USER’S INFORMATION,

MAINTENANCE AND 

SERVICE MANUAL

HIGH EFFICIENCY

TUBULAR HEAT EXCHANGER SERIES
MODELS: 

PT8/ FC8T / FL8T / LC8T / LL8T

(Two Stage Upflow / Horizontal / LoNOx)

EFFICIENCY
RATING
CERTIFIED

This product was manufactured
in a plant whose quality system
is certified/registered as being
in conformity with ISO 9001.

The manufacturer recommends that the user read all sec-
tions of this manual and keep the manual for future refer-
ence.

 

SECTION I: USER’S INFORMATION

SAFETY

1.

The furnace area must be kept clear and free of combustible mate-
rials, gasoline and other flammable vapors and liquids.

2.

Insulating materials may be combustible. The furnace must be
kept free and clear of insulating materials. The furnace area must
be examined when installed in an attic or other insulated space or
when insulation is added to be sure that the insulation material has
been kept away from the furnace.

3.

The furnace needs air for combustion in order to operate properly
and safely. Do not block or obstruct air openings on the furnace, air
openings to the area where the furnace is installed, or spaces
around the furnace.

4.

Follow the instructions exactly as shown on the OPERATING
INSTRUCTION LABEL or the Start-up and Shutdown Instructions
on Page 3 of this manual when lighting the furnace or turning the
furnace off.

5.

Should the gas supply fail to shut off or if overheating occurs, shut
off the gas valve to the furnace before shutting off the electrical
supply.

6.

Do not use this furnace if any part has been under water. A flood-
damaged furnace is extremely dangerous. Attempts to use the fur-
nace can result in fire or explosion. A qualified service agency
should be contacted to inspect the furnace and replace all gas con-
trols, control system parts, electrical parts that have been wet or
the furnace if deemed necessary.

FIRE OR EXPLOSION HAZARD - 

Failure to follow safety

warnings exactly could result in serious injury, death, or prop-
erty damage.

— 

Do not store or use gasoline or other flammable

vapors and liquids in the vicinity of this or any other
appliance.

—  

WHAT TO DO IF YOU SMELL GAS:

Do not try to light any appliance.

Do not touch any electrical switch; do not use any phone 
(including cell phone) in your building.

Leave the building immediately.

Immediately call your gas supplier from a neighbor’s 
phone. Follow the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire depart-
ment.

— 

 Installation and service must be performed by a quali-

fied installer, service agency or the gas supplier.

CONTACT INFORMATION

Go to website at www.york.com click on “contact”, then click on “contact form” and follow the instructions.

Contact us by mail:

York International

Consumer Relations

5005 York Drive

Norman, OK 73069

TABLE OF CONTENTS

CONTACT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

USER’S INFORMATION  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

SAFETY   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTRUCTIONS FOR EXAMINING THE FURNACE 
INSTALLATION   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
HOW YOUR GAS FURNACE WORKS   . . . . . . . . . . . . . . . . . . . . . . 3
START-UP AND SHUTDOWN INSTRUCTIONS  . . . . . . . . . . . . . . . 3

Read the Instructions Below Before Trying to Start the Furnace . . 3
Operating Instructions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
To Turn Off the Appliance: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

FURNACE USER MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Air Filters  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Removing Filters   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Blower Care  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Motor Lubrication  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

SERVICE AND MAINTENANCE MANUAL . . . . . . . . . . . . . . . . . . . . . 5

SAFETY SECTION  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

FURNACE MAINTENANCE SECTION  . . . . . . . . . . . . . . . . . . . . . . .5
FURNACE CLEANING SECTION . . . . . . . . . . . . . . . . . . . . . . . . . . .5

Burner Removal/Cleaning   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Cleaning the Heat Exchanger   . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

SEQUENCE OF OPERATION   . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

Heating Indoor Fan Off Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Continuous Blower:   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Hot Surface Ignition System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

TROUBLESHOOTING   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
FURNACE DIAGNOSTICS  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
DIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL   . . . . . .8

REPLACEMENT PARTS LIST   . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

FIELD INSTALLED ACCESSORIES - NON-ELECTRICAL   . . . . . .12

REPLACEMENT PART CONTACT INFORMATION . . . . . . . . . . . . .12
WIRING DIAGRAM   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
LIMITED WARRANTY  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16

Содержание FC8T

Страница 1: ...all gas con trols control system parts electrical parts that have been wet or the furnace if deemed necessary FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious...

