PIPING

All piping connections are 5/8" OD copper tubing 

(see Fig.4).

The  supply  and  return  piping  must  be  adequately 

sized to meet the design water flow requirements as 

specified for the specific installation

.

  All chilled water 

piping must be insulated to prevent condensation.  It 

is also recommended that all piping be insulated to 

prevent freezing when piping is run in an uncondi-

tioned space.

Coil freeze protection is recommended 

for applications where the fan coil is 

located in ambient air locations (attics, 

crawl spaces, etc.) or within structures 

that may be unoccupied during freez-

ing conditions.  Consult the factory for 

additional information.

Piping Precautions

• 

Flush all piping prior to connection to remove 

all debris.

• 

Use wet cotton rags to cool valve bodies when 

soldering.

• 

Open  all  valves  (midway  for  hand  valves, 

manually open on motorized valves) prior to 

soldering.

• 

When soldering to bronze or brass, heat the piping 

while in the socket/cup and begin introducing the 

solder when the flux boils rapidly.  Avoid direct 

flame into the solder joint.

• 

Heat can only be applied to the cup of the valve 

body for a minimal time before damage occurs 

(even with the use of wet rags).

• 

Avoid rapid quenching of solder joints, as this 

will produce joints of inferior quality.

• 

Connect  all  piping  per  accepted  industry 

standards and observe all regulations governing 

installation  of  piping  systems.    When  all 

connections are complete, the system must be 

pressure tested.  Repair any solder joint leaks and 

gently tighten any leaking valve packing nuts 

and piping accessories as required.  Hydronic 

systems are not designed to hold pressurized air 

and should only be tested with water.

When  connecting  piping  or  valve 

kits to fan coil units, do not bend or 

reposition the coil header tubing for 

alignment purposes.  This could cause 

a tubing fracture resulting in a water 

leak when water pressure is applied 

to the system

FIG. 4 – CW-HW SERIES UPFLOW WALL / CLOSET FAN COILS  

4-Pipe Chilled Water-Hot Water (190 - 1085 CFM)

INSTALLATION

LD12277A

Содержание YCW

Страница 1: ...mance and or a possible hazardous safety condition to service personnel and occupants Company employees and or contractors are not authorized to waive this warning Notes 1 For proper operation control valve must be normally closed 2 Aquastats provided where required 3 Electric Heat is available as an option MODELS YCW SERIES YCW Series 2 pipe 4 pipe or 2 pipe cooling with electric heat LD11554 LD1...

Страница 2: ...HILLED WATER LINES 5 8 OD COPPER STUBOUTS HOT WATER RETURN HOT WATER SUPPLY FIG 1 UNIT NOMENCLATURE LD11557A LD11698A CABINET DIMENSIONS INCHES A B C D E F FILTER SIZE COIL CONN OD SWEAT HW CW YCW 22 1 8 15 1 8 40 14 10 1 2 3 5 8 18 X 18 5 8 YCW HW 22 1 8 15 1 8 43 18 12 1 2 3 5 8 18 X 18 5 8 5 8 YCWE 22 1 8 15 1 8 40 14 10 1 2 3 5 8 18 X 18 5 8 10 YCW 31 CFM 100 s 3 4 6 8 10 12 Unit Style YCW 2 p...

Страница 3: ...provided with 2 coils with single end sheets cooling connections are on the top panel right side and the hot water connec tions are on the top panel middle front This unit is designed to be installed vertically in the upflow position and can be installed on a closet plat If damage is found a claim should be filed against the carrier immediately form platform not provided hung on a closet wall use wa...

Страница 4: ... POWER SUPPLY WIRING WALL PANEL FRAME HOT WATER OUTLET HOT WATER INLET DRY WALL 2 X 4 WALL STUD CW UNITS CHILLED WATER CONNECTION Note Front edge of unit to be flush with dry wall CROSS MEMBER ON EDGE 2 X 4 WALL STUD WALL PANEL FRAME SCREW DETAIL OF WALL PANEL FRAME INSTALLATION DRY WALL LD11695A TABLE 1 DRYWALL OPENINGS MODEL NUMBER DRYWALL CUTOUT DIM HT x WD 3YWC 28 x 42 4YWC 28 x 50 6YWC 28 x 5...

Страница 5: ...standard 120 volt power wired to a dis connect terminal block and a ground lug Fan motor hi med and low speed leads are wired to the control board There may be an unused motor lead from the motor its needs to be capped off The board is also wired to handle either 24v or 120v control wiring To use 24v remove jumpers on the control board For your 24v hot water control valve wire it in series with th...

Страница 6: ... N A N A N A N A N A 2 2 1 5 9 4 8 3 12 11 15 15 3 3 2 3 13 6 11 9 17 15 20 15 4 4 3 0 17 8 15 5 23 20 25 20 5 5 3 8 21 9 19 1 28 24 30 25 6 6 4 5 26 1 22 7 33 29 35 30 8CWE 0 0 0 0 1 7 N A N A N A N A N A 3 3 2 3 14 2 12 5 18 16 20 20 4 4 3 0 18 4 16 1 23 21 25 25 5 5 3 8 22 5 19 7 29 25 30 25 6 6 4 5 26 7 23 5 34 30 35 30 8 8 6 0 35 0 30 5 44 39 50 40 10CWE 0 0 0 0 2 7 N A N A N A N A N A 3 3 2 ...

Страница 7: ...eringtobronzeorbrass heatthepiping while in the socket cup and begin introducing the solder when the flux boils rapidly Avoid direct flame into the solder joint Heat can only be applied to the cup of the valve body for a minimal time before damage occurs even with the use of wet rags Avoid rapid quenching of solder joints as this will produce joints of inferior quality Connect all piping per accepte...

Страница 8: ...ure exists at the drain pan and a minimum trap of 1 1 2 must be provided in the drain line to assure proper drainage Drain connections primary and secondary are 3 4 MPT see Fig 5 for details On units with plastic drain pans the drain connections must be made hand tight only INSTALLATION FIG 5 CWE SERIES WALL CLOSET FAN COILS Chilled Water with Electric Heat CONDENSATE DRAIN CONNECTIONS With drain ...

Страница 9: ...C O thermostat and the TB3 3 TB2 5 jumper is in place the fan will con tinue to operate at the fan speed selected Removing the jumper will cause the fan to shut down when the thermostat is satisfied When using the T200 thermostat the stat will auto matically regulate the fan speed based on the differ ence between the space temp and setpoint 4 F off setpoint the fan will run HI 3 F off setpoint the ...

Страница 10: ...e the air and heating capacities of the unit When the filters are excessively dirty the unit heating capacity will be so reduced that it is in effective for heating the room When a room fails to heat always check the filters To ensure proper maintenance of the filters it is best to follow an organized maintenance procedure The following one is recommended Divide the total number of units on the job i...

Страница 11: ...11 JOHNSON CONTROLS FORM 115 20 NOM6 1106 This Page Intentionally Left Blank ...

Страница 12: ...ture from accumulating in the bearings See Form 50 20 NM3 Long Term Storage Installer has cleaned out interior Ensure drain pan free from foreign material Ensure air filters are clean installed properly and secured Use the directional arrows or other information on the filter to determine the proper flow direction INSTALL CHECKLIST Equipment received as ordered Unit checked for damage interior and ex...

Отзывы: