York YCAS0130 Скачать руководство пользователя страница 8

YORK INTERNATIONAL

8

OPTIONAL SINGLE POINT POWER SUPPLY CONNECTION TO FACTORY CIRCUIT BREAKER

(One Field Provided Power Supply Circuit to the chiller.  Field Connection to Circuit Breaker in ‘Option Panel’.

No internal Branch Circuit Protection per Motor Control Center.)

FIELD SUPPLIED WIRING

SYSTEM #1

SYSTEM #2

MODEL

VOLTS

MCA

1

FACTORY SUPPLIED BREAKER

COMPRESSOR

FANS

COMPRESSOR

FANS

YCAS

RATING

2

WIRE RANGE

7

 (LUGS)

RLA

X-LRA

FLA (EA)

RLA

X-LRA

FLA (EA)

0130EC

460

273

400

(2) 3/0-250

107

579

4.0

107

579

4.0

575

217

250

# 6 AWG - 350

86

463

3.1

86

463

3.1

0140EC

460

293

400

(2) 3/0-250

116

579

4.0

116

579

4.0

575

234

400

(2) 3/0-250

93

463

3.1

93

463

3.1

0150EC

460

307

400

(2) 3/0-250

128

856

4.0

115

579

4.0

575

246

400

(2) 3/0-250

103

715

3.1

92

463

3.1

0160EC

460

320

400

(2) 3/0-250

128

856

4.0

128

856

4.0

575

257

400

(2) 3/0-250

103

715

3.1

103

715

3.1

0170EC

460

335

400

(2) 3/0-250

140

856

4.0

128

856

4.0

575

268

400

(2) 3/0-250

112

715

3.1

103

715

3.1

0180EC

460

347

400

(2) 3/0-250

140

856

4.0

140

856

4.0

575

277

400

(2) 3/0-250

112

715

3.1

112

715

3.1

0200EC

460

375

630

(3) 2/0-400

149

856

4.0

149

856

4.0

575

299

400

(2) 3/0-250

119

715

3.1

119

715

3.1

0210EC

460

393

630

(3) 2/0-400

163

856

4.0

149

856

4.0

575

313

400

(2) 3/0-250

130

715

3.1

119

715

3.1

0230EC

460

407

630

(3) 2/0-400

163

856

4.0

163

856

4.0

575

324

400

(2) 3/0-250

130

715

3.1

130

715

3.1

NOTES

 (pages 2 - 7)

1. Minimum circuit ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all

other loads included in the circuit, per N.E.C. Article 430-24.  If a Factory Mounted Control Transformer is provided, add the following to

the system #2 MCA values in the YCAS Tables: -17, add 10 amps; -28, add 9 amps; -40, add 5 amps; -46, add 4 amps; -58, add 3 amps.

2. The recommendation disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the

circuit, per N.E.C. 440 - 12A1.

3. Minimum fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs (U.L. Standard 1995, Section 36.1).

Minimum fuse rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).

4. Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit,

per N.E.C. 440-22.  Maximum fuse rating  = (2.25 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).

5. Minimum circuit breaker is 150% maximum plus 100% of rated load amps included in the circuit, per circuit per U.L. 1995 Fig. 36.2.

Minimum circuit breaker rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).

6. Maximum circuit breaker is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit, per

U.L. 1995 Fig. 36.2.  Maximum circuit breaker rating = (2.25 x largest compressor RLA) + other compressor RLAs + ( # fans x each fan

motor FLA).

7. The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs.  The (1), (2), or (3)

indicate the number of termination points or lugs which are available per phase.  Actual wire size and number of wires per phase must be

determined based on ampacity and job requirements using N.E.C. wire sizing information.  The above recommendations are based on the

National Electric Code and using copper connectors only.  Field wiring  must also comply with local codes.

8. A ground lug is provided for each compressor system to accommodate field grounding conductor per N.E.C. Article 250-54.  A control

circuit grounding lug is also supplied.  Incoming ground wire range is #6 - 350 MCM.

9. The field supplied disconnect is a “Disconnecting Means” as defined in N.E.C. 100.B, and is intended for isolating the unit from the

available power supply to perform maintenance and troubleshooting.  This disconnect is not intended to be a Load Break Device.

10. Units equipped with Star-Delta compressor motor start must also include Factory provided circuit breakers in each motor control center.
11. The wiring recommendations are based on the National Electrical Code using copper connectors only. Field wiring must also comply with

local codes.

NOTE:  Wye-Delta Compressor Start not available with this option.

ELECTRICAL DATA (Continued)

Содержание YCAS0130

Страница 1: ...WIRING DIAGRAM Millennium TM AIR COOLED SCREW LIQUID CHILLERS STYLE F Supersedes 201 18 W1 798 Form 201 18 W1 1298 28971A r MODELS YCAS0130 THRU YCAS0230...

Страница 2: ...ntenance of the equipment and is are familiar with its potential hazards Shut off power supply to equipment before beginning work and follow lockout procedures When working inside equipment with power...

Страница 3: ...unit YORK Chiller YC YORK Chiller Air Cooled Compressor Type S Screw Nominal Capacity Unit Designator S Standard Unit E High Efficiency Design Series Type Start Y Star WYE Delta X Across the Line Volt...

Страница 4: ...50 2 3 0 250 155 360 1081 4 8 460 176 200 225 350 225 350 2 300 6 AWG 350 6 AWG 350 128 285 856 4 0 575 141 150 175 250 175 250 2 4 0 6 AWG 350 6 AWG 350 103 238 715 3 1 200 434 600 600 800 600 800 2...

Страница 5: ...2 4 0 6 AWG 350 6 AWG 350 103 238 715 3 1 200 402 400 500 700 500 700 2 1 500 2 3 0 250 3 2 0 400 295 656 1969 8 2 230 351 400 450 700 450 700 2 2 300 2 3 0 250 3 2 0 400 256 571 1712 7 8 0170EC 380...

Страница 6: ...40 3 2 0 400 800 0160EC 380 387 600 450 600 450 600 2 1 500 760 3 2 0 400 600 460 320 400 400 450 400 450 2 2 300 550 2 3 0 250 400 575 257 400 300 400 300 400 1 500 380 2 3 0 250 400 200 762 800 1000...

Страница 7: ...5 856 4 0 250 128 285 856 4 0 575 250 103 238 715 3 1 250 103 238 715 3 1 200 600 321 656 1969 8 2 600 295 656 1969 8 2 230 600 279 571 1712 7 8 600 256 571 1712 7 8 0170EC 380 400 169 360 1081 4 8 40...

Страница 8: ...d 1995 Section 36 1 Minimum fuse rating 1 5 x largest compressor RLA other compressor RLAs fans x each fan motor FLA 4 Maximum dual element fuse size is based on 225 maximum plus 100 of the rated load...

Страница 9: ...CAS MCA1 MIN NF D E FUSE TERMINAL BLOCK NF SERV DISC SW DATA DATA DATA DATA DISC SW2 MIN3 MAX4 LUGS WIRE RANGE7 RATING2 LUGS WIRE RANGE7 RLA X LRA FLA EA RLA X LRA FLA EA 0130EC 460 273 400 300 400 1...

Страница 10: ...tions on the following page 5 To stop unit Emergency Stop with contacts other than those shown install the stop contact between 5 and 1 If a stop device is not installed a jumper must be connected bet...

Страница 11: ...FORM 201 18 W1 11 YORK INTERNATIONAL LD03228 WIRING DIAGRAM ACROSS THE LINE START...

Страница 12: ...YORK INTERNATIONAL 12 FIG 1 CONTINUED ELEMENTARY DIAGRAM...

Страница 13: ...e relay contactor coil Any contacts connected to flow switch inputs or BAS inputs on terminals 13 19 or TB3 or any other terminals must be sup pressed with a YORK P N 031 00808 000 suppressor across t...

Страница 14: ...tions on the following page 5 To stop unit Emergency Stop with contacts other than those shown install the stop contact between 5 and 1 If a stop device is not installed a jumper must be connected bet...

Страница 15: ...FORM 201 18 W1 15 YORK INTERNATIONAL WIRING DIAGRAM WYE DELTA START LD03229...

Страница 16: ...YORK INTERNATIONAL 16 FIG 1 CONTINUED ELEMENTARY DIAGRAM...

Страница 17: ...e relay contactor coil Any contacts connected to flow switch inputs or BAS inputs on terminals 13 19 or TB3 or any other terminals must be sup pressed with a YORK P N 031 00808 000 suppressor across t...

Страница 18: ...YORK INTERNATIONAL 18...

Страница 19: ...FORM 201 18 W1 19 YORK INTERNATIONAL LD03280...

Страница 20: ...YORK INTERNATIONAL 20 LEGEND LD03281...

Страница 21: ...FORM 201 18 W1 21 YORK INTERNATIONAL LD03282 LD03283 LD03284...

Страница 22: ...YORK INTERNATIONAL 22 CONNECTION DIAGRAM SYSTEM WIRING LD03230 LD03231 LD03232...

Страница 23: ...FORM 201 18 W1 23 YORK INTERNATIONAL COMPRESSOR TERMINAL BOX LD03233...

Страница 24: ...YORK INTERNATIONAL 24 MULTI POINT POWER SUPPLY WIRING STANDARD UNIT LD03254 SINGLE POINT POWER SUPPLY WIRING WITH CIRCUIT BREAKERS LD03255...

Страница 25: ...FORM 201 18 W1 25 YORK INTERNATIONAL SINGLE POINT POWER WIRING WITH FIELD SUPPLIED CIRCUIT PROTECTION LD03256 SINGLE POINT POWER WIRING WITH CIRCUIT BREAKERS LD03257...

Страница 26: ...ORK INTERNATIONAL 26 ELECTRICAL POWER WIRING OPTIONS NON FUSED DISCONNECT SWITCH ELECTRICAL POWER WIRING OPTIONS TERMINAL BLOCKS LD03258 LD03259 ELECTRICAL POWER WIRING OPTIONS TERMINAL BLOCKS LD03260...

Страница 27: ...FORM 201 18 W1 27 YORK INTERNATIONAL LD03286...

Страница 28: ...1592 Y ork Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by York International Corporation 1998 ALL RIGHTS RESERVED Form 201 18 W1 1298 Supersedes 201 18 W1 798...

Отзывы: