5.2.5.
. Electrical Control Functions
1. Dip switch functions:
A
-89-
SW1-1~~SW1-8
SW1-1
SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8 Description
ON
OFF
OFF
*
*
*
*
*
09 indoor
OFF
ON
OFF
*
*
*
*
*
12 indoor
OFF
OFF
ON
*
*
*
*
*
18 indoor
ON
OFF
ON
*
*
*
*
*
24 indoor
*
*
*
OFF
*
*
*
*
Room card invalid
*
*
*
ON
*
*
*
*
Room card valid
*
*
*
*
OFF
*
*
*
Heat pump
*
*
*
*
ON
*
*
*
Cooling only
*
*
*
*
*
OFF
*
*
Without temperature compensation
*
*
*
*
*
ON
*
*
with temperature compensation
*
*
*
*
*
*
OFF
OFF
Cassette
*
*
*
*
*
*
OFF
ON
2P Convertible
*
*
*
*
*
*
ON
OFF
Duct
*
*
*
*
*
*
ON
ON
5P Convertible
wiring controller address
SW2-1
SW2-2
SW2-3
SW2-4
master unit
OFF
OFF
OFF
OFF
slave unit 1
ON
OFF
OFF
OFF
slave unit 2
OFF
ON
OFF
OFF
slave unit 3
ON
ON
OFF
OFF
…………
…………
…………
…………
…………
slave unit 15
ON
ON
ON
ON
SW2: wiring controller communication address
when the wiring controller is used to control many units , the wiring controller communication
address of indoor unit need be setted
Indoor unit PCB