YORK
5587001-YSG-A-520 | Start-Up & Operation Guide
118
Fault Type
Description
Caused By
Critical
Unit locked out - airflow proof failure
APS did not close when expected on fan
start-up
Critical
C1A locked out - exceeded operating envelope
limits
Variable speed drive compressor
envelope control: This output shows
lockout when three variable speed drive
compressor operating envelope shutdown
events occurred within two hours of
compressor runtime
Critical
C1A locked out due to oil switch
C1A oil switch open. Check crankcase oil
level
Critical
Furnace module 1 lockout
Heating section 1 shutdown due to ignition
control module. Check module for fault
enumerator
Critical
Furnace module 2 lockout
Heating section 2 shutdown due to ignition
control module. Check module for fault
enumerator
Critical
Furnace module 3 lockout
Heating section 3 shutdown due to ignition
control module. Check module for fault
enumerator
ServicePriority
Unit shutdown airflow validation fail
Heating and cooling shutdown, blower
operation not proven. Check APS, DPS
ServicePriority
Circuit 1 shutdown due to low pressure
Caused by low airflow, dirty filters, iced on
coil, low charge
ServicePriority
Circuit 2 shutdown due to low pressure
Caused by low airflow, dirty filters, iced on
coil, low charge
ServicePriority
C1A shutdown due to high pressure
Caused by dirty condenser coils,
condenser fan failure, over charged
ServicePriority
C1B shutdown due to high pressure
Caused by dirty condenser coils,
condenser fan failure, over charged
ServicePriority
C1C shutdown due to high pressure
Caused by dirty condenser coils,
condenser fan failure, over charged
ServicePriority
C2A shutdown due to high pressure
Caused by dirty condenser coils,
condenser fan failure, over charged
ServicePriority
C2B shutdown due to high pressure
Caused by dirty condenser coils,
condenser fan failure, over charged
ServicePriority
C2C shutdown due to high pressure
Caused by dirty condenser coils,
condenser fan failure, over charged
ServicePriority
C1A shutdown due to low pressure
Caused by low airflow, dirty filters, iced on
coil, low charge
ServicePriority
C1B shutdown due to low pressure
Caused by low airflow, dirty filters, iced on
coil, low charge
ServicePriority
C1C shutdown due to low pressure
Caused by low airflow, dirty filters, iced on
coil, low charge
ServicePriority
C2A shutdown due to low pressure
Caused by low airflow, dirty filters, iced on
coil, low charge
ServicePriority
C2B shutdown due to low pressure
Caused by low airflow, dirty filters, iced on
coil, low charge
ServicePriority
C2C shutdown due to low pressure
Caused by low airflow, dirty filters, iced on
coil, low charge
Table 33: Faults List (Continued)