York PS9 Скачать руководство пользователя страница 8

105564-UIM-A-0205

8

Unitary Products Group

SECTION V: ELECTRICAL POWER

Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.

ELECTRICAL POWER CONNECTIONS

Field wiring to the unit must be grounded. Electric wires that are field
installed shall conform to the temperature limitation for 63°F (35°C) rise
wire when installed in accordance with instructions. Refer to Table 7 in
these instructions for specific furnace electrical data.

SUPPLY VOLTAGE CONNECTIONS

IMPORTANT: 

The power connection leads and wiring box may be relo-

cated to the left side of the furnace. Remove the screws and cut wire tie
holding excess wiring. Reposition on the left side of the furnace and fas-
ten using holes provided.

1.

Provide a power supply separate from all other circuits. Install
overcurrent protection and disconnect switch per local/national
electrical codes. The switch should be close to the unit for conve-
nience in servicing. With the disconnect or fused switch in the OFF
position, check all wiring against the unit wiring label. Refer to the
wiring diagram shown in Figure 28.

2.

Remove the screws retaining the junction box cover. Route the
power wiring through the opening in the unit into the junction box
with a conduit connector or other proper connection. In the junc-
tion box there will be three wires, a Black Wire, a White Wire and a
Green Wire. Connect the power supply as shown on the unit-wir-
ing label on the inside of the blower compartment door or Figure 6.
The black furnace lead must be connected to the L1 (hot) wire
from the power supply. The white furnace lead must be connected
to neutral. Connect the green furnace lead (equipment ground) to
the power supply ground. An alternate wiring method is to use a
field provided 2” (5.08 cm) x 4” (10.2 cm) box and cover on the
outside of the furnace. Route the furnace leads into the box using
a protective bushing where the wires pass through the furnace
panel. After making the wiring connections replace the wiring box
cover and screws.

3.

The furnace's control system requires correct polarity of the power
supply and a proper ground connection. If the power supply polar-
ity is reversed, the control board will flash 9 times. The furnace will
not operate until the polarity is corrected. Refer to “Furnace Diag-
nostics” section of the “User’s Information, Maintenance, & Ser-
vice Manual provided with this furnace.

TABLE 7: 

Electrical and Performance Data

Input/Cabinet

Output

Blower Size

Blower

Max. 

Over-current 

Protect

Air Temp. Rise

MBH

kW

MBH

kW

In.

cm

HP

Amps

°F

°C

40/A

11.7

38

11.1

11 x 8

27.9 x 20.3

1/2

7.0

20

35 - 65

19 - 36

60/B

17.6

56

16.1

11 x 8

27.9 x 20.3

1/2

7.0

20

40 - 70

22 - 39

80/B

23.4

74

21.9

11 x 8

27.9 x 20.3

1/2

7.0

20

45 - 75

25 - 42

80/C

23.4

75

22.0

11 x 10

27.9 x 25.4

3/4

10.2

20

45 - 75

25 - 42

80/C

23.4

75

22.0

11 x 11

27.9 x 27.9

1

12.7

20

40 - 70

22 - 39

100/C

29.3

93

27.8

11 x 10

25.4 x 25.4

3/4

10.2

20

45 - 75

25 - 42

100/C

29.3

93

27.8

11 x 11

27.9 x 27.9

1

12.7

20

40 - 70

22 - 39

120/D

35.2

112

32.8

11 x 11

27.9 x 27.9

1

12.7

20

40 - 70

22 - 39

135/D

39.6

127

36.9

11 x 11

27.9 x 27.9

1

12.7

20

45 - 75

23 - 42

Max. Outlet 

Air Temp.

Nominal Airflow

Cabinet Width

Total Unit

AFUE

Min. Wire Size

(awg) @ 75 ft. 

One Way

Approximate

Operating Weight

°F

°C

CFM

m

3

/min

In.

cm

Amps

%

165

73.9

1200

34.0

14-1/2

36.8

9

94.0

14

121

170

76.7

1200

34.0

17-1/2

44.4

9

92.0

14

135

175

79.4

1200

34.0

17-1/2

44.4

9

92.0

14

142

175

79.4

1600

45.3

21

53.3

12

92.0

14

157

170

7607

2000

56.6

21

53.3

14

92.0

12

159

175

79.4

1600

45.3

21

53.3

12

92.0

14

162

170

76.7

2000

56.6

21

53.3

14

92.0

12

164

170

76.7

2000

56.6

24-1/2

62.2

14

92.0

12

180

175

79.4

2000

56.6

24-1/2

62.2

14

92.0

12

180

Use copper conductors only.

 FIGURE 5:  

Electrical Wiring

N

GND

L1
HOT

WHT

GRN

BLK

BLK/BLK
WHT/WHT
GRN/GRN

CLASS 2 SYSTEM
CONTROL WIRING
TO THERMOSTAT

BLOWER
COMPARTMENT
DOOR SWITCH

TRANSFORMER

IGNITION
MODULE

Содержание PS9

Страница 1: ...TWINNING AND STAGING 9 COMBUSTION AIR AND VENT SYSTEM 11 CONDENSATE PIPING 18 SAFETY CONTROLS 18 START UP AND ADJUSTMENTS 19 WIRING DIAGRAM 25 LIST OF FIGURES Dimensions 5 Furnace Base Rectangular Bl...

