background image

5715184-BIM-A-0519

28

Johnson Controls Ducted Systems

AIRFLOW SETTINGS

Cooling Airflow Settings

This unit is equipped with a five-speed blower motor. The required cool-
ing airflow can be selected by connecting the required motor speed tap
wire to the HI COOL terminal on the control board. The speed must be
selected to deliver approximately 350–400 CFM per ton of A/C cooling
capacity. Use of airflow outside of this range may result in diminished
air conditioning performance, lower overall energy efficiency, and
higher electric utility bills. See Table 17 for default cooling blower set-
tings.

Continuous Fan Airflow Default Setting

The default blower speed for continuous fan operation is LOW speed.
The continuous fan speed is set at the factory to the default continuous
fan blower speed.

In certain circumstances, it may be necessary to move the continuous
fan speed to a different speed tap. However, doing so results in higher
than normal electrical energy usage and electric utility bills.

Continuous Fan Jumpers

This furnace can be operated in continuous fan mode by setting the wall
thermostat FAN switch to ON. To select the required continuous fan air-
flow, place the FAN SPEED jumper on the control board on the pins
adjacent to the required speed. There are four options: 

With the FAN SPEED jumper in the G position, the blower runs
during continuous fan operation at the motor speed connected to
the G terminal on the control board.

With the FAN SPEED jumper in the HI COOL position, the blower
runs during continuous fan operation at the motor speed con-
nected to the HI COOL terminal on the control board.

With the FAN SPEED jumper in the LO COOL position, the
blower runs during continuous fan operation at the motor speed
connected to the LO COOL terminal on the control board.

With the FAN SPEED jumper in the HEAT position, the blower
runs during continuous fan operation at the motor speed con-
nected to the HEAT terminal on the control board.

The default position is with the jumper in the G position and the LOW
speed motor wire on the G terminal. In certain circumstances, it may be
necessary to move the continuous fan speed to a different speed tap.
However, doing so is not recommended because it results in higher
than normal electrical energy usage and electric utility bills.

Gas Heating Airflow Default Setting

This unit is equipped with a five-speed blower motor. The heating
blower speed is set at the factory to the default blower speed, which is
the blower speed that delivers the correct airflow for proper heating
operation in most applications. The default heating blower speed for
each model is shown in Table 17. Use of a heating speed other than the
default heating blower speed may result in reduced energy efficiency
and higher electric utility bills. 

In certain circumstances, it may be necessary to move the heating
blower speed to a different motor speed tap. Not all five motor speeds
are appropriate for gas heating operation. The use of heating airflow on
a speed other than the default speed results in diminished heating per-
formance and may cause the furnace temperature limit controls to shut
down the furnace.

Measurement of Temperature Rise

After about 5 minutes of operation, determine the furnace temperature
rise. Measure the temperature of both the return air and the heated air
in the ducts approximately 6 ft (1.83 m) from the furnace, where they
are not affected by radiant heat. Increase the blower speed to decrease
the temperature rise. Decrease the blower speed to increase the tem-
perature rise.

The blower speed taps are located on the furnace control board in the
blower compartment. Refer to Figure 33 and the unit-wiring label to
change the blower speed. To use the same speed tap for heating and
cooling, the heat terminal and cool terminal must be connected using a
jumper wire and connected to the required motor lead. Place all unused
motor leads on park terminals. Two park terminals are provided.

ADJUSTMENT OF FAN CONTROL SETTINGS

This furnace is equipped with a time-on/time-off heating fan control. The
fan-on delay is fixed at 30 seconds. The fan-off delay has 4 settings
(60, 90, 120, and 180 seconds). The fan-off delay is factory set to 120
seconds. The fan-off setting must be long enough to adequately cool
the furnace, but not so long that cold air is blown into the heated space.
The fan-off timing may be adjusted by positioning the jumper on two of
the four pins as shown in Figure 33.

Table 17: 

Default Blower Speeds

Model Number

Default Blower Speeds

Heat

Cool

Continuous 

Fan

MM9E060B12

Medium Low (4)

High (1)

Low (5)

MM9E080B12

Medium (3)

High (1)

Low (5)

MM9E080C16

Medium (3)

High (1)

Low (5)

MM9E080C20

Low (5)

High (1)

Low (5)

MM9E100C16

Medium High (2)

High (1)

Low (5)

 DANGER

The temperature rise, or temperature difference between the return
air and the supply (heated) air from the furnace, must be within the
range shown on the furnace rating plate and within the application
limitations shown in Table 5.
The supply air temperature cannot exceed the “Maximum Supply
Air Temperature”
 specified in these instructions and on the fur-
nace rating plate. Under NO circumstances can the furnace be
allowed to operate above the Maximum Supply Air Temperature.
Operating the furnace above the Maximum Supply Air Temperature
will cause premature heat exchanger failure, high levels of Carbon
Monoxide, a fire hazard, personal injury, property damage, and/or
death.

