York MA - 115V Скачать руководство пользователя страница 5

262673-UIM-B-0707

Unitary Products Group

5

SECTION IV: LOW VOLTAGE CONTROL 

CONNECTIONS

The 24 volt power supply is provided by an internally wired low voltage
transformer which is standard on all models. See the unit wiring label.

Field supplied low voltage wiring can exit the unit on the top right hand
corner or the right hand side panel. Refer to Figure 3.

Remove desired knockout and pierce foil faced insulation to allow wir-
ing to pass through. Use as small of a hole as possible to minimize air
leakage.

Install a 7/8” plastic bushing in the selected hole and keep low voltage
wiring as short as possible inside the control box.

To further minimize air leakage, seal the wiring entry point at the outside
of the unit.

The field wiring is to be connected at the screw terminals of the control
board. Refer to Figure 8.

NOTE: 

All wiring must comply with local and national electrical code

requirements. Read and heed all unit caution labels.

The low voltage connections may be connected to the screw terminals
or the quick connect terminals. The screw terminals and the quick con-
nect terminals are physically connected on the control board.

HUMIDITY SWITCH INPUT

The air handler control is designed to work with a humidity control that
closes when the humidity is below the set-point. The control is open
when the humidity is above the set-point. This humidity control may be
referred to as a humidistat or a dehumidistat.

The humidity switch controls both humidification and de-humidification
operation of the control. The control provides humidification using the
HUM OUT relay output and de-humidification by lowering the blower
speed. This is accomplished using the LOW FAN output and a field
installed two-speed fan relay kit for non-variable speed models and the
de-humidification input of the motor for variable speed models. The
humidity switch should be connected to the R and HUM terminals of the
control. See Figure 8.

SECTION V: REQUIRED CONTROL 

SET-UP

IMPORTANT: 

The following steps must be taken at the time of installa-

tion to insure proper system operation.

1.

Consult system wiring diagram to determine proper thermostat
wiring for your system.

2.

HEAT ENABLE jumper must be set to NO HEAT position.

3.

If a humidstat is installed, change HUM STAT jumper from NO to
YES.

4.

Set the MODE jumper to A/C (Air Conditioner) or HP (Heat Pump)
position depending on the outdoor unit included with the system.

FUNCTIONALITY AND OPERATION

Jumper Positions

Refer to Figure 5 for details of control board showing component loca-
tions.

Heat Enable Jumper

The jumper must be in the NO HEAT position. This unit cannot be used
with heat.

With the jumper in the NO HEAT position, the control will not energize
the heat relay outputs or sense the limit switch input.

If the jumper is not present, the control will operate as if the jumper is in
the HEAT position. If the jumper is not present and a heat kit is not
present, the control will sense an open limit condition and the blower
will run continuously.

 FIGURE 5:  

Control Board

HEAT ENABLE

JUMPER

HUM OUT

RELAY OUTPUT

EAC

RELAY OUTPUT

LOW FAN

RELAY OUTPUT

SPARE JUMPER

HUM STAT JUMPER

MODE JUMPER

FUSE

TABLE 2: 

Low Voltage Connections

Terminal

Signal

Comment

R

24 VAC power (fused)

G

Continuous Fan operation

Y/Y2

Second or full stage 
compressor operation

Y1

First stage compressor 
operation

Not used with outdoor units 
having one stage compressors.

W2

Second stage heat operation

W1

First stage heat operation

O

Reversing valve operation

24 VAC will be present at this
terminal when the MODE
jumper is in the AC position.
This is normal.

HUM

Humidity switch input

24 VAC will be present at this
terminal when the HUM STAT
jumper is in the NO position.
This is normal.

X/L

Connection point for 
heat pump fault indicator

This terminal is a connection
point only and does not affect
air handler control operation.

COM

24 VAC common

Содержание MA - 115V

Страница 1: ...rate injury It is also used to alert against unsafe practices and hazards involving only property dam age Improper installation may create a condition where the operation of the product could cause personal injury or property damage Improper installation adjustment alteration service or mainte nance can cause injury or property damage Refer to this manual for assistance or for additional informati...

Страница 2: ...e who have not kept up with changing residential and non HUD modular home construction practices These instructions are required as a minimum for a safe installation INSPECTION As soon as a unit is received it should be inspected for possible dam age during transit If damage is evident the extent of the damage should be noted on the carrier s freight bill A separate request for inspection by the c...

Страница 3: ...is document 8 Reposition and replace blower access panel AIR HANDLER AND COIL DOWNFLOW INSTRUCTIONS 1 Position blower casing over duct connection and secure such that the supply air end of the blower is down 2 Apply neoprene gasket to return air side of air handler 3 Place coil casing over blower return opening NOTE Tie plate and screws are provided with coils 4 Attach tie plate to casings of air ...

Страница 4: ...al and or national codes This includes the standards of the National Fire Protection Association for Installation of Air Conditioning and Ventilat ing Systems NFPA No 90B AIR FILTERS Air filters and filter racks must be field supplied SUSPENSION KITS A suspension kit is available Models 1BH0601 unit size 018 060 is designed specifically for the units contained in this instruction upflow applicatio...

Страница 5: ...s The humidity switch should be connected to the R and HUM terminals of the control See Figure 8 SECTION V REQUIRED CONTROL SET UP IMPORTANT The following steps must be taken at the time of installa tion to insure proper system operation 1 Consult system wiring diagram to determine proper thermostat wiring for your system 2 HEAT ENABLE jumper must be set to NO HEAT position 3 If a humidstat is ins...

Страница 6: ... can be used to drive an external relay 24 VAC coil that switches the power input to the motor to a lower speed tap An accessory kit is available for this application The LOW FAN output is energized when the control has the following inputs as shown in Table 4 Blower Delays The control includes the following blower delays as shown in Table 5 SECTION VI LINE POWER CONNECTIONS Power may be brought i...

Страница 7: ...1607 1533 1463 1395 1319 1044 851 725 673 673 Med 1308 1258 1197 1146 1097 887 742 648 608 609 Low 1148 1108 1061 1017 976 807 690 613 582 582 MC43B High 1462 1396 1322 1254 1172 1067 941 693 585 464 Med 1205 1154 1102 1046 980 897 704 560 441 220 Low 1075 1020 969 906 842 735 592 470 364 190 16C MC42C High 1959 1874 1802 1708 1606 1486 1408 1264 953 810 Med 1631 1587 1542 1473 1395 1315 1218 967 ...

Страница 8: ... Control Board 4 MODE Jumper on AH control board should be set to A C for air conditioners and HP for heat pumps SECTION IX MAINTENANCE Filters must be cleaned or replaced when they become dirty Inspect at least once per month The frequency of cleaning depends upon the hours of operation and the local atmospheric conditions Clean filters keep unit efficiency high LUBRICATION The bearings of the bl...

Отзывы: