![York MILLENNIUM YCAS Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/york/millennium-ycas/millennium-ycas_installation-operation-and-maintenance_3850922026.webp)
26
YORK INTERNATIONAL
DX COOLER OPTIONS
21 bar (300PSIG) Waterside Design Working Pres-
sure – The DX cooler waterside is designed and con-
structed for 21 bar (300 PSIG) working pressure. (Fac-
tory Mounted)
38 mm (1-1/2") Insulation – Double thickness insu-
lation provided for enhanced efficiency.
Flange Accessory – Consists of raised face flanges to
convert grooved water nozzles to flanged cooler connec-
tions. Includes companion flanges for field mounting.
Remote DX Cooler – Includes the main condensing
unit less the cooler, refrigerant and liquid line devices.
The insulated cooler and field accessory kits per refrig-
erant circuit are supplied separately. The condensing
unit is shipped with a refrigerant charge and the cooler
is shipped with a nitrogen holding charge.
Flow Switch Accessory – Johnson Controls model
F61MG-1C Vapor-proof SPDT, NEMA 4X switch, 10
bar (150 PSIG) DWP, -29°C to 121°C (-20ºF to 250ºF),
with 25 mm (1") NPT (IPS) connection for upright
mounting in horizontal pipe. A flow switch must be field
installed with each unit.
Star-Delta Compressor Motor Starter – Provides
approximately 65% reduced inrush current compared
to across-the-line start (Factory Mounted).
UNIT ENCLOSURES
Wire enclosure – Heavy gauge welded wire mesh
guards mounted on the exterior of the unit (Factory or
field mounted).
Louvered panels and wired guards – Louvered pan-
els mounted over the exterior condenser coil faces, and
heavy gauge welded wire mesh guards mounted around
the bottom of the unit (Factory or field mounted).
Louvered panels (condenser coils only) – Louvered
panels are mounted over the exterior condenser coil
faces on the sides of the unit to visually screen and
protect the coils (Factory or field mounted).
Louvered panels (full unit) enclosure – Louvered
panels over condenser coils and around the bottom of
the unit (Factory or field mounted).
FANS
High static fans – Fans and motors suitable for High
External Static conditions to 100 Pa.
SOUND REDUCTION OPTIONS
Low speed fans – Reduced Revs./sec. (RPM) fan
motors and alternative fan selection for low noise appli-
cations.
Compressor sound enclosures – Acoustically
treated metal compressor enclosures. Includes a com-
pressor mounted temperature transducer to prevent
overheating.
VIBRATION ISOLATION
Neoprene pad isolation – Recommended for normal
installations. (Field mounted)
25 mm (1") spring isolators – Level adjustable, spring
and cage type isolators for mounting under the unit base
rails (Field mounted).
51 mm (2") seismic spring isolators – Restrained
Spring-Flex Mountings incorporate welded steel hous-
ing with vertical and horizontal limit stops. Housings
designed to withstand a minimum 1.0 g accelerated force
in all directions to 51 mm (2"). Level adjustable, deflec-
tion may vary slightly by application. (Field mounted).
Product Description
Содержание MILLENNIUM YCAS
Страница 53: ...53 YORK INTERNATIONAL FORM 201 18 NM2 WIRING DIAGRAM ACROSS THE LINE START 7...
Страница 54: ...54 YORK INTERNATIONAL FIG 12 CONTINUED ELEMENTARY DIAGRAM Technical Data...
Страница 56: ...56 YORK INTERNATIONAL FIG 13 POWER PANEL FRONT INSIDE VIEW ACROSS THE LINE START Technical Data...
Страница 57: ...57 YORK INTERNATIONAL FORM 201 18 NM2 LD03280 FIG 14 ELECTRONIC PANEL FRONT INSIDE VIEW ACROSS THE LINE START 7...
Страница 59: ...59 YORK INTERNATIONAL FORM 201 18 NM2 WIRING DIAGRAM WYE DELTA START LD03229 FIG 15 CONT D 7...
Страница 60: ...60 YORK INTERNATIONAL FIG 15 CONTINUED ELEMENTARY DIAGRAM Technical Data...
Страница 62: ...62 YORK INTERNATIONAL FIG 16 POWER PANEL FRONT INSIDE VIEW WYE DELTA START Technical Data...
Страница 63: ...63 YORK INTERNATIONAL FORM 201 18 NM2 LD03280 FIG 17 ELECTRONIC PANEL FRONT INSIDE VIEW WYE DELTA START 7...
Страница 65: ...65 YORK INTERNATIONAL FORM 201 18 NM2 LD03282 LD03283 LD03284 FIG 19 DETAIL A see pages 54 59 7...
Страница 67: ...67 YORK INTERNATIONAL FORM 201 18 NM2 COMPRESSOR TERMINAL BOX LD03233 FIG 23 COMPRESSOR TERMINAL BOXES 7...
Страница 68: ...68 YORK INTERNATIONAL FIG 24 DETAIL B Technical Data...
Страница 88: ...88 YORK INTERNATIONAL COMPRESSOR COMPONENTS CONT D FIG 34 COMPRESSOR COMPONENTS LD03669 Technical Data...
Страница 89: ...89 YORK INTERNATIONAL FORM 201 18 NM2 COMPRESSOR COMPONENTS CONT D FIG 35 COMPRESSOR COMPONENTS LD03670 7...
Страница 90: ...90 YORK INTERNATIONAL COMPRESSOR COMPONENTS CONT D FIG 36 COMPRESSOR COMPONENTS LD03671 Technical Data...