400034-YTG-B-0708
Johnson Controls Unitary Products
11
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
TCGD12S21S2(H)
INDOOR COIL MODEL NO.
FC/MC/PC18
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
450
600
750
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
11.3 11.9 12.1 13.1 14.1 11.7 12.4 12.3 13.2 14.1 12.1 12.9 12.6 13.2 14.1
S.C.
11.1
10.2 9.1 9.0 7.2 11.5
11.0 9.6 9.2 7.4 11.9
11.8
10.0 9.5 7.5
KW
0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
75
T.C.
11.1 11.7 11.7 12.9 13.8 11.6 12.2 12.0 13.0 13.8 12.0 12.7 12.3 13.1 13.9
S.C.
10.9
10.4 9.1 9.0 7.2 11.4
11.2 9.6 9.4 7.4 11.8
11.9
10.1 9.8 7.7
KW
0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
85
T.C.
10.9 11.6 11.4 12.6 13.5 11.4 12.1 11.7 12.8 13.6 11.9 12.6 11.9 13.0 13.7
S.C.
10.7
10.6 9.0 9.0 7.1 11.2
11.3 9.6 9.6 7.5 11.7
12.1
10.3
10.1 7.8
KW
0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
95
T.C.
10.7 11.5 11.1 12.3 13.2 11.2 12.0 11.3 12.6 13.3 11.7 12.4 11.6 12.8 13.4
S.C.
10.5
10.8 9.0 9.0 7.1 11.0
11.5 9.7 9.7 7.5 11.5
12.2
10.4
10.4 7.9
KW
0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9
105
T.C.
10.0 10.9 10.2 11.5 12.5 10.6 11.4 10.5 11.8 12.7 11.1 11.9 10.9 12.0 12.9
S.C.
9.8 10.3 8.6 8.8 6.9 10.4 10.9 9.2 9.5 7.3 11.0 11.5 9.9 10.2 7.8
KW
1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
115
T.C.
9.3 10.3 9.3 10.7 11.9 9.9 10.9 9.7 11.0 12.2 10.5 11.4 10.1 11.3 12.4
S.C.
9.2 9.9 8.2 8.6 6.7 9.8 10.3 8.8 9.3 7.2 10.4
10.8 9.4 10.0 7.6
KW
1.1 1.0 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1
125
T.C.
8.6 9.7 8.4 9.9 11.2 9.3 10.3 8.9 10.2 11.6 9.9 10.9 9.4 10.5 11.9
S.C.
8.5 9.4 7.8 8.4 6.5 9.2 9.8 8.4 9.1 7.0 9.8 10.1 8.9 9.8 7.5
KW
1.1 1.1 1.1 1.2 1.2 1.2 1.1 1.1 1.2 1.2 1.2 1.2 1.1 1.2 1.2
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
–
HC18
1.00 1.00 1.00
–
UC18
1.00 1.00 1.00
AHP18
–
0.98 0.97 0.98