035-18895-000-A-0902
8
Unitary Products Group
FIG. 7 - DIMENSIONS AND CLEARANCES
All dimensions are in millimeters and inches,
unless otherwise specified. They are subject
to change without notice. Certified dimen-
sions will be provided upon request.
CLEARANCES (mm / in.)
Front
914 / 36
Back
610 / 24 (Less Economizer)
1245 / 49 (With Economizer)
Left Side (Filter Access)
610 / 24
Right Side (Outdoor Coil)
914 / 36
Below Unit
2
0 / 0
Above Unit*
1829 / 72 With 914 / 36
Maximum Horizontal Overhang
(For Outdoor Air Discharge)
NOTE: Unit and ductwork are approved for zero clearance to combustible
materials when equipped with electric heat.
*
Units must be installed oudoors. Overhanging structures or shrubs should not
obstruct outdoor air discharge outlet.
HOLE
OPENING
DIAMETER
(mm / in.)
USED FOR
A
28.6 / 1-1/8 KO
Control
Wiring
Front
19.1 / 3/4 NPS (Fem.)
Bottom
B
92.1 / 3-5/8 KO
Power
Wiring
Front
76.2 / 3 NPS (Fem.)
Bottom
UTILITIES ENTRY DATA
1235 (48-5/8") (180)
3181 (125-1/4") (180)
RETURN AIR
SUPPLY AIR
OUTDOOR AIR
OUTDOOR AIR
(Economizer)
616 (24-1/4”) (180 MBH