JOHNSON CONTROLS
47
SECTION 4 - TECHNICAL DATA
FORM 155.35-ICOM2.EN.CE/GB (1018)
DATE: 10/30/2018
4
Scope of Delivery
Johnson Controls scope of delivery for the upper com-
munication system covers the control panels for the
upper communication function. The customer must de-
liver all other related equipment: concentrator (HUB),
installation, wiring, communication program for the
central monitoring unit, and so on. See
below for more information.
TABLE 5 -
SCOPE OF DELIVERY
ITEM
CUSTOMER
JCI
REMARKS
Control panel with
upper communication
function
X
Communication protocol: Modbus TCP
Data concentrator
(HUB)
X
Installation and wiring are included
Wiring work for Ethernet
connection
X
Apply twisted pair cable
Communication
program for central
monitoring unit
X
See
and
for the details of the IP address, function
code, communication data address, and other
relevant information.
Connection Port for Ethernet Communication
Make sure that the Ethernet cable is plugged into the correct port on the Control Panel. The Ethernet connection port
is located at the bottom left on the back of the Control Panel.
TABLE 6 -
ETHERNET INTERFACE SPECIFICATION
ITEM
SPECIFICATION
Communication format
10BASE-T or 100BASE-TX
Connector shape
RJ-45 type modular jack connector
LED function
Active
(Green)
Blink
Data sending or receiving
No light
No data sending or receiving
Link
(Green)
Blink
Data sending or receiving via
10BASE-T or 100BASE-TX
No light
No connection or successor job failure
Communication Specification
TABLE 7 -
COMMUNICATION SPECIFICATIONS
Communication Protocol
Modbus TCP
Communication Path Type
10BASE-T or 100BASE-TX
IP Address
(No. 1) 192.168.1.1, (No.2) 192.168.1.2, (No. 3) 192.168.1.3
Subnet Mask
255.255.255.0
Function Code
Read Command
(Digital Signal) 0.1 Read Coil
(Analog Signal) 0.3 Read Holding Register
Write Command
(Digital Signal) 0.5 Force Single Coil
Содержание YHAU-CE
Страница 10: ...JOHNSON CONTROLS 10 FORM 155 35 ICOM2 EN CE GB 1018 DATE 10 30 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 35 ICOM2 EN CE GB 1018 DATE 10 30 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 84: ...JOHNSON CONTROLS 84 FORM 155 35 ICOM2 EN CE GB 1018 DATE 10 30 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 126: ...JOHNSON CONTROLS 126 FORM 155 35 ICOM2 EN CE GB 1018 DATE 10 30 2018 THIS PAGE INTENTIONALLY LEFT BLANK...