18
5-Speed ECM Constant Torque Motors
The 5-Speed ECM is a ‘Constant Torque’ ECM motor and delivers
air flow similar to a PSC but operates as efficiently as an ECM Motor.
Because it’s an ECM Motor, the 5-Speed ECM can ramp slowly up or
down like the ECM motor. There are 5 possible speed taps available
on the 5-Speed ECM motor with #1 being the lowest airflow and #5
being the highest airflow. These speed selections are preset at the
time of manufacture and are easily changed in the field if necessary.
If more than one tap are energized at the same time, built in logic
gives precedence to the highest tap number and allows air flow to
change with G, Y1, Y2 and W signals or with Fan, CC, CC2, and
E1 output signals. Each of those 5 speeds has a specific ‘Torque’
value programmed into the motor for each speed selection.
As static pressure increases, airflow decreases resulting in less
torque on the rotor. The motor responds only to changes in torque
and adjusts its speed accordingly.
The 5-Speed ECM motor is powered by line voltage but the motor
speed is energized by 24 VAC.
5-Speed ECM Benefits:
-
High
efficiency
-
Soft
start
- 5 speeds with up to 4 speeds on-line
- Built in logic allows air flow to change with G, Y1, Y2 and W
signals
- Super efficient low airflow continuous blower setting (G)
Blower Performance Data
S
i
Bl
S
d
S
d ECM
Dual Capacity with 5-Speed ECM
Model
Motor
Speed
Motor
Tap
T’stat
Cnct.
Blower
Size
Motor
HP
Airflow (cfm) at External Static Pressure (in. wg)
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0.4
0.45
0.5
0.6
0.7
0.8
0.9
1.00
024
High
5
W
9 x 7
1/2
1024
1013 1002
988
974
963
951
940
929
901
872
785
691
-
-
-
Med High
4
Y2
932
917
902
892
882
867
851
842
832
817
802
756
661
-
-
-
Med
3
835
826
816
801
785
772
759
749
738
719
700
677
636
-
-
-
Med Low
2
Y1
765
747
729
720
710
696
681
662
643
627
611
581
515
-
-
-
Low
1
G
665
656
647
626
605
593
580
561
541
519
496
443
392
-
-
-
036
High
5
W
9 x 7
1/2
1325
1319 1313 1293
1272
1242 1212 1158 1103
1058 1013
930
839
-
-
-
Med High
4
Y2
1279
1267 1254 1238
1222
1203
1184 1137 1089 1049 1008
926
836
-
-
-
Med
3
1229
1218 1206 1187
1167
1154
1140 1110 1079 1044 1008
929
829
-
-
-
Med Low
2
Y1
1201
1184
1167
1156
1145
1129
1113 1086 1058 1028
997
914
808
-
-
-
Low
1
G
1007
989
971
958
945
925
904
889
873
862
850
818
778
-
-
-
048
High
5
W
11 x 10
1
1890
1874 1857 1845
1833
1809 1784 1769 1754 1736 1718 1672 1629
1601
1562 1522
Med High
4
Y2
1769
1754 1739 1721
1703
1685 1666 1645 1623 1604 1585 1539 1499
1463
1432 1376
Med
3
1671
1652 1632 1614
1595
1576 1557 1536 1514 1494 1474 1430 1387
1351
1313 1173
Med Low
2
Y1
1574
1555 1535 1514
1492
1472 1452 1431 1410 1387 1363 1330 1284
1236
1108 1014
Low
1
G
1388
1370 1352 1322
1292
1264 1236 1216 1195
1178 1161 1095
984
916
842
787
060
High
5
W
11 x 10
1
2077
2066 2055 2044
2033
2017 2000 1966 1931 1904 1877 1841 1810
1791
1740 1653
Med High
4
Y2
1948
1937 1925 1910
1895
1880 1865 1831 1797 1778 1759 1720 1707
1680
1660 1612
Med
3
1810
1794 1778 1739
1700
1684 1667 1657 1646 1629 1612 1576 1583
1547
1510 1480
Med Low
2
Y1
1680
1667 1653 1618
1583
1562 1540 1522 1503 1488 1473 1465 1449
1410
1369 1319
Low
1
G
1594
1572 1550 1512
1474
1450 1426 1410 1393 1385 1376 1351 1325
1290
1168 1085
072
High
5
W
11 x 10
1
2402
2388 2373 2358
2343
2334 2325 2307 2289 2274 2258 2215 2177
2125
2052 1933
Med High
4
Y2
2209
2193 2177 2164
2151
2135
2118 2105 2092 2072 2052 2017 1982
1954
1925 1844
Med
3
2085
2072 2058 2045
2031
2010 1989 1972 1954 1936 1918 1881 1852
1821
1790 1751
Med Low
2
Y1
1961
1951 1940 1926
1911
1885 1859 1844 1829 1814 1798 1759 1727
1703
1670 1636
Low
1
G
1767
1751 1735 1715
1694
1678 1661 1640 1619 1602 1584 1548 1512
1475
1426 1397
Factory speed settings are in Bold 7/30/14
Air flow values are with dry coil and standard filter
For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]).
Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.12in. wg., and 500 fpm by 0.16 in. wg.
Highest setting is for auxiliary heat (W) and lowest setting is for constant blower (G). The “Y1” and “Y2” settings must be between the “G” and “W” settings.
L
G
N
C
1
2
3
4
5
AUX - Gray
G - Blue
Y1 - Red
Y2 - Tan
C - Black
L - Orange
G - Green
N - Brown
High Voltage
Connections
3/16 in.
Low Voltage
Connections 1/4 in.
5-Speed ECM Motor Connections - Dual Capacity
CAUTION: Disconnect all power before performing
this operation.
Setting Blower Speed - 5-Speed ECM
5-Speed ECM blower motors have five (5) speeds of which four (4
are selectable on dual capacity.
LX SERIES INSTALLATION MANUAL