SECTION 3 – HANDLING, STORAGE, INSTALLATION AND REASSEMBLY
Communication Specification
TABLE 7 -
COMMUNICATION SPECIFICATIONS
Communication Protocol
Modbus TCP
Communication Path Type
10BASE-T or 100BASE-TX
IP Address
(No. 1) 192.168.1.1, (No.2) 192.168.1.2, (No. 3) 192.168.1.3
Subnet Mask
255.255.255.0
Function Code
Read Command
(Digital Signal) 0.1 Read Coil
(Analog Signal) 0.3 Read Holding Register
Write Command
(Digital Signal) 0.5 Force Single Coil
Communication Data
TABLE 8 -
READ COMMAND
ITEM
DISPLAY
UNIT
ADDRESS
CONTENT
SET
V
ALUE
1
Set Point (Chilled / Hot water outlet
temp.)
7.0
°C
00001
0050~1000 unit, 1 unit=0.1 °C
2
Automatic stop temp. at cooling
mode (thermo-off temp)
5.0
°C
00003
0040~1000 unit, 1 unit=0.1 °C
3
Temp. difference of Automatic start
and stop control at cooling mode
5.0
°C
00005
0001~1000 unit, 1 unit=0.1 °C
4
Automatic stop temp. at heating
mode (thermo-off temp)
62.0
°C
00007
0040~1000 unit, 1 unit=0.1 °C
5
Temp. difference of Automatic start
and stop control at heating mode
5.0
°C
00009
0001~1000 unit, 1 unit=0.1 °C
OPERA
TION CONDITION
6
Operation condition
0 or 1
or 2
-
00021
0:STOP, 1:COOLING OPERATION,
2:HEATING OPERATION
7
Local or Remote mode condition
0 or 1
-
01001
0:LOCAL, 1:REMOTE
8
Solution pump condition
0 or 1
-
01003
0:STOP,1:OPERATION
9
Refrigerant pump condition
0 or 1
-
01005
0:STOP,1:OPERATION
10
Burner fan condition
0 or 1
-
01007
0:STOP,1:OPERATION
11
Load limit condition
0 or 1
-
01009
0:NORMAL OPERATION
1:LOAD LIMIT OPERATION
12
Control manipulated variable.
100
%
00023
-0100~1100 unit, 1 unit=0.1%
13
Failure signal.
0 or 1
-
01011
0:NORMAL OPERATION
1:FAILURE OCCUR
14
Alarm signal
0 or 1
-
01013
0:NORMAL OPERATION
1:ALARM OCCUR
Содержание YHAU-CE-JE Series
Страница 10: ...JOHNSON CONTROLS 10 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 22: ...JOHNSON CONTROLS 22 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 120: ...JOHNSON CONTROLS 120 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 135: ...JOHNSON CONTROLS 135 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 9 THIS PAGE INTENTIONALLY LEFT BLANK...