Страница 2: ...pace containing the furnace 4 Examine the furnace casing making sure the physical support is sound without sagging cracks or gaps Examine the furnace base making sure it is physically sound without cr...

Страница 3: ...water Operating Instructions 1 STOP Read the safety information above 2 Set the thermostat to the lowest setting 3 Turn off all electric power to the appliance 4 Remove burner door 5 Move gas control...

Страница 4: ...ve a bottom or side return air duct using the following method a If the return air filter is on the left or right side of the furnace it is a side return b If the air filter is on the bottom of the fu...

Страница 5: ...rner assembly 7 Burners may be cleaned by rinsing in hot water 8 Reassemble the burners in the reverse order Cleaning the Heat Exchanger Lower Heat Exchanger Access 1 Turn off the electrical power to...

Страница 6: ...acts of 2LP The High Fire Pressure Switch The Control checks that 2LP is closed The Gas Valve is energized on 2nd Stage High Fire The Control simultaneously de energizes the Heat Low relay and energiz...

Страница 7: ...to the fur nace SLOW GREEN FLASH Normal operation SLOW AMBER FLASH Normal first stage operation with call for heat AMBER PULSE Normal second stage operation with call for heat 3 FLASHES AMBER Indicate...

Страница 8: ...MINUTE AUTOMATIC RESET FROM LOCKOUT This control includes a watch dog type circuit that will reset from a lockout condition after 60 minutes Operational faults 6 7 8 will be reset This provides protec...

Страница 9: ...W INDUCER LOW STAGE PRESSURE SWITCH HSI 1ST STAGE MAIN VALVE FLAME SENSE LOW CIRCULATOR HEAT SPEED 1ST STAGE LOW PRESSURE SWITCH CLOSE RECOGNITION HSI WARM UP 17 SEC IGNITION ACTIVATION PERIOD 4 SEC T...

Страница 10: ...19671 002 Rev A 0704 10 Unitary Products Group SECTION III REPLACEMENT PARTS LIST 2 4 11 9 5 3 6 8 7 12 13 16 17 26 53 28 42 39 29 38 43 21 25 32 33 35 31 27 23 22 44 30 24 18 20 12A 7 35 24 36 12 19...

Страница 11: ...NGER ASS Y 25 MANIFOLD GAS 26 PANEL UPPER ACCESS 27 PAN BASE 28 PANEL BLOWER ACCESS 29 PANEL TOP 30 WRAPPER INSULATED 31 CHANNEL TOE PLATE 32 BRACKET TOP DOOR 33 BRACKET BOTTOM DOOR 34 RACK FILTER 35...

Страница 12: ...650 78 N1 1V 1PS0314 1CB0314 COMBUSTIBLE FLOOR BASE FOR DOWNFLOW UNITS ALL 14 1 2 A CABINETS 1CB0317 ALL 17 1 2 B CABINETS 1CB0321 ALL 21 C CABINETS 1CB0324 ALL 24 1 2 D CABINETS REPLACEMENT PART CON...

Страница 13: ...035 19671 002 Rev A 0704 Unitary Products Group 13 SECTION IV WIRING DIAGRAM FIGURE 9 Wiring Diagram...

Страница 14: ...035 19671 002 Rev A 0704 14 Unitary Products Group NOTES...

Страница 15: ...035 19671 002 Rev A 0704 Unitary Products Group 15 NOTES...

Страница 16: ...anty applies only to products installed in the United States and Canada EXCLUSIONS This warranty does not cover any 1 Shipping labor or material charges 2 Damages resulting from transportation install...

Отзывы: