Table 19:
Air Flow Data
HIGH / LOW SPEED COOLING AND HEAT PUMP CFM
040A10
060B12
080B12
Jumper Settings
High
Low
High
Low
High
Low
COOL Tap
ADJ Tap*
1080
750
1343
865
1320
882
A
B
960
680
1116
727
1093
755
B
B
980
690
1235
791
1203
810
A
A
870
620
1026
661
1001
693
B
A
890
620
1079
709
1080
730
A
C
770
550
889
590
880
641
C
B
790
560
900
599
910
642
B
C
650
480
787
531
803
585
D
B
700
500
814
542
836
597
C
A
590
440
712
490
738
557
D
A
640
450
725
499
749
561
C
C
540
400
641
456
682
529
D
C
080C16
100C16
100C20
Jumper Settings
High
Low
High
Low
High
Low
COOL Tap
ADJ Tap*
1787
1171
1818
1192
2019
1290
A
B
1503
987
1545
1030
1790
1174
B
B
1620
1053
1661
1083
1818
1195
A
A
1405
914
1427
936
1630
1068
B
A
1462
964
1497
991
1649
1082
A
C
1217
785
1234
819
1269
848
C
B
1245
818
1265
832
1432
956
B
C
940
608
977
648
1078
704
D
B
1091
702
1116
728
1169
770
C
A
852
551
884
572
986
638
D
A
983
626
1019
666
1062
685
C
C
764
544
791
519
866
576
D
C
120D20
Jumper Settings
High
Low
COOL Tap
ADJ Tap*
2006
1397
A
B
1687
1131
B
B
1845
1282
A
A
1552
1050
B
A
1694
1157
A
C
1502
1011
C
B
1400
944
B
C
1365
922
D
B
1364
931
C
A
1232
808
D
A
1225
808
C
C
1117
718
D
C
HIGH / LOW HEAT CFM
040A10
060B12
80B12
Jumper Settings
High
Low
High
Low
High
Low
HEAT Tap
ADJ Tap*
960
670
1364
843
1433
945
A
Any
840
590
1253
745
1320
887
B
Any
740
520
1102
660
1223
840
C
Any
640
450
1014
607
1134
768
D
Any
80C16
100C16
100C20
Jumper Settings
High
Low
High
Low
High
Low
HEAT Tap
ADJ Tap*
1684
1095
1803
1182
2194
1417
A
Any
1542
1011
1686
1084
1999
1290
B
Any
1426
927
1530
1016
1799
1182
C
Any
1289
832
1427
936
1614
1062
D
Any
120D20
Jumper Settings
High
Low
HEAT Tap
ADJ Tap*
1937
1323
A
Any
1757
1199
B
Any
1594
1062
C
Any
1429
957
D
Any
All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to 0.6”
w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c. external
static pressure is not recommended.
NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower that what is required to operate an airflow switch on certain models of electronic air
cleaners. Consult the instructions for the electronic air cleaner for further details.
* The ADJ “D” tap should not be used.