159
T h e b r e a k e r t r i p s a t o n c e w h e n i t
is set to "ON".
Measure insulation resistance to ground to see
if there is any leakage.
Trip of breaker or blow
of fuse
The breaker trips in few minutes
when it is set to "ON"
C h e c k p o w e r s u p p l y c i r c u i t .
Check if the plug is properly plugged in and
make the loose contact firm.
Change controller fuse
Check remote controller
C h a n g e b a t t e r i e s
Power voltage is too low
R e m o t e c o n t r o l l e r m a l f u n c t i o n
R e c e i v e r i s b r o k e n
C o n t r o l l e r i s b r o k e n
Receiver loose or poor connection
N o p o w e r
Fuse of controller burnt out
Remote controller is short of power
Power plug is not well plugged in and poor con-
nection
Fasten the wiring; measure the output
v o l t a g e o f t h e t r a n s f o r m e r , i f i t i s
incorrect, change the transformer
p
u t
r
at
s t
o
n
n
a
c
r
e
n
oit
i
d
n
o
c
ri
A
The air conditioner
does not react after
it is powered ( after
the plug is inserted,
the buzzer does
not sound and the
remote startup has
no response)
The remote controller
does not receive
signals (after it is
powered, the buzzer
will sound, unless it
has malfunction)
The circuit or the part of the air conditioner has
malfunction. They heat and break the insulation
and lead to short circuit or creepage. Measure
the insulation resistance or eliminate the malfunc-
t i o n o n e b y o n e . I f t h e b r e a k e r i t s e l f h a s
malfunction, then replace the breaker.
The transformer connection is loose or has bad
contact or the transformer has malfunction
First, press the manual switch button AUTO,
if there is no response,check based on the
above methods. If it runs normally after
pressing the button,check again whether the
installation position and the connection wire
of the reception head is correct. If it is
correct,then replace the receiver or the re-
mote controller.
heck the voltage. If it is lower than 10£¥ of the rated voltage, check the
cause, improve the power supply condition and add the stabilized voltage
power supply.
Note: When replacing the controller, make sure insert the wire jumper into the new controller, otherwise the
unit display C5
Troubleshooting Guide
Troubleshooting Guide
Содержание EVJC 12
Страница 2: ...74 74...
Страница 30: ...102...
Страница 32: ...104 www johnsoncontrols com...
Страница 34: ...106 by johnson controls 2...
Страница 35: ...107 by johnson controls 3 Fig 1 Fig 2 Fig 3 15 cm 15 cm 70 cm 15 cm 15 cm 200 cm 5 6 7 30 cm 50 cm 2 3 4 1 5...
Страница 46: ...118...
Страница 48: ...120 www johnsoncontrols com...
Страница 49: ...121 High Wall EVHC 09 to 12 DSAAAR SERVICE MANUAL SM EVHC D 09 12GB 05 10 EVHC 09 EVHC 12...
Страница 65: ...137 LULQJ LDJUDP Schematic Diagram Indoor Unit Schematic Diagram...
Страница 66: ...138 Schematic Diagram Outdoor Unit...
Страница 69: ...141 TOP VIEW Schematic Diagram BOTTOM VIEW 1 3 4 5 6 2 7 8 9 10 11 12 Outdoor Unit...
Страница 113: ...185 Exploded View Exploded View Indoor Unit...
Страница 114: ...186 Exploded View Outdoor Unit...
Страница 118: ...190 High Wall EVHC 18 to 24 DSAAAR SERVICE MANUAL SM EVHC D 18 24GB 05 10 EVHC 18 EVHC 24...
Страница 132: ...204 LPHQVLRQV Dimensions QGRRU 8QLW Tube exit Air inlet Right Left Ceiling W D H 02 18K 24K...
Страница 133: ...205 890 340 955 560 380 424 700 60cm 60cm 60cm 60cm LPHQVLRQV Outdoor Unit Bolt Nut Spanner...
Страница 140: ...212 TOP VIEW Schematic Diagram BOTTOM VIEW 1 2 3 4 5 6 7 8 9 7 8 9 10 11 12 13 1 2 3 4 5 6 10...
Страница 142: ...214 Schematic Diagram Key testing spot bottom...
Страница 197: ...269 Exploded View Exploded View Indoor Unit 78 Model EVKC 18 DS...
Страница 198: ...270 Exploded View Model EVKC 24 DS 79...
Страница 199: ...271 Exploded View Outdoor Unit 80...