manualshive.com logo in svg
background image

Notes: 

Air handler units have been tested to UL 60335-2-40 / CSA 22.2 No. 236 standards up to 0.6 in. W.C. external static pressure.

Dry coil conditions only, tested without filters.

For optimal performance, external static pressures of 0.2 in. W.C to 0.5 in. W.C are recommended. Heating applications tested at 0.5 in. W.C. external static pressure.
Above 0.5 in. W.C., CFM is reduced by 2% per 0.1 in. increase in static.

Low speed cooling used only with two stage outdoor units. Speed is preset to 65% of high speed.

Dehumidification speed is 85% of jumper selected cool tap.

Any compressor operation uses HI COOL and LO COOL DIP switches. Indoor heating operates off the heatkit selection and the HEAT DIP switches.

At some settings, low cool and/or low heat airflow may be lower than what is required to operate an airflow switch on certain models of electronic air cleaners. Consult
the instructions for the electronic air cleaner for further details.

Airflow (CFM) indicator light (LED2) flashes once for every 100 CFM (for example, 12 flashes is 1200 CFM) - blinks are approximate ±10% of actual CFM.

Airflow selection

When not using communicating functionality, you must set the airflow
and comfort setting selection switches correctly at the time of installation
for correct system operation. Place switches in the correct locations
based on the information shown in 

Table 2

. An example of switch posi-

tions is shown below in 

Figure 2

. 0 indicates the OFF position and 1 indi-

cates the ON position. The airflow configuration switches are located in
the SW4 switch bank.

Inputs to the air handler control board pass to the motor, which deter-
mines the target CFM to deliver. Refer to the

 Installation Manual

 for more

information on these inputs.

These variable speed air handlers are designed to deliver constant
airflow (CFM) regardless of the external static pressure (ESP) in the
ductwork. Therefore, if too many supply registers are closed, a filter
becomes clogged, or there is a restriction in the ductwork, the motor
automatically operates at a higher speed to compensate for the higher
ESP. This may result in a higher operating sound level and motor
damage.

Table 2: 

Airflow data (CFM)

DIP Switch

B18B

B24C

B36D

C36D

C42F

D42F

High cool Low cool High cool Low cool High cool Low cool High cool Low cool High cool Low cool High cool Low cool

000

575

400

700

475

800

550

825

600

1100

700

1125

675

001

625

450

725

525

900

600

900

650

1200

750

1225

875

010

675

475

800

575

975

650

1000

700

1300

800

1325

925

011

725

525

850

625

1075

700

1050

750

1400

850

1425

1000

100

775

550

925

650

1150

775

1150

825

1500

925

1550

1075

101

850

575

975

700

1250

825

1225

850

1625

975

1675

1150

110

900

625

1075

725

1325

900

1300

900

1725

1050

1775

1225

111

950

650

1100

775

1400

950

1350

950

1825

1100

1875

1275

DIP Switch

C48G

D48G

C60H

D60H

D60J

High cool Low cool High cool Low cool High cool Low cool High cool Low cool High cool Low cool

000

1150

725

1125

700

1400

975

1400

975

1375

925

001

1250

775

1225

875

1525

1075

1550

1075

1475

1050

010

1350

850

1325

925

1650

1150

1700

1150

1750

1125

011

1450

900

1425

1000

1800

1250

1850

1250

1875

1225

100

1575

975

1550

1075

1925

1350

2000

1350

2000

1350

101

1675

1025

1675

1150

2050

1425

2125

1425

2000

1400

110

1775

1100

1800

1225

2050

1525

2125

1550

2000

1475

111

1875

1150

1900

1275

2050

1600

2125

1650

2000

1575

 Figure 2: 

DIP-10

ON

DIP Switch example: 0101000110

1

2

3

4

5

6

7

8

9

10

A1708-001

NOTICE

Incorrect airflow and comfort settings may result in decreased system
efficiency and performance.

Clearances 

It is essential to provide the following clearances:

Refrigerant piping and connections - minimum 12 in.

Maintenance and servicing access - minimum 36 in. from the front
of the unit for blower motor or coil replacement

Condensate drain lines routed to clear filter and panel access

Filter removal - minimum 36 in.

The supply air ductwork connected to this unit is designed for 1 in.
clearance for the first 18 in. of combustible materials if an electric
heat kit accessory is installed.

A combustible floor base accessory is available for downflow appli-
cations of this unit, if required by local code.

External duct static

Measure the supply air static pressure. Record this positive number.
Measure the return air static pressure. Record this negative number.
Treat the negative number as a positive and add the two numbers
together to determine the total external system static pressure. If a filter
rack is installed on the return air end of the air handler or indoor coil
section, make sure to measure the return air duct static between the filter
and the indoor coil.

Figure 3:  

Duct static measurements

Take measurements here if using
a filter rack.
Return air static must be taken
between the filter and indoor coil.

A1704-001

Table 3: 

Electrical heat: minimum fan CFM for single-phase heatkits

Heater kit

models

1,2

Nominal 

kW

at 240 V

Airflow 

configuration 

heat dip switch 

setting*

Aux heat 

configuration 

heatkit 

selection dip 

switch setting

Air handler models (CFM

3

)

B18B B24C B36D C36D

C42F

D42F

C48G D48G C60H D60H

D60J

8HK(0,1)6500206

2.4

00

0001

625

650

625

825

825

825

825

825

825

825

825

8HK(0,1)6500506

4.8

00

0010

650

650

650

825

825

825

825

825

825

825

825

8HK(0,1)6500806

7.7

00

0011

750

800

750

1100

1100

1150

1100

1150

1100

1150

1150

8HK(0,1)6501006

9.6

00

0100

790

950

750

1100

1100

1500

1100

1500

1100

1500

1500

8HK(1,2)6501506

14.4

00

0101

650, 

950

650, 

975

825, 

1100

825, 

1100

825, 

1575

825, 

1100

825, 

1575

825, 

1100

825, 

1575

825, 

1700

8HK(1,2)6502006

19.2

00

0110

750, 

975

1100, 

1300

1100, 

1300

1325, 

1575

1100, 

1300

1325, 

1575

1100, 

1300

1325, 

1575

1500, 

1700

8HK(1,2)6502506

24

00

0111

1325, 

1650

1325, 

1650

1500, 

1800

1. (0,1) - 0 = no service disconnect or 1 = with service disconnect.
2. (1,2) - 1 = with service disconnect, no breaker jumper bar or 2 = with service disconnect and breaker jumper bar.
3. For minimum fan CFM, if there are two values present, the first value is low-stage CFM (W1) and the second value is full-stage CFM (W1+W2). If higher kW/CFM is 
needed for low-stage, see 

Table 5

.

* To increase airflow by approximately 20%, adjust the HEAT DIP switches from 00 to 01.

Table 4: 

Electrical heat: minimum fan CFM for three-phase heatkits

Heater kit

models

1,2

Nominal 

kW

at 240 V

Airflow 

configuration 

heat dip switch 

setting*

Aux heat 

configuration 

heatkit 

selection dip 

switch setting

Air handler models (CFM

3

)

B18B B24C B36D C36D

C42F

D42F

C48G D48G C60H D60H

D60J

8HK06501025

9.6

00

1000

790

950

1150

1150

1150

1500

1150

1500

1150

1500

1700

8HK06501525

14.4

00

1001

950

1150

1150

1150

1575

1150

1575

1150

1575

1700

8HK16502025

19.2

00

1010

1150, 

1150

1150, 

1300

1150, 

1400

1500, 

1575

1150, 

1300

1500, 

1575

1150, 

1300

1500, 

1575

1700

8HK16502525

24

00

1011

1575, 

1650

1575, 

1650

1700, 

1800

1. (0,1) - 0 = no service disconnect or 1 = with service disconnect.
2. (1,2) - 1 = with service disconnect, no breaker jumper bar or 2 = with service disconnect and breaker jumper bar.
3. For minimum fan CFM, if there are two values present, the first value is low-stage CFM (W1) and the second value is full-stage CFM (W1+W2). If higher kW/CFM is 
needed for low-stage, see 

Table 5

.

* To increase airflow by approximately 20%, adjust the HEAT DIP switches from 00 to 01.

Table 5: 

Aux heat configuration - stage 1 kW dip switch settings

W1 = W1

00, 01

W1 = W2

10

W1 = W1 + W2

11

Отзывы: