2.2 Start-up data
Electrical data
Rating plate
Actual
Power supply
Check specifica‐
tions in the Installa‐
tion Manual
Control voltage
Fan consumption (A)
Consumption of condenser fan 1 (A)
Consumption of condenser fan 2 (A)
Consumption of compressor 1 (A)
Consumption of compressor 2 (A)
Consumption of supply fan (A)
Heating element 1 (Optional)
Heating element 2 (Optional)
Cool and heat modes
Cooling circuit. Compressor 1
Mode
Value
Subcooling (min. 8 K, max. 18 K)
°C
Liquid pressure: _____ bar
Liquid temperature: _____ °C
Overheating (min. 4 K, max. 10 K)
°C
Suction pressure: _____ bar
Suction temperature: _____ °C
Complete liquid line checked in sight glass
Correct oil level checked in sight glass
Cooling circuit. Compressor 2
Mode
Value
Subcooling (min. 8 K, max. 18 K)
°C
Liquid pressure: _____ bar
Liquid temperature: _____ °C
Overheating (min. 4 K, max. 10 K)
°C
Suction pressure: _____ bar
Suction temperature: _____ °C
Complete liquid line checked in sight glass
Correct oil level checked in sight glass
Air flow rate values
m
3
/h
Design
Measured
2
Unit installation data
2.2
Start-up data
26