JOHNSON CONTROLS
47
SECTION 3 – HANDLING, STORAGE, INSTALLATION AND REASSEMBLY
FORM 155.33-ICOM2.EN.GB
ISSUE DATE:12/4/2017
4
FIGURE 18 -
4-WIRE N:1 CONNECTION WITH USER-CREATED CABLE
LD21549
The next table contains information about the commu-
nication specifications needed for the Modbus RTU.
See
for information about the
Read Command or
for informa-
tion about the Write Command.
Communication Protocol
Modbus/RTU
Communication path type
RS422/RS485 Data Length: 8 Bit Stop Bit: 1 Bit Parity: EVEN Speed: 9600 bps
Connector
D-Sub 9pin
Function Code
Read Coil Status:01 Read Holding Register:03
Device
Digital Signal: Coil Analog Signal: Holding Register
Slave Equipment Address
1
TABLE 12 -
COMMUNICATION SPECIFICATIONS