035-09651-001-A-0304
Unitary Products Group
9
Model
Accessory
Static Resistance, IWG
BLOWER CFM
2400
2700
3000
3300
3600
F3EH090
Electric
Heat
10 KW
0.01
0.01
0.01
0.02
0.02
16 KW
0.01
0.02
0.02
0.03
0.04
26 KW
0.03
0.04
0.05
0.06
0.07
36 KW
0.05
0.07
0.08
0.10
0.11
Supply Air Plenum
0.03
0.03
0.04
0.05
0.06
Return Air Grille
0.02
0.03
0.04
0.05
0.06
BLOWER CFM
3200
3600
4000
4400
4800
F4EH120
Electric
Heat
10 KW
0.02
0.02
0.03
0.03
0.04
16 KW
0.03
0.04
0.05
0.06
0.07
26 KW
0.06
0.07
0.09
0.11
0.13
36 KW
0.09
0.11
0.14
0.17
0.20
Supply Air Plenum
0.05
0.06
0.07
0.08
0.10
Return Air Grille
0.05
0.06
0.07
0.08
0.10
TABLE 6 - ACCESSORY STATIC RESISTANCE (IWG)
(To be included with Duct System Static Resistance)
CONTROL WIRE SIZING
Wire Size
Maximum Total
Circuit Length
(Feet)
#19 Solid
130
#18 Solid
170
#18 Stranded
180
#16 Stranded
270
#14 Stranded
455
#12 Stranded
730
To determine the total circuit length, add the following distances:
1 - Outdoor Unit to Indoor Unit ___________
2 - Indoor Unit to Thermostat ____________
3 - Thermostat to Indoor Unit ____________
4 - Indoor Unit to Outdoor Unit ___________
5 - Outdoor Unit to Elec. Heater __________
Total Circuit Length __________
Model
Motor HP*
Blower RPM
Adjustable Motor Pulley
Fixed Blower Pulley
Belt
Pitch Dia.
(Inches)
Bore
(Inches)
Pitch Dia.
(Inches)
Bore
(Inches)
Designation
Pitch Lg.
(Inches)
60 Hz
F3EH090
1-1/2
655 - 880
2.8 - 3.8
7/8
7.5
1
A36
37.3
F4EH120
2
700 - 950
7.0
50 Hz
F3EH090
1-1/2
542 - 732
7.5
F4EH120
2
581 - 786
7.0
*
These factory-mounted motors are wired for a 460V power supply. Refer to the wiring diagram inside the motor terminal box when reconnecting the motor leads for a
208 or 230 volt power supply.
TABLE 7 - BLOWER MOTOR AND DRIVE DATA
Blower
Motor
HP
Power
Supply
FLA
Max. Fuse
Size,
1
AMPS
Max. Wire
Length
2
(Ft.)
F3EH090
1-1/2
208-3-60
5.3
10
207
230-3-60
5.8
10
209
460-3-60
2.7
5
897
380-3-50
3.3
5
606
415-3-50
4.0
5
546
F4EH120
2
208-3-60
7.5
10
146
230-3-60
6.8
10
178
460-3-60
3.4
5
712
380-3-50
4.0
5
500
415-3-50
4.5
5
485
NOTE: Refer to Form 550.13-N10.1 for electrical data on units equipped with an electric
heat accessory.
1
Dual element, time delay fuses.
2
Based on three 60
°
C, 14 AWG, insulated copper conductors in steel conduit, a 3% voltage
drop.
TABLE 8 - ELECTRICAL DATA