FILTER PERFORMANCE

The airflow capacity data published in the “Blower Perfor-
mance” table shown represents blower performance WITHOUT
filters.

All applications of these furnaces require the use of field

installed air filters. All filter media and mounting hardware or
provisions must be field installed external to the furnace cabi-
net. DO NOT attempt to install any filters inside the furnace.

1. Air velocity through throwaway type filters may not exceed 300 feet per min-

ute (91.4 m/min). All velocities over this require the use of high velocity fil-
ters.

2. Do not exceed 1800 CFM using a single side return and a 16x25 filter. For 

CFM greater than 1800, you may use two side returns or one side and the 
bottom or one return with a transition to allow use of a 20x25 filter.

*

- 24" clearance in front and 18" on side recommended for service 
access.

All furnaces approved for alcove and attic installation.

ACCESSORIES

Propane (LP) Conversion Kit - 

This accessory conversion kit

may be used to convert natural gas (N) units for propane (LP)
operation.

S1-1NP0347 - All Models

Concentric Vent Termination -

 For use through rooftop, side-

wall. Allows combustion air to enter and exhaust to exit through
single common hole. Eliminates unsightly elbows for a cleaner
installation.

S1-1CT0302 (2") & S1-1CT0302-636 (2")
S1-1CT0303 (3") & S1-1CT0303-636 (3")

Sidewall Vent Termination Kit - 

For use on sidewall, two-pipe

installations only. Provide a more attractive termination for loca-
tions where the terminal is visible on the side of the home.
S1-1HT0901 (3")
S1-1HT0902 (2")

Condensate Neutralizer Kit - 

Neutralizer cartridge has a 1/2

plastic tube fittings for installation in the drain line. Calcium car-
bonate refill media is also available from the Source 1 Parts 
(P/N S1-02630228000).

S1-1NK0301

Side Return Filter Racks - 

S1-1SR0200 - All Models
S1-1SR0402 - All Models

Bottom Return Filter Racks - 

1BR05xx series are galvanized

steel filter racks. 1BR06xx are pre-painted steel filter racks to
match the appearance of the furnace cabinet.

S1-1BR0514 or 1BR0614 - For 14-1/2” cabinets
S1-1BR0517 or 1BR0617 - For 17-1/2” cabinets
S1-1BR0521 or 1BR0621 - For 21” cabinets
S1-1BR0524 or 1BR0624 - For 24-1/2” cabinets

Combustible Floor Base Kit -

 For installation of these fur-

naces in downflow applications directly onto combustible floor-
ing material, These kits are required to prevent potential
overheating situations.tible floor base kit provides access for
combustible airflow.

S1-1CB0514 - For 14-1/2” cabinets
S1-1CB0517 - For 17-1/2” cabinets
S1-1CB0521 - For 21” cabinets
S1-1CB0524 - For 24-1/2” cabinets

High Altitude Pressure Switches - 

For installation where the

altitude is less than 5,000 feet it is not required that the pres-
sure switch be changed. For altitudes above 5,000 feet, see kits
below.

S1-1PS3308 - All Models

Thermostats 

- Compatible thermostat controls are available

through accessory sourcing.

EXTERNAL STATIC PRESSURE SETUP

Set appropriate airflow per temperature rise for gas heating. Set
appropriate airflow per “Blower Performance CFM” table for
cooling/heat pump heating operating based on outdoor unit
size.

To measure external static pressure:

Measure the supply air static pressure

Record this positive number

Measure the return air static pressure

Record this negative number

Treat the negative number as a positive and add the two
numbers together

This is total system static

NOTICE

Single side return above 1800 CFM is approved as long as
the filter velocity does not exceed filter manufacturer’s rec-
ommendation and a transition is used to allow use on a
20x25 filter.

Recommended Filter Sizes (High velocity 600 FPM)

CFM

Cabinet

Size

Side

(in)

Bottom

(in)

1000

A

16 x 25

14 x 25

1200

B

16 x 25

16 x 25

1600

C

16 x 25

20 x 25

2000

C

(2) 16 x 25

20 x 25

2000

D

(2) 16 x 25

22 x 25

Unit Clearances to Combustibles

Application

Upflow

Downflow

Horizontal

Top

1" 0" 0" 

Vent

0" 0" 0" 

Rear

0" 0" 0" 

Side

0" 0" 1" 

Front*

0" 0" 0" 

Floor

Combustible

Combustible

1

1. For combustible floors only when used with special sub-base.

Combustible

Closet

Yes

Yes

Yes

Line Contact

No

No

Yes

Supply Duct

Return

Duct

Содержание TM9Y120D20MP11

Страница 1: ...timer allows two stage operation with a single stage thermostat Easily applied in upflow horizontal left or right or downflow installation with minimal conversion necessary Compact easy to install ideal height 33 tall cabinet Standard ECM constant torque drive for cooling SEER enhancement improved comfort with optional airflow delay profiles and continuous fan options for IAQ performance Easy acce...

Страница 2: ...13 3 8 11 3 4 113 TM9Y060B12MP11 1200 B 17 1 2 16 3 8 13 1 4 119 TM9Y080B12MP11 1200 B 17 1 2 16 3 8 14 3 4 123 TM9Y080C16MP11 1600 C 21 19 7 8 16 1 2 130 TM9Y100C16MP11 1600 C 21 19 7 8 18 1 4 136 TM9Y100C20MP11 2000 C 21 19 7 8 18 1 4 143 TM9Y120D20MP11 2000 D 24 1 2 23 3 8 21 3 4 154 Ratings Physical Electrical Data Model Input High Low Output High Low Total Unit AFUE High Fire Air Temp Rise Lo...

Страница 3: ...ter racks 1BR06xx are pre painted steel filter racks to match the appearance of the furnace cabinet S1 1BR0514 or 1BR0614 For 14 1 2 cabinets S1 1BR0517 or 1BR0617 For 17 1 2 cabinets S1 1BR0521 or 1BR0621 For 21 cabinets S1 1BR0524 or 1BR0624 For 24 1 2 cabinets Combustible Floor Base Kit For installation of these fur naces in downflow applications directly onto combustible floor ing material The...

Страница 4: ...7 1128 1097 1069 1013 Medium 1098 1084 1059 1027 998 967 939 910 879 822 Medium Low 1012 993 953 930 894 851 828 773 752 692 Low 865 810 763 730 689 628 594 520 496 448 80C High 1713 1682 1643 1600 1558 1519 1480 1436 1385 1333 Medium High 1554 1519 1485 1439 1404 1368 1327 1280 1176 1130 Medium 1380 1351 1302 1263 1224 1171 1128 1085 1030 943 Medium Low 1177 1142 1083 1050 988 922 890 819 798 687...

Отзывы: