035-14520-001 Rev. B (0803)
10
Unitary Products Group
* Indicates models available in 50 Hz. Models designated by “93" volt code.
Table 2:
PHYSICAL AND ELECTRICAL DATA
Models F2RC/F2FC/F2RP/F2FP/F3RP(T)
018
024
030
036(RP/FP)
036(RC/FC)
Blower - Diameter x Width
9 x 6
10 x 6
10 x 8
10 x 8
10 x 8
Motor
HP
1/4
1/4
1/3
1/2
1/2
Nominal RPM
1075
1075
1075
1075
1075
Voltage
208/230
Amps
Full Load (208/230)
1.6 / 1.4
1.6/1.4 (50 Hz:2.1)
2.5 / 2.2
3.3/2.9 (50 Hz:2.3)
3.3 / 2.9
Locked Rotor (208/230)
3.3 / 2.9
3.3 / 2.9
6.2 / 5.5
7.4 / 6.5
7.4 / 6.5
Filter
1
Type
DISPOSABLE OR PERMANENT
Size
16 x 20 x 1
16 x 20 x 1
16 x 20 x 1
20 x 20 x 1
16 x 20 x 1
Permanent Type Kit
1PF601BK
1PF601BK
1PF601BK
1PF602BK
1PF601BK
Shipping / Operating Weight (lbs.) - RP/FP
92 / 87
98 / 93
105 / 100
115 / 109
—
Shipping / Operating Weight (lbs.) - RC/FC
—
95/ /90
95 / 90
—
105 / 100
Models F2RP/F2FP/F3RP(T)/F3FP(T)/F2FV/F3FV(T)
040
042
045
048
060
Blower - Diameter x Width
10 x 8
10 x 8
10 x 10
11 x 10
11 x 10
Motor
HP
1/3
3/4
1/3
1/2
3/4
Nominal RPM
1075
1130
925
1085
1100
Voltage
208/230
Amps
Full Load (208/230)
2.5 / 2.2
4.4 / 3.8
3.0 / 2.7
3.4/3.3 (50 Hz:2.4) 4.5/4.4 (50 Hz:5.7)
Locked Rotor (208/230)
6.2 / 5.5
11.9 / 10.3
4.8 / 4.1
4.6 / 4.0
8.4 / 7.3
Filter
1
Type
DISPOSABLE OR PERMANENT
Size
16 x 20 x 1
20 x 20 x 1
22 x 20 x 1
22 x 20 x 1
22 x 20 x 1
Permanent Type Kit
1PF602BK
1PF602BK
1PF603BK
1PF603BK
1PF603BK
Shipping / Operating Weight (lbs.) - RP/FP
121 / 115
115 / 121
150 / 144
148 / 142
155 / 149
Shipping / Operating Weight (lbs.) - RC/FC
—
—
—
—
—
1.
Field Supplied
Table 3:
ELECTRICAL DATA - COOLING ONLY (50 & 60 Hz)
Models
F2RP, F3RP(T), F2RC,
F2FC, F2FP, F3FP(T)
Total Motor Amps
Minimum Circuit Ampacity
Maximum
O.C.P.D.
Minimum
Wire Size
A.W.G.
60 Hertz
60 Hertz
50 Hertz
208V
230V
208V
230V
220V
240V
018(N/H)06
1.6
1.4
2.0
1.8
--
--
15
14
024(N/H)06*
1.6
1.4
2.0
1.8
2.9
2.7
15
14
030(N/H)06
2.5
2.2
3.2
2.8
--
--
15
14
036(N/H)06*
3.3
2.9
4.2
3.7
3.2
2.9
15
14
040H06
2.5
2.2
3.2
2.8
--
--
15
14
042(N/H)06
4.4
3.8
5.5
4.8
--
--
15
14
045H06
3.0
2.7
3.9
3.4
--
--
15
14
048(N/H)06*
3.4
3.3
4.9
4.3
3.3
3.0
15
14
060(N/H)06*
4.5
4.4
6.4
5.5
7.8
7.2
15
14
Table 4:
CONVERSION TABLE
KW & MBH Conversions - for Total Power Input Requirement
FOR
208V
OPERATION MULTIPLY
240V
TABULATED KW & MBH BY
.751
230V
240V
.918
220V
240V
.840