York FC8T-UH Скачать руководство пользователя страница 26

272312-UIM-A-0407

26

Unitary Products Group

RAPID AMBER FLASH:

 Flame sense current is below 1.5 microamps.

Check and clean flame sensor. Check for proper gas flow.

4

 

AMBER FLASHES: 

The control board is recieving a “Y” signal from

the thermostat without a “G” signal, indicating improper thermostat wir-
ing.

1 RED FLASH:

 This indicates that flame was sensed when there was

not a call for heat. With this fault code the control will turn on both the
inducer motor and supply air blower. A gas valve that leaks through or
is slow closing would typically cause this fault.

2 RED FLASHES:

 This indicates that the normally open pressure

switch contacts are stuck in the closed position. The control confirms
these contacts are open at the beginning of each heat cycle. This would
indicate a faulty pressure switch or miswiring.

3 RED FLASHES:

 This indicates the normally open pressure switch

contact did not close after the inducer was energized. This could be
caused by a number of problems: faulty inducer, blocked vent pipe, bro-
ken pressure switch hose or faulty pressure switch.

4 RED FLASHES:

 This indicates that a primary or auxiliary limit switch

has opened its normally closed contacts. With this fault code the control
will operate the supply air blower and inducer. This condition may be
caused by: dirty filter, improperly sized duct system, incorrect blower
speed setting, incorrect firing rate or faulty blower motor.

5 RED FLASHES:

 This fault is indicated if the normally closed contacts

in the rollout switch opens. The rollout control is manually reset. If it has
opened, check for proper combustion air, proper inducer operation, and
primary heat exchanger failure or burner problem. Be sure to reset the
switch after correcting the failure condition.

6 RED FLASHES:

 This indicates that after the unit was operating, the

pressure switch opened 4 times during the call for heat. If the main
blower is in a “Delay on” mode it will complete it, and any subsequent
delay off period. The furnace will lock out for one hour and then restart.

7 RED FLASHES:

 This fault code indicates that the flame could not be

established. This no-light condition occurred 3 times (2 retries) during
the call for heat before locking out. Low gas pressure, faulty gas valve,
faulty hot surface ignitor or burner problem may cause this. The furnace
will lock out for one hour and then restart.

8 RED FLASHES:

 This fault is indicated if the flame is lost 5 times (4

recycles) during the heating cycle. This could be caused by low gas
pressure or faulty gas valve. The furnace will lock out for one hour and
then restart.

9 RED FLASHES:

 Indicates reversed line voltage polarity or grounding

problem. Both heating and cooling operations will be affected. Check
polarity at furnace and branch. Check furnace grounding. Check that
flame probe is not shorted to chassis.

10 RED FLASHES:

 Gas valve energized with no call for heat. Check

gas valve and gas valve wiring.

11 RED FLASHES:

 This indicates that a primary or auxiliary limit switch

has opened its normally-closed contacts and has remained open for
more than five minutes. This condition is usually caused by a failed
blower motor or blower wheel.

12 RED FLASHES:

 This code indicates an open igniter circuit, which

could be caused by a disconnected or loose wire or by a cracked or bro-
ken igniter.

STEADY ON RED: 

Control failure. Replace control board.

60-MINUTE AUTOMATIC RESET FROM LOCKOUT:

 This control

includes a “watchdog” type circuit that will reset from a lockout condition
after 60 minutes. Operational faults 6,7,8 will be reset. This provides
protection to an unoccupied structure if a temporary condition exists
causing a furnace malfunction. An example would be a low incoming
gas supply pressure preventing unit operation. When the gas pressure
is restored, at some point the “watchdog” would restart the unit and pro-
vide heat for the house.

NOTE: 

If a flame is detected the control flashes the LED for 1/8 of a

second and then enters a flame stabilization period.

DIAGNOSTIC FAULT CODE STORAGE AND 

RETRIEVAL

The control in this furnace is equipped with memory that will store up to
five error codes to allow a service technician to diagnose problems
more easily. This memory will be retained even if power to the furnace
is lost. 

This feature should only be used by a qualified service tech-

nician. 

