OptiView Control Center
ANALOG INPUT RANGES
The following table indicates the valid display range for
each of the analog input values. In the event that the input
sensor is reading a value outside of these ranges, the <
or > symbols will be displayed beside the minimum or
maximum value, respectively.
Analog Parameter
Device
English Range
Metric Range
Low
High
Units
Low
High
Units
Leaving Chilled Liquid Temperature
RT1
0
81
ºF
-17.7
27.2
ºC
Returning Chilled Liquid Temperature
RT6
0
93
ºF
-17.7
33.9
ºC
Leaving Cooling Liquid Temperature
RT4
8
134
ºF
-13.3
56.6
ºC
Returning Cooling Liquid Temperature
RT5
8
134
ºF
-13.3
56.6
ºC
Evaporator Refrigerant Temperature
RT8
8
134
ºF
-13.3
56.6
ºC
Generator Pressure
PT1
0
775
mmHg
0
775
mmHg
Entering Steam Temperature
RT7
91
346
ºF
32.8
174.4
ºC
Entering Steam Pressure
PT2
10
40
PSIA
68.9
275.8
Kpa
Entering Hot Water Temperature
RT7
91
346
ºF
32.8
144.4
ºC
Strong Solution Temperature
RT3
91
346
ºF
32.8
144.4
ºC
Strong Solution Concentration
RT3 & RT9 40% *
70% *
%
40% *
70% *
%
ADC Temperature
RT2
100
220
ºF
37.8
104.4
ºC
Strong Solution Leaving STS Temperature
RT10
60
220
ºF
32.8
174.4
ºC
Refrigerant from Condenser Temperature
RT9
8
134
ºF
-13.3
56.6
ºC
Purge Pump Pressure
PT3
12.9
219.7
mmHg
12.9
219.7
mmHg
Purge Tank Pressure
PT4
12.9
219.7
mmHg
12.9
219.7
mmHg
* The calculated strong solution concentration range is from 40% to 70%, this function was copied from the millenium control source code.
TABLE 1 –
ANALOG INPUT RANGE