Johnson Controls Unitary Products
7
5006167-YTG-F-0517
ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY: 208/230-1-60
Air Handler
Models
Heater
Models
1,2
Heater
Amps
@240V
Field Wiring
Min. Circuit Ampacity
MOP.
3
208V
230V
208V
230V
MP08B
6HK(0,1)6500206
10
12.6
13.7
15
15
6HK(0,1)6500506
20
23.4
25.7
25
30
6HK(0,1)6500806
32
36.6
40.3
40
45
6HK(0,1)6501006
40
45.0
49.6
45
50
6HK(1,2)6501306
52
58.2
64.3
60
70
MP12B
6HK(0,1)6500206
10
14.1
15.2
15
20
6HK(0,1)6500506
20
24.9
27.2
25
30
6HK(0,1)6500806
32
38.1
41.8
40
45
6HK(0,1)6501006
40
46.5
51.1
50
60
6HK(1,2)6501306
52
59.7
65.8
60
70
6HK(1,2)6501506
60
68.2
75.0
70
80
6HK(1,2)6501806
72
81.4
89.7
90
90
6HK(1,2)6502006
80
89.8
98.9
90
100
MP14D
6HK(0,1)6500206
10
14.3
15.5
15
20
6HK(0,1)6500506
20
25.1
27.4
30
30
6HK(0,1)6500806
32
38.4
42.1
40
45
6HK(0,1)6501006
40
46.8
51.3
50
60
6HK(1,2)6501306
52
60.0
66.0
60
70
6HK(1,2)6501506
60
68.4
75.2
70
80
6HK(1,2)6501806
72
81.6
89.9
90
90
6HK(1,2)6502006
80
90.0
99.2
90
100
MP16C
6HK(0,1)6500206
10
14.4
15.6
15
20
6HK(0,1)6500506
20
25.3
27.5
30
30
6HK(0,1)6500806
32
38.5
42.2
40
45
6HK(0,1)6501006
40
46.9
51.5
50
60
6HK(1,2)6501306
52
60.1
66.1
70
70
6HK(1,2)6501506
60
68.5
75.4
70
80
6HK(1,2)6501806
72
81.8
90.0
90
90
6HK(1,2)6502006
80
90.2
99.3
90
100
MP20D
6HK(0,1)6500206
10
15.9
17.1
20
20
6HK(0,1)6500506
20
26.8
29.0
30
30
6HK(0,1)6500806
32
40.0
43.7
40
45
6HK(0,1)6501006
40
48.4
53.0
50
60
6HK(1,2)6501306
52
61.6
67.6
70
70
6HK(1,2)6501506
60
70.0
76.9
70
80
6HK(1,2)6501806
72
83.3
91.5
90
100
6HK(1,2)6502006
80
91.7
100.8
100
110
1. (0,1) - 0 = no service disconnect OR 1 = with service disconnect.
2. (1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect & breaker jumper bar.
3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. The 1st circuit includes blower motor amps.
Refer to the latest edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.