background image

036-21323-002-C-0206

Unitary Products Group

11

REFRIGERANT PIPING

GENERAL GUIDELINES

Many service problems can be avoided by taking adequate
precautions to provide an internally clean and dry system and
by using procedures and materials that conform with estab-
lished standards.

Use hard drawn copper tubing where no appreciable amount
of bending around pipes or other obstructions is necessary.
Use long radius ells wherever possible with one exception -
small radius elbows for the traps in all vapor risers. If soft cop-
per is used, care should be taken to avoid sharp bends which
may cause a restriction.

Pack fiber glass insulation and a sealing material such as
permagum around refrigerant lines where they penetrate a
wall to reduce vibration and to retain some flexibility.

Support all refrigerant lines at minimum intervals with suitable
hangers, brackets or clamps.

Insulate all vapor lines with a minimum of 1/2” ARMA-FLEX
or equal. Liquid lines exposed to direct sunlight and/or high
temperatures must also be insulated.

Never solder vapor and liquid lines together. They can be
taped together for convenience and support purposes, but
they must be completely insulated from each other.

LINE SIZING

When sizing refrigerant lines for a split-system air conditioner,
check the following:

1.

Suction line pressure drop due to friction at full capacity,

2.

Liquid line pressure drop due to friction at full capacity,

3.

Suction line velocity for oil return at part capacity, and

4.

Liquid line pressure drop due to static head.

NOTE:

Never base refrigerant line sizes on the OD of the
suction and liquid connections on the unit.

Tables 13 and 14 list friction losses for both the suction and
liquid lines on the system. Table 12 shows the amount of
refrigerant charge required per foot of refrigerant line.

When the evaporator coil is below the condensing unit, the
suction line must be sized for both pressure drop and for oil
return. For certain piping arrangements, different suction line
sizes may have to be used. The velocity of the suction gas
must always be great enough to carry oil back to the com-
pressor.

When the condensing unit is below the evaporator coil, the
liquid line must be designed for the pressure drop due to both
friction loss and vertical rise. If the total pressure drop
exceeds 40 psi, some refrigerant may flash before it reaches
the thermal expansion valve. This flashing will not only cause
erratic valve operation and poor system performance, but
could also damage the expansion valve.

TABLE 12: REFRIGERANT LINE CHARGE

1

1. Charges are based on 40°F suction temperature and 

105°F liquid temperature.

Refrigerant Line

2

2. Type “L” copper tubing.

Line Size

O.D. (in.)

Refrigerant

Charge (lb./ft.)

Liquid

5/8

0.113

Vapor

1-1/8

0.013

1-3/8

Содержание HB 240

Страница 1: ...ce port connections Refrigerant 22 holding charge Five minute compressor anti short cycle timer Two independent control circuits Compressor operation to 40 F Field installed Low Ambient VFD Control to...

Страница 2: ...0 22 13 LB180 SUPPLY AIR PLENUM DIMENSIONS 23 14 RETURN AIR GRILLE FOR LB180 DIMENSIONS 23 LIST OF TABLES Tbl Pg 1 UNIT APPLICATION DATA 7 2 ARI RATINGS COOLING AND SOUND 7 3 ELECTRICAL DATA COMPRESSO...

Страница 3: ...vertical applications the air velocity across the indoor coil keeps the condensate from dripping off the finned surface onto the filters NOTE On horizontal applications the unit must be installed with...

Страница 4: ...ad operation Field installed Pump Out Kit for applications where liquid slugging could be an issue FIGURE 2 INDOOR PRODUCT NOMENCLATURE YORK INDOOR PRODUCT NOMENCLATURE H A 120 C 0 0 A 2 A A A 1 A Mod...

Страница 5: ...Base Sections are available to raise vertical indoor units above the floor Outdoor air may be introduced through these bases by cutting an access opening for the out door air duct connection These ba...

Страница 6: ...Unitary Products Group FIGURE 4 VERTICAL ARRANGEMENTS LB180 AND LB240 FIGURE 5 HORIZONTAL ARRANGEMENTS LB180 AND LB240 CERTAIN BLOWER POSITIONS ARE NOT RECOMMENDED BECAUSE THE BLOWER MOTOR SHOULD NOT...

Страница 7: ...rd 370 TABLE 3 ELECTRICAL DATA COMPRESSORS Model Number Compressors Power Supply System 1 System 2 RLA LRA RLA LRA HB180 208 230 3 60 25 6 190 0 25 6 190 0 HB180 460 3 60 12 8 95 0 12 8 95 0 HB180 575...

Страница 8: ...ctly connected to the condenser fans Motor rotation is counterclockwise when viewing the lead end which is opposite the shaft end 3 The amount of charge in the unit as shipped from the factory 4 Total...

Страница 9: ...er Wiring 2 1 8 KO 2 1 8 KO Control Wiring 7 8 KO 7 8 KO TABLE 9 UNIT CLEARANCES Location Dimensions Overhead Top 1 1 Units must be installed outdoors Overhanging structures or shrubs should not obstr...

Страница 10: ...ON LOCATIONS TABLE 11 PIPING AND ELECTRICAL CONNECTION SIZES CONNECTION ENTRY SIZE A SUCTION LINE SYS 1 1 1 8 ID 15 Ton 1 3 8 ID 20 Ton B LIQUID LINE SYS 1 5 8 ID C SUCTION LINE SYS 2 1 1 8 ID 15 Ton...

Страница 11: ...check the following 1 Suction line pressure drop due to friction at full capacity 2 Liquid line pressure drop due to friction at full capacity 3 Suction line velocity for oil return at part capacity a...

Страница 12: ...should be sized for a friction loss equivalent to a 2 F change in saturation temperature or approximately 3psi sizing the lines for the proper return of oil is more important 5 These friction losses...

Страница 13: ...145 7 123 4 101 0 Indicates Nominal Capacity Rating Point INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR 15 Ton Capacity Tables HB180 Matched with LB180 AIR...

Страница 14: ...0 2 127 8 105 5 83 1 Indicates Nominal Capacity Rating Point INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR 15 Ton Capacity Tables HB180 Matched with LB180 AI...

Страница 15: ...5 127 3 112 1 97 0 81 8 57 150 4 22 0 150 4 147 6 138 6 123 5 108 3 93 1 78 0 6000 72 174 2 23 3 129 7 112 2 94 7 77 2 59 7 N A N A 67 160 1 22 7 159 4 141 9 124 4 106 9 89 4 71 9 54 4 62 149 2 22 1 1...

Страница 16: ...89 8 162 4 134 9 Indicates Nominal Capacity Rating Point INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR 20 Ton Capacity Tables HB240 LB240 AIR ON EVAPORATOR O...

Страница 17: ...MOTORS BUT NOT THE INDOOR BLOWER MOTOR 20 Ton Capacity Tables HB240 LB240 AIR ON EVAPORATOR OUTDOOR AMBIENT TEMPERATURE F 115 CFM W B GROSS INPUT GROSS SENSIBLE CAPACITY MBh TEMP CAP POWER RETURN AIR...

Страница 18: ...3 1 2 91 972 3 6 3 36 5600 688 1 9 1 76 776 2 4 2 24 859 2 9 2 68 924 3 3 3 05 981 3 8 3 56 5800 696 2 0 1 85 785 2 5 2 36 873 3 0 2 83 931 3 4 3 2 990 4 0 3 75 6000 647 1 9 1 78 704 2 1 1 95 794 2 7...

Страница 19: ...N BLOWER PERFORMANCE 15 TON BLOWER PERFORMANCE 0 4 0 6 0 8 1 1 2 1 4 1 6 4200 4700 5200 5700 6200 6700 7200 7700 CFM ESP FIGURE 9 20 TON BLOWER PERFORMANCE 20 TON BLOWER PERFORMANCE 0 4 0 6 0 8 1 1 2...

Страница 20: ...8 1LD0437 800 1000 2LR04605032 184 230 460 1LD0437 800 1000 2LP04605058 184 575 1LD0437 800 1000 1LD0439 700 830 LB240 5 2LR04605023 184 208 1LD0438 580 720 1LD0439 700 830 2LR04605032 184 208 230 460...

Страница 21: ...Ton Indoor Vertical 720 830 198 224 217 191 89 5 29 5 20 Ton Indoor Horizontal 990 1115 212 195 340 368 100 74 20 Ton Indoor Vertical 990 1115 281 254 276 305 100 36 5 FIGURE 10 HORIZONTAL APPLICATIO...

Страница 22: ...TION D D D E LESS BOTTOM PANEL BLOWER SECTION J L K K KNOCKOUT FOR SUCTION PIPING KNOCKOUT FOR LIQUID PIPING KNOCKOUT FOR DRAIN PIPING 4 9 16 10 3 16 2 7 32 19 3 32 3 1 2 5 25 64 3 3 8 5 1 3 8 Knockou...

Страница 23: ...036 21323 002 C 0206 Unitary Products Group 23 FIGURE 13 LB180 SUPPLY AIR PLENUM DIMENSIONS1 1 Shipped knocked down for field assembly FIGURE 14 RETURN AIR GRILLE FOR LB180 DIMENSIONS...

Страница 24: ...bration generated by the unit CONDENSER LA300 LB180 240 360 480 600 EACH UNIT SHALL BE ETL and cETL approved completely assembled for one piece shipping and rig ging leak pressure and functionally tes...

Отзывы: