SECTION 7 – MAINTENANCE
FORM 155.31-ICOM2.EN.UL
ISSUE DATE: 12/21/2018
7
V11
Purging operating valve for purge tank line
V14
Purge main valve
V16
Purging operating valve for absorber line
YHAU-CW(L) 400-2000EX(W)(4)(S)P
YHAU-CW(L)150-300EX(S)P
LD19978
V16
V11
V14
V16
V11
V14
FIGURE 51 -
LOCATION OF MANUAL VALVE IN PURGING SYSTEM
V11
Purging operating valve for purge tank line
V14
Purge main valve
V16
Purging operating valve for absorber line
MANUAL METHOD TO PURGE NON-
CONDENSABLE GAS DIRECTLY FROM
ABSORBER WITH VACUUM PUMP
When the chiller operates at a lower capacity than usual
for a long period of time or when it restarts after a pow-
er failure, the absorber may contain non-condensable
gases. If the machine starts under these conditions, its
performance and efficiency decrease. If this happens,
manually purge non-condensable gas directly from the
absorber according to the following procedure:
1. Set the valves according to pattern B. See
2. Press the Purge Mode
MANUAL
button.
3. Press the Manual Purge
ON
button. The vacuum
pump starts. The solenoid valves SV1 and SV2
open.
4. After step 3 begins, confirm that vacuum gauge
stands at 0 ~0.15 PSI.abs.
5. Reading the vacuum gauge, open valve V13.
6. Then, open valve V16 gradually. Confirm that the
pressure on the vacuum gauge increases slightly.
Содержание YHAU-CW
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 31 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 20: ...JOHNSON CONTROLS 20 FORM 155 31 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 43: ...JOHNSON CONTROLS 43 SECTION 4 TECHNICAL DATA 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 130: ...JOHNSON CONTROLS 130 FORM 155 31 ICOM2 EN UL ISSUE DATE 12 21 2018 THIS PAGE INTENTIONALLY LEFT BLANK...