YORK INTERNATIONAL
8
OPTIONAL SINGLE POINT POWER SUPPLY CONNECTION TO FACTORY CIRCUIT BREAKER
(One Field Provided Power Supply Circuit to the chiller. Field Connection to Circuit Breaker in Option Panel.
No internal Branch Circuit Protection per Motor Control Center.)
FIELD SUPPLIED WIRING
SYSTEM #1
SYSTEM #2
MODEL
VOLTS
MCA
1
FACTORY SUPPLIED BREAKER
COMPRESSOR
FANS
COMPRESSOR
FANS
YCAS
RATING
2
WIRE RANGE
7
(LUGS)
RLA
X-LRA
FLA (EA)
RLA
X-LRA
FLA (EA)
0130EC
460
273
400
(2) 3/0-250
107
579
4.0
107
579
4.0
575
217
250
# 6 AWG - 350
86
463
3.1
86
463
3.1
0140EC
460
293
400
(2) 3/0-250
116
579
4.0
116
579
4.0
575
234
400
(2) 3/0-250
93
463
3.1
93
463
3.1
0150EC
460
307
400
(2) 3/0-250
128
856
4.0
115
579
4.0
575
246
400
(2) 3/0-250
103
715
3.1
92
463
3.1
0160EC
460
320
400
(2) 3/0-250
128
856
4.0
128
856
4.0
575
257
400
(2) 3/0-250
103
715
3.1
103
715
3.1
0170EC
460
335
400
(2) 3/0-250
140
856
4.0
128
856
4.0
575
268
400
(2) 3/0-250
112
715
3.1
103
715
3.1
0180EC
460
347
400
(2) 3/0-250
140
856
4.0
140
856
4.0
575
277
400
(2) 3/0-250
112
715
3.1
112
715
3.1
0200EC
460
375
630
(3) 2/0-400
149
856
4.0
149
856
4.0
575
299
400
(2) 3/0-250
119
715
3.1
119
715
3.1
0210EC
460
393
630
(3) 2/0-400
163
856
4.0
149
856
4.0
575
313
400
(2) 3/0-250
130
715
3.1
119
715
3.1
0230EC
460
407
630
(3) 2/0-400
163
856
4.0
163
856
4.0
575
324
400
(2) 3/0-250
130
715
3.1
130
715
3.1
NOTES
(pages 2 - 7)
1. Minimum circuit ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all
other loads included in the circuit, per N.E.C. Article 430-24. If a Factory Mounted Control Transformer is provided, add the following to
the system #2 MCA values in the YCAS Tables: -17, add 10 amps; -28, add 9 amps; -40, add 5 amps; -46, add 4 amps; -58, add 3 amps.
2. The recommendation disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the
circuit, per N.E.C. 440 - 12A1.
3. Minimum fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs (U.L. Standard 1995, Section 36.1).
Minimum fuse rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
4. Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit,
per N.E.C. 440-22. Maximum fuse rating = (2.25 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
5. Minimum circuit breaker is 150% maximum plus 100% of rated load amps included in the circuit, per circuit per U.L. 1995 Fig. 36.2.
Minimum circuit breaker rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).
6. Maximum circuit breaker is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit, per
U.L. 1995 Fig. 36.2. Maximum circuit breaker rating = (2.25 x largest compressor RLA) + other compressor RLAs + ( # fans x each fan
motor FLA).
7. The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs. The (1), (2), or (3)
indicate the number of termination points or lugs which are available per phase. Actual wire size and number of wires per phase must be
determined based on ampacity and job requirements using N.E.C. wire sizing information. The above recommendations are based on the
National Electric Code and using copper connectors only. Field wiring must also comply with local codes.
8. A ground lug is provided for each compressor system to accommodate field grounding conductor per N.E.C. Article 250-54. A control
circuit grounding lug is also supplied. Incoming ground wire range is #6 - 350 MCM.
9. The field supplied disconnect is a Disconnecting Means as defined in N.E.C. 100.B, and is intended for isolating the unit from the
available power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.
10. Units equipped with Star-Delta compressor motor start must also include Factory provided circuit breakers in each motor control center.
11. The wiring recommendations are based on the National Electrical Code using copper connectors only. Field wiring must also comply with
local codes.
NOTE: Wye-Delta Compressor Start not available with this option.
ELECTRICAL DATA (Continued)
Содержание YCAS0130
Страница 11: ...FORM 201 18 W1 11 YORK INTERNATIONAL LD03228 WIRING DIAGRAM ACROSS THE LINE START...
Страница 12: ...YORK INTERNATIONAL 12 FIG 1 CONTINUED ELEMENTARY DIAGRAM...
Страница 15: ...FORM 201 18 W1 15 YORK INTERNATIONAL WIRING DIAGRAM WYE DELTA START LD03229...
Страница 16: ...YORK INTERNATIONAL 16 FIG 1 CONTINUED ELEMENTARY DIAGRAM...
Страница 18: ...YORK INTERNATIONAL 18...
Страница 19: ...FORM 201 18 W1 19 YORK INTERNATIONAL LD03280...
Страница 20: ...YORK INTERNATIONAL 20 LEGEND LD03281...
Страница 21: ...FORM 201 18 W1 21 YORK INTERNATIONAL LD03282 LD03283 LD03284...
Страница 22: ...YORK INTERNATIONAL 22 CONNECTION DIAGRAM SYSTEM WIRING LD03230 LD03231 LD03232...
Страница 23: ...FORM 201 18 W1 23 YORK INTERNATIONAL COMPRESSOR TERMINAL BOX LD03233...
Страница 27: ...FORM 201 18 W1 27 YORK INTERNATIONAL LD03286...