The control stores up to five separate error codes. If more than five
error codes have occurred since the last reset, only the five most recent
will be retained. The furnace control board has a button, labeled "LAST
ERROR" that is used to retrieve error codes. This function will only work
if there are no active thermostat signals. So any call for heating, cooling
or continuous fan must be terminated before attempting to retrieve error
codes. 

To retrieve the error codes, push the LAST ERROR button. The LED on
the control will then flash the error codes that are in memory, starting
with the most recent. There will be a two-second pause between each
flash code. After the error codes have all been displayed, the LED will
resume the normal slow green flash after a five second pause. To
repeat the series of error codes, push the button again.

If there are no error codes in memory, the LED will flash two green
flashes. To clear the memory, push the LAST ERROR button and hold it
for more than five seconds. The LED will flash three green flashes when
the memory has been cleared, then will resume the normal slow green
flash after a five-second pause.

FILTER PERFORMANCE

The airflow capacity data published in Tables 17 & 18 represent blower
performance WITHOUT filters. To determine the approximate blower
performance of the system, apply the filter drop value for the filter being
used or select an appropriate value from Table 15.
The filter pressure drop values in Table 15 are typical values for the
type of filter listed and should only be used as a guideline. Actual pres-
sure drop ratings for each filter type vary between filter manufacturers.

IGNITION CONTROL

Normal flame sense current is approximately

3.7 microamps DC (µa)

Low flame signal warning starts at 1.5 microamps.

Low flame signal control lockout point is

0.1 microamps DC (µa)

Содержание FC8T-UH

Страница 1: ...DJUSTMENTS 22 WIRING DIAGRAM 30 LIST OF FIGURES Dimensions 6 Typical Attic Installation 7 Typical Suspended Furnace Crawl Space Installation 7 Side Return Cutout Markings 8 Gas Valve 8 Upflow Gas Pipi...

Страница 2: ...s from combustible materials as listed under Clearances to Combustibles in Table 1 Provide clearances for servicing ensuring that service access is allowed for both the burners and blower These models...

Страница 3: ...d Never store items such as the following on near or in contact with the fur nace 1 Spray or aerosol cans rags brooms dust mops vacuum cleaners or other cleaning tools 2 Soap powders bleaches waxes or...

Страница 4: ...t the specified external static pressure and within the air temperature rise specified on the nameplate Table 2 is a guide for determining whether the rectangular duct system that the furnace is being...

Страница 5: ...plenum On all installations without a coil a removable access panel is recommended in the outlet duct such that smoke or reflected light would be observable inside the casing to indi cate the presenc...

Страница 6: ...essibility IMPORTANT If an external mounted filter rack is being used see the instructions provided with that accessory for proper hole cut size HORIZONTAL MODELS IMPORTANT This furnace may be install...

Страница 7: ...removed and a new plenum installed that is the proper size for the new furnace Attach the return plenum to the furnace inlet duct flanges This is typi cally through the use of S cleat material when a...

Страница 8: ...fer to Table 15 SECTION IV GAS PIPING GAS SAFETY IMPORTANT Plan your gas supply before determining the correct gas pipe entry Use 90 degree service elbow s or short nipples and con ventional 90 degree...

Страница 9: ...e gas valve body is a very thin casting that cannot take any external pressure Never apply a pipe wrench to the body of the gas valve when installing piping A wrench must be placed on the octag onal h...

Страница 10: ...o the proper gas orifice size when the furnace is installed Do not attempt to drill out any orifices to obtain the proper orifice size Drilling out a gas orifice will cause misalignment of the burner...

Страница 11: ...ty is corrected Refer to FURNACE DIAGNOSTICS section of the User s Information Maintenance Service Manual provided with this furnace for symptoms of reversed power supply polarity LOW VOLTAGE CONTROL...

Страница 12: ...lt Common is optional when used with batteries Thermostat Installer Setup Number 1 System Type must be set to 6 2 Heat 2 Cool Conventional R 24 Volt Hot Heat XFMR W2 Second Stage Heat RC 24 Volt Hot C...

Страница 13: ...BSG Bonnet Sensor Bonnet Sensor Optional BS Bonnet Sensor W2 Second Stage Auxiliary Heat W2 Second Stage Auxiliary Heat AUX Auxiliary Heat E W1 First Stage Auxiliary Heat E W1 First Stage Auxiliary H...

