Subcooling

Check  liquid  subcooling  at  steady  full  compressor 

load  only.  It  is  important  that  all  fans  are  running 

for  the  system.  Measure  liquid  line  temperature  on 

the copper line at the main liquid line service valve.  

Measure liquid pressure at the liquid line service valve.  

Subcooling should be 

5 - 7°F (2.77 - 3.88°C)

YCIV

 

0157 & 0590 subcooling should be 10

°F (5.55°C). 

No 

bubbles should show in the sight glass. If subcooling 

is out of range, add or remove refrigerant as required 

to  clear  the  sight  glass.  Do  not  overcharge  the  unit. 

Subcooling should be checked with a flash tank level 

of approximately 35% with a clear sight glass.

general Operation 

After  completion  of  the  above  checks  for  System  1, 

switch  OFF  the  ‘SYS  1’  switch  on  the  keypad  and 

repeat the process for each subsequent system. When 

all  run  correctly,  stop  the  unit,  switch  all  applicable 

switches to the ‘ON’ position and restart the unit.

Assure all checks are completed in the EQUIPMENT 

START-UP CHECK SHEET. The chiller is then ready 

to be placed into operation.

Содержание YCIV 0590-1500 50Hz

Страница 1: ...enser coils with the full operating charge as given in the Technical Data Section Service and Oil Line Valves Open each compressor suction economizer and discharge service valve If valves are of the b...

Страница 2: ...ore placing the unit back in service valves should be opened and power must be switched on if power is removed for more than 8 hours for at least 8 hours 24 hours if ambient temperature is below 86 F...

Страница 3: ...igerant will be seen in the liquid line sight glass After several minutes of operation and provided a full charge of refrigerant is in the system the bubbles will disappear and be replaced by a solid...

Страница 4: ...the sight glass If subcooling is out of range add or remove refrigerant as required to clear the sight glass Do not overcharge the unit Subcooling should be checked with a flash tank level of approxim...

Страница 5: ...roperly charged and there are no piping leaks 4 Open each system suction service valve discharge service valve economizer service valve liquid line stop valve and oil line ball valve 5 The oil separat...

Страница 6: ...s the cooler Excessive flow may cause catastrophic damage to the evaporator 7 Check the control panel to ensure it is free of foreign material wires metal chips tools documents etc 8 Visually inspect...

Страница 7: ...using the arrow keys scroll to the compressor overload settings Verify the Fac tory Set overload potentiometer s on the VSD logic board are set correctly In the unlikely event that they are not set c...

Страница 8: ...CONTACT YORK REPRESENTATIVE Programmed Values 10 Program the required operating values into the micro for cutouts safeties etc and record them in the chart below Suction Press Cutout _________________...

Страница 9: ...Daily Schedule start and stop times 14 Place the panel in Service mode and turn on each fan stage one by one Assure the fans rotate in the correct direction so air flow exits the top of the chiller 1...

Страница 10: ...entering the compressor and the temperature corresponding to the suction pressure as shown in a standard pressure temperature chart SUPERHEAT Example Suction Temp 46 F 8 C minus Suction Press 30 PSIG...

Страница 11: ...FORM 201 23 CL1 309 JOHNSON CONTROLS 11 notes...

Страница 12: ...861 1001 www york com P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by Johnson Controls 2009 ALL RIGHTS RESERVED Form 201 23 CL1 309 Supersede...

Отзывы: