JOHNSON CONTROLS
6
Dimensions -
YCAL0064-YCAL0080 (SI)
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit
is no higher than on spring isolators. Recommended minimum clearances: Side to wall – 2m; rear to wall – 2m; control panel to end wall
– 1.2m; top – no obstructions allowed; distance between adjacent units – 3m. No more than one adjacent wall may be higher than the
unit.
LD04878
2311
759 (EDGE OF
UNIT TO COOLER
CONNECTION)
403
VIEW A-A
51
38
76
321
127
127
76
38
76
CONTROL ENTRY
(8) 13 CONDUIT K.O.'S
98
25 TYP.
B
B
VIEW B-B
POWER ENTRY
(2) 64,51,38 CONDUIT K.O.'S
(5) 13 CONDUIT K.O.'S
102
NOTE:
All dimensions are in mm unless specified otherwise.
HFC-407c for YCAL0064 and YCAL0070 models only