Страница 14: ...gas supplies must be provided as specified with these instruc tions Since the furnaces are side by side with no space between gas supplies must enter on the right and left respectively All gas piping...

Страница 15: ...wers will come on in the selected continuous fan speed and will stay on until the G signal is removed SECTION VI VENT SYSTEM VENT SAFETY This Category I furnace is designed for residential application...

Страница 16: ...ese instructions Approved Modular Homes must be vented with an approved roof jack and may not be common vented with other appliances VENTING Category I venting consists of vertically venting one or mo...

Страница 17: ...se masonry chimney kits 3 The chimney must extend at least three 3 ft 0 91 cm above the highest point where it passes through a roof of a building and at least two 2 feet higher than any portion of th...

Страница 18: ...tion should be located where it will not be affected by wind gusts light snow airborne leaves or allow recirculation of flue gases 4 Termination should be located where it will not be damaged or expos...

Страница 19: ...anufacturer s instructions Dampers Louvers and Grilles Canada Only 1 The free area of a supply air opening shall be calculated by sub tracting the blockage area of all fixed louvers grilles or screens...

Страница 20: ...horizontally from the burner level of the appliance Refer to COMBUSTION AIR SOURCE FROM OUTDOORS and VENT AND SUPPLY AIR SAFETY CHECK in these instructions for additional information and safety check...

Страница 21: ...mounted on the burner assembly If the temperature around the burner exceeds the set point the ignition control and the gas valve are de energized The operation of this control indicates a malfunction...

Страница 22: ...m Source 1 which has the following items 1 12 30 cm length x 1 8 0 3 cm diameter tubing 2 pieces of 4 10 cm length x 1 8 0 3 cm diameter tubing 1 5 16 0 8 cm tee 1 5 16 0 8 cm x 1 8 3 175 mm reducing...

Страница 23: ...at the gas meter times a barometric pressure and temperature correction factor of 0 960 times 3600 then divided by the time it took to measure 0 10 m3 of gas from the gas meter For Propane LP Gas mul...

Страница 24: ...h low and high have been calibrated at the factory Additional pressure adjustment should not be necessary If adjustment is necessary set to the following specifications After adjustment check for gas...

Страница 25: ...eration Start the system by setting the thermostat above the room temperature Observe the system s response Then use the troubleshooting section in this manual to check the system s operation FURNACE...

Страница 26: ...mit switch has opened its normally closed contacts and has remained open for more than five minutes This condition is usually caused by a failed blower motor or blower wheel 12 RED FLASHES This code i...

Страница 27: ...the difference in ESP values in the table 0 60 w c 150 Pa 0 50 w c 125 Pa to obtain a percentage 0 58 0 50 0 60 0 50 0 8 Multiply percentage by airflow difference to obtain airflow reduction 0 8 X 70...

Страница 28: ...50 1440 1430 1390 1360 1310 1270 1220 1150 41 6 41 1 40 8 40 5 39 4 38 5 37 1 36 0 34 5 32 6 Low 1260 1260 1260 1260 1250 1200 1150 1110 1070 1010 35 7 35 7 35 7 35 7 35 4 34 0 32 6 31 4 30 3 28 6 80...

Страница 29: ...640 1550 1460 56 6 55 5 54 7 53 8 51 0 49 8 48 4 46 4 43 9 41 3 Medium 1440 1440 1430 1420 1400 1380 1340 1300 1220 1150 40 8 40 8 40 5 40 2 39 6 39 1 37 9 36 8 34 5 32 6 Low 1220 1230 1230 1230 1200...

Страница 30: ...272312 UIM A 0407 30 Unitary Products Group SECTION IX WIRING DIAGRAM FIGURE 31 Wiring Diagram...

Страница 31: ...272312 UIM A 0407 Unitary Products Group 31 NOTES...

Страница 32: ...t to change without notice Printed in U S A 272312 UIM A 0407 Copyright by York International Corp 2007 All rights reserved Supersedes 167185 UIM C 0806 Unitary 5005 Norman Product York OK Group Drive...

Отзывы: