036-21121-002 Rev. A (0602)
Unitary Products Group
9
Multipliers for determining the performance with other indoor sections.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
H1RA018S06
INDOOR COIL MODEL NO.
G1FA024S14,17
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
550
650
750
ID DB (°F)
85
80
70
85
80
70
85
80
70
ID WB (°F)
72
67
57
72
67
57
72
67
57
75
T.C.
20.6
19.7
18.1
20.7
19.8
18.5
20.8
19.8
18.9
S.C.
12.7
12.8
12.3
13.3
13.5
13.4
13.7
13.8
14.0
K.W
1.68
1.65
1.64
1.72
1.71
1.70
1.75
1.74
1.73
85
T.C.
20.6
19.3
17.4
20.9
19.6
18.0
21.1
19.8
18.4
S.C.
12.7
12.6
11.9
13.5
13.4
13.1
14.1
14.0
13.8
K.W
1.58
1.54
1.53
1.62
1.59
1.58
1.65
1.63
1.62
95
T.C.
19.0
17.5
15.5
19.5
18.0
16.1
19.8
18.2
16.5
S.C.
12.8
12.4
11.5
13.7
13.3
12.8
14.5
14.1
13.6
K.W
1.97
1.91
1.90
2.02
1.96
1.95
2.05
2.00
1.99
105
T.C.
18.4
16.6
14.2
18.9
17.1
15.0
19.2
17.4
15.4
S.C.
12.5
11.8
10.7
13.6
12.8
12.0
14.4
13.7
12.8
K.W
1.82
1.77
1.75
1.88
1.82
1.80
1.91
1.86
1.83
115
T.C.
16.3
14.5
11.9
16.9
15.0
12.7
17.2
15.2
13.1
S.C.
12.3
11.2
10.0
13.5
12.4
11.2
14.3
13.2
12.0
K.W
2.24
2.19
2.14
2.31
2.24
2.19
2.35
2.28
2.22
125
T.C.
14.3
12.3
9.7
14.9
13.0
10.5
15.2
13.1
10.8
S.C.
12.0
10.6
9.3
13.3
11.9
10.4
14.2
12.8
11.2
K.W
2.66
2.61
2.53
2.74
2.66
2.58
2.79
2.70
2.61
NOTE:
ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM
Air Handler
Coil
T.C.
S.C.
KW
N1AHB0806
G2FD024S17
1.06
1.06
0.99
F2RC/F2FC024
0.97
0.97
0.99
G1FA030S14
1.06
1.06
0.99
G1HD024
1.03
1.03
0.95
G1NA024S17G
1.00
0.94
0.98
G1UA024S14,17
1.00
1.00
1.00
G1UA030S14
1.06
1.06
0.99
G2FD024S14,17
1.06
1.06
0.99
G2FD030S17
1.08
1.08
1.00
G2FD035S14
1.08
1.08
1.00