background image

GENERAL

YORK Model DEG units are single package air conditioners with

gas heat designed for outdoor installation on a rooftop or a slab.
The units are completely assembled on rigid, permanently

attached base rails. All piping, refrigerant charge, and

electrical wiring is factory-installed and tested. The units

require only electric power, gas piping and duct connections

at the point of installation.
The gas-fired heaters have aluminized steel tubular heat

exchangers and spark ignition with intermittent pilot.
This appliance is not to be used for temporary heating of

buildings or structures under construction.

INSPECTION

As soon as a unit is received, it should be inspected for possible

damage during transit. If damage is evident, the extent of the

damage should be noted on the carrier's freight bill. A separate

request for inspection by the carrier's agent should be made in

writing. Refer to Form 50.15-NM for additional information.

REFERENCE

Additional information on the design, installation, operation

and service of this equipment is available in the following

reference forms:

55.70-N1

-General Installation

55.70-N2

-Pre-start & Post-start Check List

530.18-N1.2V

-Economizer Accessory

530.18-N1.13V -Man. Outdoor Air Damper Accy 0-35%

530.18-N1.14V -Man. Outdoor Air Damper Accy 0-100%

530.18-N1.12V -Motorized Outdoor Air Damper Accy.

530.18-N1.8V

-Coil Guard

530.18-N2.11V -Low NOx Accessory

530.18-N8.2V

-High Altitude Accy. (Natural Gas)

530.18-N8.3V

-High Altitude Accy. (Propane)

530.18-N8.4V

-Gas Piping Accessory

530.18-N8.12V -Propane Conversion Accessory

690.15-N25V

-Low Ambient Accessory

Renewal Parts:

Refer to Parts Manual for complete listing of replacement

parts on this equipment.

All forms referenced in this instruction may be ordered from:

Standard Register

Toll Free Tel.: 877-318-9675

Fax: 877-379-7920

APPROVALS

Design certified by CGA and  UL listed as follows:

1. For use as a forced air furnace with cooling unit.

2. For outdoor installation only.

3. For installation directly on combustible flooring or, in the U.S.A.,

on wood flooring or Class A, B, or C roof covering material.

4. For use with natural gas and/or propane (LP) gas.

Not suitable for use with conventional venting systems.

SUNLINE PLUS

GAS / ELECTRIC

SINGLE PACKAGE AIR CONDITIONERS

INSTALLATION INSTRUCTION

Supersedes: 035-14832-002-A-0302

035-14832-003-A-0204

MODELS D2EG 048 & 060 and D3EG 036

(11 SEER)

Installer should pay particular attention to the words:

NOTE, CAUTION

and

WARNING

. Notes are intended to clarify or make

the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal in-

jury and/or equipment damage may result if installation procedure is not handled properly.

FOR YOUR SAFETY

Do not store or use gasoline or

other flammable vapors or liquids

in the vicinity of this or any other

appliance

.

If you smell gas:

1. Open windows

2. Don't touch electrical switches.

3. Extinguish any open flame.

4. Immediately call your gas supplier.

CAUTION

THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH THE ENCLOSED INSTALLATION INSTRUC-

TIONS AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMITED TO, BUILDING,

ELECTRICAL, AND MECHANICAL CODES

WARNING

INCORRECT INSTALLATION MAY CREATE A CONDITION WHERE THE OPERATION OF THE PRODUCT COULD

CAUSE PERSONAL INJURY, PROPERTY DAMAGE AND/OR DEATH.

WARNING

DE-ENERGIZE THE ELECTRICAL POWER AND TURN OFF THE GAS SUPPLY TO THE UNIT BEFORE ATTEMPTING TO

INSPECT, REPAIR OR PERFORM MAINTENANCE TO THE UNIT.

Содержание SUNLINE PLUS D2EG 048

Страница 1: ...g of replacement parts on this equipment All forms referenced in this instruction may be ordered from Standard Register Toll Free Tel 877 318 9675 Fax 877 379 7920 APPROVALS Design certified by CGA and UL listed as follows 1 For use as a forced air furnace with cooling unit 2 For outdoor installation only 3 Forinstallationdirectlyoncombustibleflooringor intheU S A on wood flooring or Class A B or ...

