Verasys
Verasys
™
is an easy, intuitive way to control and optimize
single and multi-site light commercial or commercial build-
ings. Verasys provides a remote accessible central loca-
tion that can range from 1 to 100 Smart Equipment units
or devices. From HVAC to lighting to even refrigeration,
Verasys includes full commissioning, scheduling, alarm
notifications, setpoint adjustment, trending and more
without ever needing to be physically at the equipment.
Verasys communicates using BACnet
®
MS/TP and
can be used with the Smart Equipment controller. With
proper installation and BACnet addressing, all Verasys
devices self-identify without the requirement of pro-
gramming tools and licensing.
Additionally, using their third party device solutions,
Verasys allows third-party HVAC equipment to also in-
tegrate for greater application flexibility and to protect
existing investments.
NOTE:
The Applied Smart Equipment controller is
only compatible with smart building hub (SBH)
firmware version 3.2.0.766 and above. For the
latest firmware version go to
, and navigate to Login > Product Informa-
tion & Support > Device Updates.
For related documentation, including how to set up
parameters, and training videos, visit
com/resources/technical-literature-and-documentation
LD28041
Figure 44: Verasys Dashboard
Table 31: Verasys Related Documentation
Topic
Document
Technical specifications
Smart Building Hub Catalog
Page
(LIT-1901080)
Getting up and running
quickly with the MAP
gateway
Smart Building Hub Quick
Start Guide
(Part No. 24-10737-00229)
Installing and wiring a SBH
Smart Building Hub
Installation Instructions
(Part No. 24-10737-00237)
Table 32: BACnet Points List
BACnet
Attributes
Object
Type
Object
ID
Read/
Write
Short Description
Long
Description
Point Definitions (Units)
TempOccTimeout
AV
29521 R/W
TempOccTimeout
Temporary
Occupancy
Timeout
A BAS command to adjust temporary
occupancy timeout (30–480 minutes)
OprZT
AV
29522
R
OprST
Operational Zone
Temperature
Displays the active ZT (°F)
ZTAlarmOffset
AV
29524 R/W
ZTAlarmOffset
ZT Alarm Setpoint
Offset
A BAS command to adjust ZT alarm
setpoint offset (0.0–25.0°F)
ZTAlarmDelay
AV
29525 R/W
ZTAlarmDelay
ZT Alarm Time
Delay
A BAS command to adjust ZT alarm
time delay (0–120 minutes)
NetZT
AV
29526 R/W
NetZT
Network Override
ZT
A BAS command to adjust network
override ZT (0.0–100.0°F)
OprIAQ
AV
29527
R
OprIAQ
Operational IAQ
Displays the active indoor air CO
2
(PPM)
NetIAQ
AV
29530 R/W
NetIAQ
Network Override
IAQ
A BAS command to override indoor
air CO
2
(0–5,000 PPM)
OprZH
AV
29531
R
OprSH
Operational
Space Humidity
Displays the active space humidity
(%RH)
NetSH
AV
29533 R/W
NetSH
Network Override
Zone Humidity
A BAS command to override zone
humidity (0–100 %RH)