!

Содержание MM9E Series

Страница 1: ...Termination 21 Downward Venting 22 Direct Vent Air Intake Connection and Vent Connection 22 Outside and Ambient Combustion Air 23 Attic and Crawl Space Combustion Air Termination 24 Gas Valve 27 Readi...

Страница 2: ...The size of the unit must be based on an acceptable heat loss cal culation for the structure ACCA Manual J or other approved meth ods may be used 12 When moving or handling this furnace prior to inst...

Страница 3: ...hes etc Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials When outdoor air is used for combustion the combustion air intake duct system...

Страница 4: ...r protected to avoid physical damage by vehicles 24 in clearance in front and 18 in on side recommended for service access All furnaces approved for alcove installation FOR FURNACES INSTALLED IN THE C...

Страница 5: ...urnace does not operate properly The ducts attached to the furnace plenum must be of sufficient size so the furnace operates at the specified external static pressure and within the air temperature ri...

Страница 6: ...wnflow installations must use a suitable duct connector approved by the furnace manufacturer for use with this furnace The duct connec tors are designed to be connected to the rectangular duct under t...

Страница 7: ...Filters Downflow furnaces typically are installed with the filters located above the furnace extending into the return air plenum or duct Any branch duct rectangular or round duct attached to the plen...

Страница 8: ...ng 7 6 9 17 5 7 6 9 17 5RWDWH YHQW EORZHU HLWKHU ZD IMPORTANT On all installations without a coil a removable access panel is recommended in the outlet duct such that smoke or reflected light would be...

Страница 9: ...ZQIORZ RPEXVWLRQ LU QOHW DV 3LSH QWU OHFWULFDO QWU RQGHQVDWH UDLQ 2SWLRQDO 5HWXUQ LU XWRXW LWKHU VLGH RU ODGGHG GRRU DGG DSSR LPDWHO DQ DGGLWLRQDO 6833 1 RPEXVWLRQ LU QOHW 5 7851 1 9HQW RQQHFWLRQ 2XWO...

Страница 10: ...pples and conventional 90 degree elbow s to enter through the cabinet access holes FIGURE 11 Gas Valve DANGER An overpressure protection device such as a pressure regulator must be installed in the ga...

Страница 11: ...be shut off prior to disconnecting the electrical power before proceeding with the conversion WARNING SHOCK HAZARD Turn off electrical supply to furnace WARNING Never use an open flame to check for l...

Страница 12: ...thermostat by following the instructions that come with the thermostat With the thermostat set in the OFF position and the main electrical source disconnected connect the thermostat wiring from the w...

Страница 13: ...nsate pan is self priming and contains an inter nal trap to prevent flue gas leaking Do not install an external con densate trap IMPORTANT The furnace indoor coil and humidifier drains may be combined...

Страница 14: ...taken to prevent the drain line from freezing Failure to provide proper protection from freezing can result in improper operation or damage to the equipment and possible property damage When exposed t...

Страница 15: ...I VR WKDW QR VDJJLQJ ORRSV ZLOO FROOHFW DQG KROG FRQGHQVDWH ZKLFK ZLOO FDXVH WKH IXUQDFH WR QRW RSHUDWH 6KRUWHQ SUHVVXUH VZLWFK KRVH 5H URXWH DQG VKRUWHQ SUHVVXUH VZLWFK KRVH 6KRUWHQ UDLQ JXWWHU KRVH...

Страница 16: ...KLV SRVLWLRQ 127 0D UHTXLUH WKH ORQJHU KRVH WKDW LV SURYLGHG ZLWK ZLGHU FDELQHWV 0RYH FRQGHQVDWH GUDLQ KRVH WR WKLV SRVLWLRQ 0D H LW HLWKHU VLGH RI WKH FDELQHW 0RYH UDLQ JXWWHU KRVH WR WKLV SRVLWLRQ K...

Страница 17: ...ciety for Test ing and Materials ASTM standards D1785 Schedule 40 PVC D2665 PVC DWV F891 PVC DWV Cellular Core D2261 ABS DWV or F628 Schedule 40 ABS Pipe cement and primer must conform to ASTM Standar...

Страница 18: ...A 100 000 3 80 100 000 3 60 100 000 4 145 100 000 4 125 Elevation 4001 5000 Elevation 8001 9000 Model Input BTUH Pipe Size in Max Equivalent Length ft Model Input BTUH Pipe Size in Max Equivalent Leng...

Страница 19: ...A Dimension Illustrated in Figure 21 2 in Standard 2 5 16 in 3 in Standard 3 1 16 in 2 in Sweep 3 1 4 in 3 in Sweep 4 1 16 in TABLE 9 Equivalent Length of Fittings Fitting Equivalent Length 2 in 90 sw...

Страница 20: ...as supplier 12 in 30 5 cm or in accordance with local installation codes and the requirements of the gas supplier F Clearance to outside corner 12 in 30 5 cm or in accordance with local installation c...

Страница 21: ...ustion air sec tions in these instructions Follow the instructions for outdoor combus tion air or ventilated combustion air and the instructions for installing the vent system with the vent terminatin...

Страница 22: ...imming pool or a location where swimming pool chemicals might be stored Be sure the terminal assembly follows the outdoor clearances listed in Section 1 Outdoor Air Contaminants An unconfined space is...

Страница 23: ...n 12 in 30 5 mm of the bottom of the confined space shall communicate directly or by means of ducts with the outdoors crawl spaces or attic spaces 2 One permanent opening commencing within 12 in 30 5...

Страница 24: ...eing placed into operation could result in carbon monxide poisoning or death The following steps shall be followed for each appliance connected to the venting system being placed into operation while...

Страница 25: ...pilots 2 Run furnace for a minimum of 3 minutes in heating operation 3 Measure time in sec for gas meter to complete 1 revolution and note reading The 2 cubic ft dial provides a more accurate measure...

Страница 26: ...300 750 78 46 92 231 25 144 288 720 80 45 90 225 26 138 277 692 82 44 88 220 27 133 267 667 84 43 86 214 28 129 257 643 86 42 84 209 29 124 248 621 88 41 82 205 30 120 240 600 90 40 80 200 31 116 232...

Страница 27: ...ench 3 Turn the electrical and gas supplies back on and with the burners in operation check for gas leakage around the gas valve pressure port using an approved non corrosive gas leak detection fluid...

Страница 28: ...ower speed for each model is shown in Table 17 Use of a heating speed other than the default heating blower speed may result in reduced energy efficiency and higher electric utility bills In certain c...

Страница 29: ...B High 1418 1390 1364 1333 1304 1281 1246 1205 Medium High 1305 1281 1244 1217 1182 1149 1109 1066 Medium 1139 1112 1071 1035 992 951 908 874 Medium Low 1017 986 948 901 859 819 765 727 Low 885 821 76...

Страница 30: ...on air is provided the pressure switch closes and the ignition control provides a 17 second ignitor warm up period The gas valve then opens the gas starts to flow ignition occurs and the flame sensor...

Страница 31: ...Flashes and will enter a one hour soft lockout 5 RED FLASHES This fault is indicated if the normally closed rollout switch opens The rollout control is manually reset Check for proper combustion air...

Страница 32: ...e memory has been cleared and resumes the normal slow green flash after a five second pause SECTION XI REPLACEMENT PARTS LIST DESCRIPTION MOTOR MOTOR DIRECT DRIVE BLOWER BLOWER COMBUSTION ELECTRICAL C...

Страница 33: ...RVICE 5754336 UWD A 0519 Fault Code Retrieval To retrieve fault codes push and release ERROR button on control board The LED will flash the last five error codes beginning with the most recent If ther...

Страница 34: ...5715184 BIM A 0519 34 Johnson Controls Ducted Systems NOTES...

Страница 35: ...Ells Polarity is correct black is L1 hot white is N neutral Ground wire is connected Line voltage value to furnace volts AC Low voltage value between R and C on furnace control board volts AC Thermos...

Страница 36: ...atic in w c after Air Side Heating Air Side Cooling Air Side Continuous Fan Clean Up Give owner the owner s manual provided Gas Type Explain thermostat use and programming if applicable to owner Cycle...

Отзывы: