101
YORK INTERNATIONAL
FORM 201.18-NM6
1.9
MOTOR PROTECTION MODULES
A Motor Protection Module for each compressor is lo-
cated in the Control Panel. These modules supply mo-
tor over-temperature protection, 3-phase current pro-
tection, phase imbalance, phase rotation, and a program-
ming and troubleshooting 7 segment display.
The motor over-temperature protection is supplied by
3 temperature sensors imbedded in the motor wind-
ings 120 degrees apart. The module monitors these
sensors allowing it to sense a hot winding and shut
down the compressor if motor cooling is inadequate.
The on-board C.T.s provide 3-phase current protec-
tion which look at 3 of the 6 motor legs and send
an analog signal proportional to average motor cur-
rent to I/O Expansion board and on to the micropro-
cessor board for microprocessor low/high current pro-
tection and current display. This allows the micro to
monitor current and shut a system down if low or high
motor current is sensed. This is a non-adjustable pro-
tection circuit electronically sized to a system's motor
specifications.
Internally, the on-board 3 C.T.s and internal circuitry
allow the Motor Protection Module to protect against
high motor current as programmed on the Motor Pro-
tector dip switches. These switches are set at the fac-
tory according to motor specifications.
The module also provides phase rotation protection to
assure the screw compressor does not rotate backwards.
A single phase protection circuit located in the module
also monitors for a phase imbalance. If current imbal-
ance exceeds 17% of the average motor current in one
of the phases, the Motor Protector will recognize it and
shut the system down.
Whenever the Motor Protection Module senses a fault,
internal contacts will open and shut the system down.
These contacts are wired in series with the compressor
motor contactor. When the contact opens, the micro will
attempt to start the system 2 more times. Since the
motor contactor signal path from the Relay Output
Board to the motor contactor is broken by the Motor
Protection Module contacts, it will lock the system out
after 3 faults. The Motor Protection Module must then
be reset by removing 115VAC power from the Control
Panel. After the Motor Protector is reset, the individual
system SYS switch must be switched OFF and then
ON to reset the microprocessor to allow restart of the
system.
Anytime the module faults, a thorough
investigation of the problem should be
performed before attempting to return
the system to operation. Failure to per-
form this investigation could lead to
motor or compressor failure. Addi-
tional details on the Motor Protection
Module can be found on page 16.
8
Содержание MILLENIUM YCAS Series
Страница 34: ...34 YORK INTERNATIONAL FIG 9 OPTION PANEL SECTION OPTIONS PANEL LAYOUT TYPICAL 00246VIP Installation...
Страница 47: ...47 YORK INTERNATIONAL FORM 201 18 NM6 7 This page intentionally left blank...
Страница 59: ...59 YORK INTERNATIONAL FORM 201 18 NM6 7 This page intentionally left blank...
Страница 60: ...60 YORK INTERNATIONAL FIG 18 ELEMENTARY DIAGRAM ACROSS THE LINE START ELEMENTARY DIAGRAM Technical Data...
Страница 63: ...63 YORK INTERNATIONAL FORM 201 18 NM6 7 WIRING DIAGRAM WYE DELTA START LD06015...
Страница 68: ...68 YORK INTERNATIONAL Technical Data LEGEND 0283 0343 LD06179...
Страница 69: ...69 YORK INTERNATIONAL FORM 201 18 NM6 7 LD05957...
Страница 70: ...70 YORK INTERNATIONAL Technical Data CONNECTION DIAGRAM SYSTEM WIRING LD06019...
Страница 71: ...71 YORK INTERNATIONAL FORM 201 18 NM6 7 COMPRESSOR TERMINAL BOX LD06020...
Страница 88: ...88 YORK INTERNATIONAL COMPRESSOR COMPONENTS CONT D FIG 31 COMPRESSOR COMPONENTS LD03669 Technical Data...
Страница 89: ...89 YORK INTERNATIONAL FORM 201 18 NM6 COMPRESSOR COMPONENTS CONT D FIG 32 COMPRESSOR COMPONENTS LD03670 7...
Страница 90: ...90 YORK INTERNATIONAL COMPRESSOR COMPONENTS CONT D FIG 33 COMPRESSOR COMPONENTS LD06232 Technical Data LD06231...