Страница 2: ...Air Conditioner Air Cooled PRODUCT IDENTIFIER EG High Efficiency Gas Electric VOLTAGE CODE 06 208 230 1 60 25 208 230 3 60 46 460 3 60 58 575 3 60 NOMINAL GAS HEATING OUTPUT CAPACITY 036 3 Ton 048 4 Ton 060 5 Ton 0 0 3 0 6 2 5 FACTORY INSTALLED HEAT N Natural Gas NOMINAL COOLING CAPACITY 040 40 MBH 060 60 MBH 079 79 MBH 099 99 MBH MAINTENANCE TROUBLESHOOTING Normal Maintenance 17 Cleaning Flue Pas...

Страница 3: ...Do not remove any packaging until the unit is near the place of installation Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails Spreaders whose length exceeds the largest dimension across the unit MUST be used across the top of the unit BEFORE LIFTING A UNIT MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILL LIFT EVENLY Units...

Страница 4: ...sign certified unit Field alteration to comply with electrical codes should not be required A disconnect switch should be field provided for the unit The switch must be separate from all other circuits Refer to Figure 9 for installation location If any of the wire supplied with the unit must be replaced replacement wire must be of the type shown on the wiring diagram Electrical lines must be sized...

Страница 5: ...U N I T H A S A N E C O N O M I Z E R R E M O V E J U M P E R J 1 F R O M T E R M I N A L S 8 A N D 1 0 O N T H E R E L A Y B O A R D T O P R E V E N T S I M U L T A N E O U S O P E R A T I O N O F T H E C O M P R E S S O R A N D T H E E C O N O M I Z E R I F Y O U W A N T T O C O N T R O L T H E R E C O N O M I Z E R O N A S E C O N D S T A G E O F C O O L I N G O R H A V E A N D E L E C T R I C ...

Страница 6: ...that system at test pressures in excess of 1 2 psig 3 48kPa The furnace must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 48kPa 7 A 1 8 inch NPT plugged tapping accessible for test gage connection must be installed immediately upstream of t...

Страница 7: ...er 2 Remove the 1 2 knockout A in the units rear panel located to the right side of the outdoor air opening Insert the two loose wires from inside the unit into the 1 2 bushing provided Insert wires and bushing into knockout Snap bushing into place 3 Mount the outdoor air sensor to the rear panel just below the knockout described in Step 2 Secure with two self drilling screws at dimples B provided...

Страница 8: ...13 5 1 COND FAN PROPELLER DIA in FAN MOTOR HP NOM CFM TOTAL 22 4 500 22 4 200 22 4 500 COND COIL ROWS DEEP FINS PER INCH FACE AREA Sq Ft 2 18 17 1 2 18 17 1 2 18 17 1 AIR FILTERS SEE NOTE QUANTITY PER UNIT 14 x 20 x 1 QUANTITY PER UNIT 14 X 25 X 1 TOTAL FACE AREA sq ft 2 1 6 3 2 1 6 3 2 1 6 3 CHARGE REFRIGERANT 22 lbs oz 9 12 9 8 9 8 COMPRESSOR QUANTITY PER UNIT HERMETIC TYPE 1 RECPT 1 RECPT 1 SCR...

Страница 9: ...53 780 992 815 1034 855 1080 905 NOTE FOR 208 VOLTS MULTIPLY VALUES BY 0 95 INCLUDES ALLOWANCES FOR A WET EVAPORATOR COIL 1 FILTERS AND THE GAS FIRED HEAT EXCHANGERS REFER TO TABLE 8 FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN GAS ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS MODEL DEG AIR FLOW CFM Available External Static Pressure IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM Watts RPM Watts RPM Watt...

Страница 10: ...815 925 850 964 880 1001 910 1600 864 770 908 805 948 835 987 870 1500 882 740 926 780 965 830 5 TON SIDE DUCT CONNECTIONS 230 460 575 Volts MODEL DEG AIR FLOW CFM Available External Static Pressure IWG 0 90 1 00 1 10 1 20 1 30 1 40 1 50 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 060 2500 2400 1193 1665 2300 1170 1580 1202 1620 2200 1148 1480 1180 1530 2100 1121 1385 115...

