10
P01432Q-rev.1
5.3 Mounting Indoor Unit
Hang the indoor unit as shown in Figure 5.3.
Field-Supplied Parts
* Suspension Bolts: 4-M10 or W3/8
* Nut: 8-M10 or W3/8
5.2 Suspension Bolts and Piping Connections
(1) Mark the positions of the suspension bolts, refrigerant pipe connections and condensate pipe
connection.
(2) Installation dimensions are shown in Figure 5.2.
Suspension
Bracket
Suspension Bolts (4-M10 or W3/8)
(Field-Supplied)
False Ceiling Side
Max. 29-1/2 [750]
Vibration-proof
Rubber
(Accessory)
Nut & Washer
(8-M10 or W3/8)
Unit
Figure 5.3 Mounting Indoor Unit
Figure 5.2 Suspension Bolts
1-15/16 [50]
5-7/16
[138]
1-9/16 [40]
49-3/16 [1250]
52-3/8 [1330] (for Suspension Bolt)
39-3/8 [1000]
56 -
φ
1/8 [3]
Around the Flange
2-9/16 x 1-3/8 [65 x 35]
(for Suspension Bolt)
Refrigerant Gas Pipe Connection
Refrigerant Liquid Pipe Connection
Condensate Pipe Connection
9-7/8 [251]
13-5/8 [346
]
16-
11
/16 [424]
1/2 [13]
15/16 [24]
40-3/16 [1021] (for Suspension Bolt
)
1 [25]
5/8 [16]
1-1/8 [28]
42-1/16 [1069]
7/8 [23]
1-15/16 [50]
4-7/16
[113]
41-5/16 [1050]
60 -
φ
1/8 [3]
Around the Flange
Unit: inch [mm]