SECTION 2 – OPTIVIEW CONTROL CENTER
FORM 160.79-O3
ISSUE DATE: 11/09/2018
2
This screen allows the Operator to choose what units
of measurement to display parameters in, the screen
languages, and the date format.
Each Custom User value is not linked to a specific but-
ton. Instead, the Change button is pressed which en-
ables the cursor arrows which are used to highlight the
Custom User parameter the user wishes to modify. At
this point the ‘
a
’ (Check) button is pressed and the
value may be entered.
DISPLAY ONLY
None
PROGRAMMABLE
System Language
Access Level Required: OPERATOR
Allows the user to define the language for all Screens.
The desired language is selected by scrolling through
the list of those available. English is the Default lan-
guage and is selected by pressing the Up Arrow key
when the dialog box appears during the selection pro-
cess. The selected language will not be displayed un-
til after the user navigates from the USER Screen to
another Screen. Available languages are English, Tra-
ditional Chinese, Simplified Chinese, French, Portu-
guese, Spanish, Italian, German, Hungarian, and Turk-
ish.
English / Metric Units
Access Level Required: OPERATOR
Define the unit system (English or Metric) used by the
chiller display.
Custom User ID (4)
Access Level Required: SERVICE
This allows the user to specify up to four (4) Custom
User ID values. Each user ID will then require a cor-
responding Password and User Level. A User ID can
be defined for various maintenance personnel. Service
Technicians refer to
Service Manual (Form 160.79-
M1)
.
Custom User Password (4)
Access Level Required: SERVICE
This allows the user to specify up to four (4) Custom
Password values. Each Password will then require a
corresponding User ID and User Level. Service Tech-
nicians refer to
Service Manual (Form 160.79-M1)
.
USER SCREEN
LD27876
FIGURE 37 -
USER SCREEN