.87
3.92
3.91
3.94
4.01
3.97
4.02
4.01
85
T.C.
50.6
53.1
53.1
57.7
63.1
52.1
53.3
53.1
57.6
62.7
53.5
53.5
53.2
57.5
62.3
S.C.
49.8
46.3
39.1
38.6
30.2
52.3
49.9
41.9
41.2
31.7
54.7
53.6
44.7
43.8
33.1
KW
4.17
4.22
4.19
4.24
4.23
4.27
4.32
4.29
4.33
4.33
4.37
4.42
4.39
4.42
4.43
95
T.C.
48.5
50.5
50.4
54.8
60.7
49.9
50.7
50.3
54.7
60.5
51.2
50.8
50.2
54.6
60.3
S.C.
47.7
45.1
37.8
37.6
29.5
50.1
48.8
40.5
40.3
31.0
52.4
52.5
43.1
43.0
32.6
KW
4.59
4.63
4.61
4.66
4.65
4.69
4.73
4.70
4.75
4.74
4.79
4.83
4.79
4.84
4.83
105
T.C.
46.0
47.3
47.2
51.3
56.9
47.2
47.4
47.0
51.1
56.5
48.4
47.4
46.9
50.9
56.2
S.C.
45.3
43.6
36.5
36.3
28.2
47.4
47.0
39.2
38.9
29.7
49.5
50.4
41.8
41.6
31.3
KW
5.17
5.20
5.17
5.22
5.22
5.26
5.29
5.27
5.32
5.32
5.35
5.38
5.37
5.42
5.42
115
T.C.
43.6
44.1
44.0
47.9
53.1
44.6
44.1
43.8
47.6
52.6
45.6
44.0
43.6
47.3
52.2
S.C.
42.9
42.0
35.2
34.9
26.9
44.8
45.2
37.8
37.6
28.4
46.7
48.3
40.5
40.2
30.0
KW
5.74
5.76
5.74
5.79
5.80
5.83
5.85
5.83
5.88
5.89
5.92
5.94
5.92
5.97
5.98
125
T.C.
41.1
41.0
40.8
44.4
49.3
41.9
40.7
40.5
44.0
48.7
42.8
40.5
40.2
43.7
48.1
S.C.
40.4
40.5
33.9
33.6
25.5
42.1
43.3
36.5
36.2
27.1
43.8
46.2
39.1
38.8
28.7
KW
6.31
6.32
6.31
6.36
6.37
6.40
6.42
6.40
6.45
6.47
6.49
6.52
6.49
6.54
6.57
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.