SECTION 3 – HANDLING, STORAGE, INSTALLATION AND REASSEMBLY
HOT INSULATION AND COLD INSULATION
PROCEDURE
The installation of insulation is out of
scope. The customer is responsible for
performing the work.
1. The recommended materials and their thickness
for hot insulation and cold insulation are shown in
.
2. Use a bonding agent, iron wire, iron band, and so
on to fix the hot insulation and cold insulation ma
-
terials. Never rivet them. Johnson Controls does
not recommend the use of welding pins.
TABLE 1 -
INSULATING MATERIAL AND THICKNESS
HOT INSULATION
EXHAUST GAS INSULATION
COLD INSULATION
Material
Rock wool or glass wool
Fineflex B10 blanket (Tombo #5615
equivalency product)
Polyurethane foam, polystyrene
foam, or glass wool
Thickness
50 mm
150 mm
50 mm
TABLE 2 -
POINTS REQUIRING HOT OR COLD INSULATION
POINT REQUIRING
HOT INSULATION
POINT REQUIRING
COLD INSULATION
POINT THAT MUST NOT BE
HEAT-INSULATED
Exhaust gas flue duct
Evaporator shell
Sight glass
Heat exchanger
Evaporation water changer casing
Valve manipulator
High temperature generator
Refrigerant spray piping
Pressure gauge
Waste hot water heat exchanger
Refrigerant blow piping
Thermometer insertion hole
• Low temperature generator
• Waste hot water-driven generator
Point carrying Cold Insulation label
Relay insertion hole
Point carrying Hot Insulation label
• Exhaust gas inlet temperature sensor
• Exhaust gas damper radiation fins
3.
Make sure that the outer covering, flanged parts,
and evaporator water chamber casing can be eas-
ily removed to facilitate servicing.
4. The points that require hot insulation or cold insu-
lation are shown in
5. The casing of the absorber and condenser water
chamber does not require insulation. If you use
insulation, make sure it can be easily removed.
6. For the high temperature generator, install the in-
sulation so that the front, sides, and rear insulation
can be removed separately. In addition, make sure
that the insulation around the exhaust gas inlet
and the outlet inspection windows can be easily
removed.
Содержание YHAU-CE-JE Series
Страница 10: ...JOHNSON CONTROLS 10 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 22: ...JOHNSON CONTROLS 22 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 120: ...JOHNSON CONTROLS 120 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 135: ...JOHNSON CONTROLS 135 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 9 THIS PAGE INTENTIONALLY LEFT BLANK...