Страница 2: ...ational vehicles Failure to carefully read and follow all instructions in this manual can result in furnace malfunction death personal injury and or property damage Furnaces for installation on combu...

Страница 3: ...required for passage to the front when servicing or for inspection or replacement of flue vent connections In all cases accessibility clearances shall take precedence over clear ances for combustible...

Страница 4: ...sure drop across any applied coil TABLES 2 AND 3 are to be used as a guide only to help the installer determine if the duct sizes are large enough to obtain the proper air flow CFM through the furnace...

Страница 5: ...1 for unit and plenum dimensions Attic installations must meet all minimum clearances to combustibles and have floor support with required service accessibility The supply air temperature MUST NEVER e...

Страница 6: ...ctions in this section specify the type of gas approved for this furnace only use those approved gases The instal lation of a drip leg and ground union is required Refer to Figure 4 IMPORTANT An acces...

Страница 7: ...ing a wrench to the body of the gas valve will damage the valve causing improper operation and or the valve to leak TABLE 5 High Altitude Conversion 40 120 MBTUH Models Type Of Gas Orifice at Sea Leve...

Страница 8: ...ernate wiring method is to use a field provided 2 5 08 cm x 4 10 2 cm box and cover on the outside of the furnace Route the furnace leads into the box using a protective bushing where the wires pass t...

Страница 9: ...using the same duct system it is very important that the two furnace cir culating air blowers operate in unison If one blower starts before the second blower the duct system will become pressurized an...

Страница 10: ...then will shut off at the same time Continuous Fan On a thermostat call for continuous fan G signal both furnace blowers will come on at the same time in cooling speed and will stay on until the G sig...

Страница 11: ...ow a maximum of 5 elbows in the combustion air piping and a maximum of 5 elbows in the vent piping 4 Three vent terminal elbows two for vent pipe and one for air intake pipe are already accounted for...

Страница 12: ...n air systems from the furnace to the out side termination B Ventilated combustion air systems from the furnace to the attic or crawl space termination 6 Disassemble the combustion air and vent piping...

Страница 13: ...0 kW 36 inches 91 cm for models 100 000 BTUH 30 kW Two pipe direct vent applications 9 inches 23 cm for models 50 000 BTUH 15 kW 12 inches 30 cm for models 50 000 BTUH 15 kW Single pipe applications 4...

Страница 14: ...ombustion air systems must be installed so the vent and the combustion air pipes terminate in the same atmospheric zone Refer to Figures 15 or 16 VENTING MULTIPLE UNITS Multiple units can be installed...

Страница 15: ...ll bring air in from the outdoors to the furnace combustion air intake collar on the burner box The second pipe Shown in Figure 19 is the furnace vent pipe The combustion air intake pipe should be loc...

Страница 16: ...e louver is in the fully open position This type of installation requires that the supply air to the appli ance s be of a sufficient amount to support all of the appliance s in the area Operation of a...

Страница 17: ...sage Follow all notes procedures and required materials in the SEALED COMBUS TION AIR SUPPLY section in these instructions when installing the combustion air pipe from the unit and into a ventilated a...

Страница 18: ...p pump must be approved for use with acidic condensate CONDENSATE DRAIN TRAP AND DRAIN FREEZE PROTECTION Special precautions MUST be made if installing furnace in an area which may drop below freezing...

Страница 19: ...th x 1 8 0 3 cm diameter tubing 2 pieces of 4 10 cm length x 1 8 0 3 cm diameter tubing 1 5 16 0 8 cm tee 1 5 16 0 8 cm x 1 8 0 3 cm reducing coupling 1 1 8 0 3 cm adapter 1 Dwyer Manometer These item...

Страница 20: ...3600 then divided by the time it took to measure 0 10 m3 of gas from the gas meter For Propane LP Gas multiply the Heat content of the gas MJ m3 or Default 93 15 times 0 10 m3 of gas measured at the...

Страница 21: ...l reference atmo spheric pressure Refer to Figure 26 for connection details IMPORTANT The cap for the pressure regulator must be removed entirely to gain access to the adjustment screw Loosening or ti...

Страница 22: ...s user selection of the blower speed that is energized during continuous fan operation Place jumper on the HI COOL LO COOL or HEAT pins The blower speed connections shown in Figure 27 are typical How...

Страница 23: ...35 1175 33 1105 31 1045 30 990 28 905 25 890 25 790 22 80 1600 C 100 1600 C HIGH 1960 56 1955 55 1925 55 1890 54 1830 52 1765 50 1695 48 1615 46 1600 45 1485 42 M HI 1565 44 1560 44 1560 44 1575 45 15...

Страница 24: ...that total system static is 0 58 w c To determine the system airflow complete the follow ing steps Obtain the airflow values at 0 50 w c 125 Pa 0 60 w c 150 Pa ESP Airflow 0 50 2285 CFM 64 70 m3 min A...

Страница 25: ...105564 UIM A 0205 Unitary Products Group 25 SECTION XI WIRING DIAGRAM FIGURE 28 Wiring Diagram...

Страница 26: ...105564 UIM A 0205 26 Unitary Products Group NOTES...

Страница 27: ...105564 UIM A 0205 Unitary Products Group 27 NOTES...

Страница 28: ...change without notice Printed in U S A 105564 UIM A 0205 Copyright by York International Corp 2005 All rights reserved Supersedes 035 20377 002 Rev A 0904 Unitary 5005 Norman Product York OK Group Dr...

Отзывы: