5167540-YIM-H-0518
Johnson Controls Ducted Systems
25
Component
Models
ZR037
ZR049
ZR061
Nominal Tonnage
3
4
5
CONDENSER FAN DATA
Quantity of fans
1
2
2
Fan diameter (Inch)
24
24
24
Type
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
Quantity of motors
1
2
2
Motor HP each
1/3
1/3
1/3
No. speeds
Var.
Var.
Var.
RPM (max.)
850
850
850
Total CFM
3500
7000
7000
BELT DRIVE EVAP FAN DATA
Quantity
1
1
1
Fan Size (Inch)
12 x 9
12 x 9
12 x 9
Type
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
1VP34
1VL44
1VP34
1VL44
1VP34
1VL44
Blower Sheave
AK61
AK59
AK61
AK59
AK61
AK59
Belt
A47
A47
A47
A47
A47
A47
Motor HP each
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
2
RPM
1725
1725
1725
1725
1725
1725
Frame size
56
56
56
56
56
56
FILTERS
Quantity - Size
4 - (24 x 16 x 2)
2, 3
4 - (24 x 16 x 2)
2, 3
4 - (24 x 16 x 2)
2, 3
4 - (24 x 16 x 4)
4
4 - (24 x 16 x 4)
4
4 - (24 x 16 x 4)
4
1. ZR049, ZR061 have crankcase heaters standard
2. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3.
3. 2 In. Pleated, Optional, MERV 8.
4. 4 In. Pleated, Optional, MERV 13.
ZR037-061 Single Stage Gas Heat Physical Data (Continued)