5169034-UIM-B-0216

6

Johnson Controls Unitary Products

UNIT CONNECTIONS

There are several ways to handle the supply and return air duct
connections. The location and sizing of the connections depends on the
situation and the method best suited to the installation. Upflow,
horizontal or downflow applications may be used.
The supply air duct should be properly sized by use of a transition to
match unit opening. Refer to Table 1 for air handler unit inlet and outlet
dimensions.

Duct work that is not designed to match the supply air opening can
cause turbulence inside the plenum. This turbulence can change the air
flow patterns across the electric heater limit switches. If the factory
suggested transition cannot be fabricated, it is recommended that a
block off plate (approximately 8" high and running the full width of the
plenum) be attached to the supply opening. Refer to Figure 8 as a
visual aid. The use of this block off plate will enable better air circulation
across the limit switches.

AIR FILTERS

Return air filters are required and must be field supplied. Filtration must
be accomplished external to the unit.

.

SECTION V: ELECTRIC HEATER 

INSTALLATION

If the air handler requires electric heat, install the electric heat kit
according to the installation instructions included with the kit. After
installing the kit, mark the air handler nameplate to designate the heater
kit that was installed. If no heater is installed, mark the name plate
appropriately to indicate that no heat kit is installed.
Use only 6HK Revision C or later heater kits, as listed on air handler
name plate and in these instructions. Use data from Tables 4 through 9
for information on required minimum motor speed tap to be used for
heating operation and maximum over-current protection device
required as listed for combination of air handler and heater kit.

For Upflow, Downflow and Horizontal left-hand applications, the kits can
be installed without modification. 

Field modification is required for Horizontal right-hand airflow applica-
tion only. Follow instructions with heater for modification.

SECTION VI: LINE POWER CONNECTIONS

Power may be brought into the unit through the supply air end of the
unit (top left when unit is vertical) or the left side panel. Use the hole
appropriate to the unit’s orientation in each installation to bring conduit
from the disconnect. The power lead conduit should be terminated at
the electrical control box. To determine proper wire sizing, refer to
Tables 3, 7-10 and the latest edition of the National Electric Code or in
Canada the Canadian electrical Code and local codes to determine
correct wire sizing. To minimize air leakage, seal the wiring entry point
at the outside of the unit.

All electrical connections to air handlers must be made with copper
conductors. 

Direct connection of aluminum wiring to air handlers is

not approved.

If aluminum conductors are present, all applicable local and national
codes must be followed when converting from aluminum to copper
conductors prior to connection to the air handler.

The chosen conductor and connections all must meet or exceed the
amperage rating of the overcurrent protector (service disconnect or
fuse) in the circuit.

Additionally, existing aluminum wire within the structure must be sized
correctly for the application according to National Electric Code and
local codes. Caution must be used when sizing aluminum rather than
copper conductors, as aluminum conductors are rated for less current
than copper conductors of the same size.

 FIGURE 8:  

Duct Work Transition

 CAUTION

Use 1/2” screws to connect duct work to unit. Longer screws will
pierce the drain pan and cause leakage. If pilot holes are drilled, drill
only though field duct and unit bottom duct flange.

 CAUTION

Equipment should never be operated without a filter.

A

0

332-

001

RE

COMM

ENDED

TRAN

S

ITI

O

N

S

UGGE

S

TED L

OC

ATI

O

N

O

F BL

OC

O

FF PLATE

!

!

NOTICE

In some horizontal applications, the service disconnects on the elec-
tric heat kits must be rotated 180° so the up position of the discon-
nect is the ON position. This service disconnect orientation change is
required by UL1995, Article 26.19 (in reference to all circuit break-
ers). 

Содержание ME08B

Страница 1: ...ld installed accessories Single phase kits are available from 2 5 kW to 25 kW 208 230 volt three phase kits are available from 10kW to 25kW SECTION II SAFETY This is a safety alert symbol When you see...

Страница 2: ...carrier s freight bill A separate request for inspection by the carrier s agent should be made in writing Also before installation the unit should be checked for screws or bolts which may have loosen...

Страница 3: ...URATION These air handler units are supplied ready to be installed in an upflow downflow horizontal right or horizontal left position Refer to Figure 2 The unit requires no conversion procedures AIR H...

Страница 4: ...ENSIONS C D 12 3 16 19 1 8 B 20 1 2 21 1 2 TABLE 1 Dimensions ME MODELS Dimensions1 Wiring Knockout Dimensions1 2 A B C D E F Height Width Bottom Opening Top Opening Power Control ME08B 21 1 2 17 1 2...

Страница 5: ...d be designed in accordance with the Air Conditioning Contractors of America ACCA Manual D HORIZONTAL SUSPENSION For suspension of these units in horizontal applications it is recom mended to use angl...

Страница 6: ...for Horizontal right hand airflow applica tion only Follow instructions with heater for modification SECTION VI LINE POWER CONNECTIONS Power may be brought into the unit through the supply air end of...

Страница 7: ...heat kit connected to tap 5 for the heating speed and the cooling heat pump connected to tap 4 for the heating speed The cooling heat pump indicating speed is supplied by the thermostat G signal The...

Страница 8: ...correct wire sizing TABLE 4 Electrical Heat Minimum Fan Speed Heater Kit Models1 2 3 Nom kW 240V Air Handler Models ME08B ME12B ME14D ME16C ME20D 6HK 0 1 6500206 2 4kW Med Lo 2 Med Lo 2 Med Lo 2 Med L...

Страница 9: ...onnect OR 1 with service disconnect 2 1 2 1 with service disconnect no breaker jumper bar OR 2 with service disconnect breaker jumper bar 3 6HK3 3 Phase with terminal block connectors only 6HK4 3 Phas...

Страница 10: ...Field Wiring Min Circuit Ampacity MOP 3 208V 230V 208V 230V TABLE 8 Electrical Data For Multi source Power Supply 208 230 1 60 Air Handler Models Heater Models Heater Amps 240V Min Circuit Ampacity M...

Страница 11: ...A and MOP requirements are given here only for reference if used with field installed single point power modification S1 32436041000 3 MOP Maximum Overcurrent Protection device must be HACR type circu...

Страница 12: ...MED HI 1272 1245 1209 1174 1143 1106 1073 3 MED 1072 1040 1007 973 937 874 778 2 MED LO 857 821 794 756 676 613 567 1 LO 654 606 557 504 443 379 271 CM30B 5 HI 1354 1325 1294 1263 1230 1198 1168 4 ME...

Страница 13: ...52 1706 1680 1633 1591 1546 1511 2 MED LO 1545 1505 1468 1432 1393 1351 1307 1 LO 1340 1296 1260 1219 1169 1118 1055 CM48D 5 HI 2062 2024 1993 1952 1910 1868 1836 4 MED HI 2006 1958 1932 1890 1850 181...

Страница 14: ...e fan only to assure a dry coil Drill 2 holes one 12 away from the air handler in the supply air duct and on 12 away from the air handler in the return air duct before any elbows in the duct work Inse...

Страница 15: ...L AND NATIONAL CODES MUST BE FOLLOWED SEE INSTALLATION INSTRUCTIONS FOR PROPER LOW VOLTAGE FIELD WIRING CONNECTIONS LEGEND LS LIMIT SWITCH SEQ SEQUENCER HE HEATING ELEMENT FL FUSIBLE LINK H SEQUENCER...

Страница 16: ...UE BLUE BLUE BLUE YELLOW YELLOW BLACK BLACK YELLOW YELLOW BLACK BLACK RED WHITE BLACK BLUE BLACK BLUE YELLOW BLACK YELLOW YELLOW BLUE BLACK BLUE BLACK YELLOW RLY 1 RLY 2 RLY 3 RLY 6 RLY 5 RLY 4 HE2 FL...

Страница 17: ...dry bulb temperature Return air dry bulb temperature Temperature drop 1 2 3 4 5 Low Medium Low Medium Medium High High A B C D Outside air dry bulb temperature Return air wet bulb temperature Supply a...

Страница 18: ...oting and correcting any problems Operate the unit through cooling cycles from the thermostat noting and correcting any problems Operate the unit through mechanical heating cycles from the thermostat...

Отзывы: