background image

LOW VOLTAGE CONTROL CONNECTIONS

Use 7/8 inch knockout on the left hand side panel to bring low
voltage wiring into air handler.

CAUTION: Use 7/8 inch plastic bushing provided to prevent

chafing wires.

All field control wiring to be connected at screw terminals of
connector board. See Figure 8.

Remove control wiring harness supplied with 2HW electric heat
accessory and discard. Every connector board is supplied with a
complete electric heat wiring harness connected to the lower right
hand corner of connector board (See Figure 8). Plug in free end
of wiring harness to electric heat control board.  If the transformer
kit is installed, discard electric heat wiring harness attached to
connector board. Install wiring harness provided with transformer
accessory at the connection in lower right hand corner of connec-
tor board.

Field supplied low voltage wiring must be kept as short as possi-
ble and away from the blower motor wires. Refer to Table 2, 3 or
5 for minimum wire size.

The 24 volt power supply is provided by an internally wired low
voltage transformer. However, if the unit is connected to a 208 volt
power supply the low voltage transformer must be rewired to the
208 volt tap. See the unit wiring label.

See Figure 9, 10 and 11 for low voltage terminal connections.

If thermostat used has an adjustable heat anticipator, see Table
below for proper setting.

BLOWER SPEED SELECTION

All variable speed air handlers (N*VS) are designed to deliver
constant CFM regardless of the external static pressure (ESP) in
the ductwork. Therefore, if too many supply registers are closed,
a filter becomes clogged, or there is a restriction in the ductwork,
the motor will automatically operate at a higher speed to compen-
sate for the higher ESP. This may result in a higher operating
sound level.

To Set Cooling CFM:

Refer to the outdoor unit technical guide for the recommended
airflow with the matching evaporator coil. Refer to the label on the
blower housing or Table 1 for the possible HI speed cooling and/or

Electric Heater with

Cooling or

Electric Heater Only

KW

Adjustable

Heat

Anticipator

2HW

5 - 20

0.1 Amps

HEAT ANTICIPATOR SETTING  

FIGURE 7 - Blower Connections

GRD.

FAN MOTOR SPEED TAP RECEPTACLE
ON TRANSFORMER OR HEATER ACCESSORY

PURPLE

BLUE

PURPLE

BLUE

VARIABLE
SPEED MOTOR

5 PIN CONNECTOR

WIRE HARNESS
TO CONNECTOR
BOARD (16 PIN
CONNECTOR)

208/230V

FIGURE 8 - N*VS Connector Board

SCREW
TERMINAL
BOARD

HUMIDISTAT
ACCESSORY
JUMPER

DELAY
PROFILE TAP

BLOWER MOTOR
INTERFACE HARNESS
CONNECTS HERE

COOL TAP

ELECTRIC
HEAT TAP

ADJ TAP

ELECTRIC HEAT OR TRANSFORMER WIRING
HARNESS CONNECTS HERE

JUMPER IN STORED POSITION

(Vertically on RH side, pins “A” and “B”)

HEAT PUMP JUMPER

JUMPER IN “A” CFM
POSITION

(Horizontally jumper two “A” pins)

535.03-N1Y

6

Unitary Products Group

Содержание N1VSD10A06

Страница 1: ...be made in writing See Form 50 15 NM for more information REFERENCE This instruction should be used in conjunction with installation instructions supplied with each accessory as well as the matching...

Страница 2: ...an evaporator coil is installed in an attic or above a finished ceiling an auxiliary drain pan should be provided under the coil as is specified by most local building codes If the coil is provided w...

Страница 3: ...uction 1 Attach coil casing to blower section in a way appropriate to indoor unit application See Form 535 01 N5V for G HC or G FC Coils and Form 535 01 N6V for G HT Coils Confirm the orifice size bef...

Страница 4: ...nnect Line Sizes A B C D E F G H J K L M Liquid Vapor Liquid Vapor D10 024 16 1 4 1 12 1 8 3 7 8 12 1 8 14 1 4 22 3 4 54 1 2 3 1 2 1 1 2 1 3 4 3 1 2 F 6 F 11 5 16 5 8 030 14 1 4 22 3 4 54 1 2 3 1 4 6...

Страница 5: ...the use of smaller size power wire but will require a greater number of wires To accomplish this field con version refer to Figure 5 Dual Supply as an example and proceed as follows 1 Remove the jumpe...

Страница 6: ...thermostat used has an adjustable heat anticipator see Table below for proper setting BLOWER SPEED SELECTION All variable speed air handlers N VS are designed to deliver constant CFM regardless of the...

Страница 7: ...lected To Set Delay Profile Every variable speed air handler has multiple blower off delay profiles to optimize system performance and efficiency Refer to Table below for the type of system installed...

Страница 8: ...ION HEAT Tap Jumper at A Jumper at B Jumper at C No Jumper Cubic Foot Per Minute CFM 1300 1300 1450 1600 TABLE 1 CFM TAP SELECTION BLOWER SIZE TRANFORMER KIT MIN CIRCUIT AMPACITY MAX T D FUSE SIZE MIN...

Страница 9: ...ABLE 4 ELECTRICAL DATA HEATER ACCESSORY FOR 208 VOLT OPERATION MULTIPLY 240 VOLT TABULATED KW MBH BY 751 230 VOLT 240 VOLT 918 1 KW MBH CONVERSIONS Blower Size Heater Accessory Model No Field Wiring 2...

Страница 10: ...W 6 6 C Y R G CONNECTOR BOARD X or L B or C 6 0 5 3 O X HUMIDISTAT JUMPER MUST BE REMOVED DEHUMIDIFICATION CONTROL CONNECTION N O T U S E D NO T US E D B K THE RMOS TA T G W 1 X or L C or B R WIRE NU...

Страница 11: ...IRE NUT RED OUTDOOR UNIT R C Y G O X W W1 W2 HUMIDISTAT JUMPER MUST BE REMOVED Y 1 Y 2 BK DEHUMIDIFICATION CONTROL CONNECTION R C Y 1 Y 2 Y2 OUT NO Y 1 Y 2 W 2 TWO STAGE COOL ING MUST BE USED BRN YEL...

Страница 12: ...USED WITH A HEAT PUMP UNIT HEAT PUMP MODELS E FH THERMO STAT G X or L R O UTDO OR HEATPUMP R C Y G O X W W1 W2 INDOOR UNIT CONNECTOR BOARD HUMIDISTAT JUMPER MUST BE REMOVED Y 1 Y 2 BK DEHUMIDIFICATIO...

Отзывы: