Programming of the Cooling Setpoints, Daily Schedule,
and Safeties is accomplished by using the keys located
under the Setpoints section.
The three keys involved are labeled COOLING
SETPOINTS, SCHEDULE/ADVANCE DAY, and
PROGRAM.
Following are instructions for programming the
respective setpoints. The same instruction should be
used to view the setpoints with the exception that the
setpoint will not be changed.
Cooling Setpoints
The Cooling Setpoint and range can be programmed by
pressing the COOLING SETPOINTS key.
SETPOINTS KEYS
00069VIP
Leaving Chilled Liquid Control
S E T P O I N T = 4 5 . 0 ° F
R A N G E = +/- 2 . 0 ° F
The above message shows the current chilled water
temperature SETPOINT at 45.0°F (notice the cursor
positioned under the number 0). Pressing either the
↑
(UP) and ↓ (DOWN)
arrow will change the setpoint in
0.5°F increments. After using the
↑ (UP) and ↓ (DOWN)
arrows to adjust to the desired setpoint, the ENTER/
ADV key must be pressed to enter this number into
memory and advance to the RANGE setpoint.
This will be indicated by the cursor moving under the
current RANGE setpoint. The
↑ (UP) and ↓ (DOWN)
arrow keys are used to set the range, in .5°F increments,
to the desired RANGE setpoint. After adjusting the
setpoint, the ENTER/ADV key must be pressed to enter
the data into memory.
Содержание YCAL0014E Series
Страница 4: ...JOHNSON CONTROLS 4 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 10: ...JOHNSON CONTROLS 10 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 18: ...JOHNSON CONTROLS 18 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 31: ...JOHNSON CONTROLS 31 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 126: ...JOHNSON CONTROLS 126 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 140: ...JOHNSON CONTROLS 140 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 155: ...JOHNSON CONTROLS 155 FORM 150 62 NM8 1020 5 6 ...
Страница 157: ...JOHNSON CONTROLS 157 FORM 150 62 NM8 1020 5 6 LD08855 ...
Страница 161: ...JOHNSON CONTROLS 161 FORM 150 62 NM8 1020 161 5 6 ...
Страница 163: ...JOHNSON CONTROLS 163 FORM 150 62 NM8 1020 5 6 ...
Страница 167: ...JOHNSON CONTROLS 167 FORM 150 62 NM8 1020 5 6 ...
Страница 169: ...JOHNSON CONTROLS 169 FORM 150 62 NM8 1020 5 6 ...
Страница 171: ...JOHNSON CONTROLS 171 FORM 150 62 NM8 1020 5 6 ...
Страница 173: ...JOHNSON CONTROLS 173 FORM 150 62 NM8 1020 5 6 ...
Страница 175: ...JOHNSON CONTROLS 175 FORM 150 62 NM8 1020 5 6 ...
Страница 177: ...JOHNSON CONTROLS 177 FORM 150 62 NM8 1020 5 6 ...
Страница 181: ...JOHNSON CONTROLS 181 FORM 150 62 NM8 1020 5 6 ...
Страница 183: ...JOHNSON CONTROLS 183 FORM 150 62 NM8 1020 5 6 LD08833 ...
Страница 185: ...JOHNSON CONTROLS 185 FORM 150 62 NM8 1020 5 6 ...
Страница 187: ...JOHNSON CONTROLS 187 FORM 150 62 NM8 1020 5 6 ...
Страница 189: ...JOHNSON CONTROLS 189 FORM 150 62 NM8 1020 5 6 ...
Страница 191: ...JOHNSON CONTROLS 191 FORM 150 62 NM8 1020 5 6 ...
Страница 195: ...JOHNSON CONTROLS 195 FORM 150 62 NM8 1020 5 6 ...
Страница 197: ...JOHNSON CONTROLS 197 FORM 150 62 NM8 1020 5 6 ...
Страница 199: ...JOHNSON CONTROLS 199 FORM 150 62 NM8 1020 5 6 ...
Страница 200: ...JOHNSON CONTROLS 200 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 211: ...JOHNSON CONTROLS 211 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...