Страница 11: ...6 3 4 9 135 130 64 52 0 2 3 2 3 1 4 1 4 5 0 5 0 2 2 2 2 38 6 25 7 13 2 11 4 60 40 20 15 60 40 20 15 060 208 230 1 60 208 230 3 60 460 3 60 575 3 60 187 187 414 518 253 253 504 630 32 1 19 3 10 0 7 9 135 150 73 50 2 3 2 3 1 4 1 4 6 6 6 6 3 3 3 3 49 0 33 0 17 2 14 6 80 50 25 20 80 50 25 20 NOTES 1 Utilization Range A in accordance with ARI Standard 110 2 Dual element time delay type TABLE 10 ELECTRI...

Страница 12: ...r motorized Air Damper Left Side Filter Access 24 Less Economizer 36 With Economizer Right Side Cond Coil 24 Below Unit1 20 Above Unit2 72 For Condenser Air Discharge 1 Units may be installed on combustible floors made from wood or class A B or C roof covering material 2 Units must be installed oudoors Overhanging structures or shrubs should not obstruct the outdoor coil nor the fan outlet NOTE A ...

Страница 13: ...lose and the blower motor operates INTERMITTENT BLOWER With the room thermostat system switch set to the AUTO or HEAT position and the fan switch set to AUTO the supply air blower will operate after the room thermostat calls for heat and the air in the gas heat compartment has achieved a pre set temeprature When TH1 on the thermostat closes the draft motor relay DMR or DMC is energized The DMR or ...

Страница 14: ...e same as listed on the unit nameplate 2 Make sure that the vent and combustion air hoods have been properly installed 14 Unitary Products Group 035 14832 003 A 0204 Units Tons Capacity MBH Limit Control Opens F Input Output 3 4 3 4 5 5 50 75 100 125 100 125 40 60 79 99 79 99 165 165 165 165 165 165 TABLE 12 LIMIT CONTROL SETTING OPERATING INSTRUCTIONS CAUTION This furnace is equipped with an inte...

Страница 15: ...red supply air CFM Refer to Table 9 for blower motor and drive data The tension on the belts should be adjusted as shown in Figure 14 Start the supply air blower motor Adjust the resistances in both the supply and the return air duct systems to balance the air distribution throughout the conditioned space The job specifications may require that this balancing be done by someone other than the equi...

Страница 16: ...rom Table 14 If the actual input is not within 5 of the furnace rating with allowance being made for the permissible range of the regulator setting replace the orifice spuds with spuds of the proper size NOTE To find the Btu input multiply the number of cubic feet of gas consumed per hour by the Btu content of the gas in your particular locality contact your gas company for this information it var...

Страница 17: ...harge outlet periodically to make sure that the buildup of soot and dirt is not excessive If necessary clean to maintain adequate combustion air discharge The manufacture recommends that the furnace system be inspected once a year by a qualified service person CLEANING FLUE PASSAGES AND HEATING ELEMENTS With proper combustion adjustment the heating element of a gas fired furnace will seldom need c...

Страница 18: ... DMC is pulled in d If the DMR or DMC relay is pulled in check for a loose line voltage connection e If the DMR or DMC relay is not pulled in check for 24 volts at the DMR or 24 volts at TMC G terminal coil If 24 volts is present replace the DMR or DMC relay If 24 volts is not present check for a loose 24 volt connec tion back to the relay board and check the connections from the room thermostat t...

Страница 19: ...volts across terminals MV and COMMON terminals If no voltage is detected replace the ignitor control If voltage is pres ent replace the gas valve 8 Furnace lights with roll out or one burner has delayed igni tion a Make sure that the pilot burner is aligned properly with the carryover as described in PILOT CHECKOUT b Make sure that the carryovers on adjoining burners are screwed fast and are level...

Страница 20: ... 0204 Supersedes 035 14832 002 A 0302 Unitary Products Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2004 All Rights Reserved ...

Отзывы: