ELECTRICAL DATA

NOTES (pages 4 - 7)

1.

MRA is Maximum Running Amps, the maximum continuous current at any operating point in the rating range. Also referred to as MCA,
or Minimum Circuit Ampacity to be provided by the installer. If a Factory Mounted Control Transformer is provided, add 3 amps to the
system #1 MCA values in the YCAS Tables.

2.

The recommended disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the
circuit, per N.E.C. 440 - 12A1.

3.

Minimum recommended fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs. Minimum fuse rating
= (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).

4.

Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit,
per N.E.C. 440-22. Maximum fuse rating  = (2.25 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).

5.

Minimum recommended circuit breaker is 150% maximum plus 100% of rated load amps included in the circuit. Minimum circuit breaker
rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).

6.

Maximum circuit breaker is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit,
per U.L. 1995 Fig. 36.2. Maximum circuit breaker rating = (2.25 x largest compressor RLA) + other compressor RLAs + ( # fans x each
fan motor FLA).

7.

The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs.  The (1), (2), or (3)
indicate the number of termination points or lugs which are available per phase.  Actual wire size and number of wires per phase must
be determined based on ampacity and job requirements using N.E.C. wire sizing information.  The above recommendations are based
on the National Electrical Code and using copper connectors only. Field wiring  must also comply with local codes.

8.

A ground lug is provided for each compressor system to accommodate field grounding conductor per N.E.C. Article 250-54. A control
circuit grounding lug is also supplied.

9.

The field supplied disconnect is a “Disconnecting Means” as defined in N.E.C. 100.B, and is intended for isolating the unit from the
available power supply to perform maintenance and troubleshooting.  This disconnect is not intended to be a Load Break Device.

10. Two-compressor machines with single-point power connection, and equipped with Star-Delta compressor motor start must also include

Factory provided circuit breakers in each motor control center.

11. Consult factory for Electrical Data on units equipped with “High Static Fan” option.  50Hz High Static Fans are 3.5kW each.

12. FLA for each “Low Noise Fan” motor:   380v/50Hz = 4.1A.

ACR-LINE

ACROSS THE LINE START

CB

CIRCUIT BREAKER

DE FU

DUAL ELEMENT FUSE

DISC SW

DISCONNECT SWITCH

FACT MOUNT CB

FACTORY-MOUNTED CIRCUIT BREAKER

FACT MOUNT FUSE

FACTORY-MOUNTED FUSES

FLA

FULL LOAD AMPS

HZ

HERTZ

MAX

MAXIMUM

MCA

MINIMUM CIRCUIT AMPACITY

MIN

MINIMUM

MIN NF

MINIMUM NON-FUSED

RLA

RUNNING LOAD AMPS

S.P. WIRE

SINGLE-POINT WIRING

UNIT MTD SERV SW

UNIT-MOUNTED SERVICE (NON-FUSED DISCONNECT

SWITCH)

WYE-DELTA

WYE-DELTA START

XLRA

ACROSS-THE-LINE INRUSH LOCKED ROTOR AMPS

YLRA

WYE-DELTA INRUSH LOCKED ROTOR AMPS

LEGEND

VOLTAGE  CODE
50=380/415-3-50

Содержание eco YCAS0685EB

Страница 1: ...WIRING DIAGRAM eco2 AIR COOLED SCREW LIQUID CHILLERS MODELS YCAS STYLE F Supersedes 201 18 W7 700 Form 201 18 W9 601 MODELS YCAS0685 THROUGH YCAS0965 50Hz Better ecology Better economy 28971AR ...

Страница 2: ...agram Detail C 28 Connection Diagram System Wiring 29 Control Power Transformer Kit Optional 31 TABLE OF CONTENTS WARNING HIGH VOLTAGE is used in the operation of this equipment DEATH OR SERIOUS INJURY may result if personnel fail to observe precautions Work on electronic equipment should not be undertaken unless the individual s has have been trained in the proper maintenance of the equipment and...

Страница 3: ...teristics of the unit YORK Chiller YC YORK Chiller Air Cooled Compressor Type S Screw Nominal Capacity Unit Designator E High Efficiency Design Series Type Start Y Star WYE Delta X Across the Line Voltage Code 50 380 415 3 50 Refrigerant B R 407C YC A S 0685 E B 50 Y F NOMENCLATURE ...

Страница 4: ...ompressor 3 Fan11 12 Model Data YCAS Volts MRA1 Min NF Protection13 Standard Optional NF RLA Y LRA X LRA RLA Y LRA X LRA Qty FLA ea LRA ea MCA Disc SW2 9 Min 3 5 Max 4 6 Terminal block Disc Switch 0685EB 380 367 400 400 500 2 2 4 0 2 3 0 250 99 219 692 162 267 857 7 5 7 25 0775EB 380 367 400 400 450 2 2 4 0 2 3 0 250 128 267 857 128 267 857 8 5 7 25 0835EB 380 410 400 450 500 2 1 0 300 2 250 500 1...

Страница 5: ...X LRA Qty FLA ea LRA ea MCA Disc SW2 9 Min 3 5 Max 4 6 Terminal Block Disc Switch 0685EB 380 141 150 175 225 1 2 4 0 1 2 4 0 99 219 629 3 5 7 25 0775EB 380 184 200 225 300 1 2 4 0 1 4 300 128 267 857 4 5 7 25 0835EB 380 184 200 225 300 1 2 4 0 1 4 300 128 267 857 4 5 7 25 0905EB 380 226 250 300 350 1 1 0 300 1 4 300 163 267 857 4 5 7 25 0965EB 380 223 250 300 350 1 1 0 300 1 4 300 155 267 857 5 5 ...

Страница 6: ...Circuit Breakers in each Motor Control Center CHILLER FIELD SUPPLIED WIRING MODEL FIELD PROVIDED POWER SUPPLY FACTORY PROVIDED LUGS WIRE RANGE 7 YCAS MIN NF OVER CURRENT PROTECTION STANDARD OPTIONAL NF MRA1 DISC SW 2 9 MIN 3 5 MAX 4 6 TERMINAL BLOCK DISC SWITCH 0685EB 482 600 600 600 2 2 0 500 2 250 500 0775EB 517 600 600 600 2 2 0 500 2 250 500 0835EB 560 600 700 700 2 2 0 500 2 250 500 0905EB 63...

Страница 7: ...4 5 7 25 128 267 857 4 5 7 25 163 267 857 4 5 7 25 155 267 857 5 5 7 25 Compressor 1 Data Compressor 3 Data Fan Data11 12 RLA Y LRA X LRA RLA Y LRA X LRA Qty FLA ea LRA ea 99 219 692 162 267 857 7 5 7 25 128 267 857 128 267 857 8 5 7 25 163 267 857 128 267 857 8 5 7 25 163 267 857 163 267 857 8 5 7 25 155 267 857 148 267 857 11 5 7 25 ...

Страница 8: ...ng lugs The 1 2 or 3 indicate the number of termination points or lugs which are available per phase Actual wire size and number of wires per phase must be determined based on ampacity and job requirements using N E C wire sizing information The above recommendations are based on the National Electrical Code and using copper connectors only Field wiring must also comply with local codes 8 A ground...

Страница 9: ...ONNECT SUPPLY CURRENT FUSE SIZE SWITCH SIZE 2 115V 1Ø 20A 20A 30A 3 or 4 115V 1Ø 30A 30A 30A Non CE 50 60Hz 3 or 4 115V 1Ø 25A 30A 30A CE 50Hz NO OF CONTROL MCA RECOMMENDED NON FUSED COMPRESSORS POWER MAX LOAD DUAL ELEMENT DISCONNECT SUPPLY CURRENT FUSE SIZE SWITCH SIZE 2 400V 50Hz 6 3A 15A 3 or 4 400V 50Hz 9 4A 15A CONTROL POWER SUPPLY UNITS WITH STANDARD CONTROL CIRCUIT TRANSFORMERS ...

Страница 10: ...E SYSTEM CIRCUIT BREAKERS MULTIPLE POINT NON FUSED DISCONNECTS WITH SEPARATE SYSTEM TERMINAL BLOCKS SUITABLE FOR ACROSS THE LINE START ONLY DEF or HACR TYPE CB Supply 2 Supply 1 1 2 3 TB TB TB SW SW LD04365 LD04364 DEF or CONVENTIONAL TYPE CB 1 TB TB 2 3 SUPPLY 1 SUPPLY 2 SW SW ...

Страница 11: ...E POINT NON FUSED DISCONNECTS WITH SEPARATE SYSTEM CIRCUIT BREAKERS SINGLE POINT WITH NON FUSED DISCONNECT SWITCH SYSTEM CIRCUIT BREAKERS DEF or CONVENTIONAL CB Supply 2 Supply 1 CB SW SW CB CB 1 3 2 LD04366 LD04367 DEF or CONVENTIONAL TYPE CB Unit Supply 1 3 2 CB SW CB CB ...

Страница 12: ... WITH SEPARATE SYSTEM CIRCUIT BREAKERS MULTIPLE POINT WITH SEPARATE SYSTEM TERMINAL BLOCKS SUITABLE FOR ACROSS THE LINE START ONLY Unit Supply DEF or CONVENTIONAL TYPE CB 1 3 2 CB TB CB CB LD04368 Supply 2 1 3 2 DEF or HACR TYPE CB Supply 1 TB TB TB TB TB LD04369 ...

Страница 13: ...FORM 201 18 W9 13 YORK INTERNATIONAL POWER WIRING POSSIBILITIES CONTROL 120 1 50 SUPPLY VIA STANDARD CONTROL TRANSFORMER CONTROL 120 1 50 SUPPLY WITHOUT STANDARD CONTROL TRANSFORMER LD07043 LD07044 ...

Страница 14: ...YORK INTERNATIONAL 14 ELEMENTARY DIAGRAM FIG 1 ELEMENTARY DIAGRAM LD04172A ...

Страница 15: ...FORM 201 18 W9 15 YORK INTERNATIONAL ELEMENTARY DIAGRAM FIG 2 ELEMENTARY DIAGRAM LD04172B ...

Страница 16: ...EL CHILLERS NOT PRESENT ON 3 COMPRESSOR CHILLERS PRESENT ON CERTAIN MODEL CHILLERS NOT PRESENT ON 3 COMPRESSOR CHILLERS FIG 3 STANDARD COMPRESSOR POWER SUPPLY ACROSS THE LINE START STANDARD COMPRESSOR POWER SUPPLIES ACROSS THE LINE START LD04173 ...

Страница 17: ...ON CERTAIN MODEL CHILLERS NOT PRESENT ON 3 COMPRESSOR CHILLERS PRESENT ON CERTAIN MODEL CHILLERS NOT PRESENT ON 3 COMPRESSOR CHILLERS FIG 4 STANDARD COMPRESSOR POWER SUPPLY WYE DELTA START STANDARD COMPRESSOR POWER SUPPLIES WYE DELTA START LD04174 ...

Страница 18: ...YORK INTERNATIONAL 18 STANDARD COMPRESSOR POWER SUPPLIES ACROSS THE LINE START FIG 5 ELEMENTARY DIAGRAM ...

Страница 19: ...FORM 201 18 W9 YORK INTERNATIONAL YORK INTERNATIONAL 19A 19 FORM 201 18 W9 SHLD G ISN RS485 PORT ...

Страница 20: ...19B YORK INTERNATIONAL 20 FORM 201 18 W9 YORK INTERNATIONAL CONNECTION DIAGRAM FIG 6 CONNECTION DIAGRAM Box Information continued on page 22 ...

Страница 21: ...FORM 201 18 W9 21 YORK INTERNATIONAL ...

Страница 22: ...YORK INTERNATIONAL 22 CONNECTION DIAGRAM FIG 7 CONNECTION DIAGRAM LD04180 Box Information continued from page 20 ...

Страница 23: ...FORM 201 18 W9 23 YORK INTERNATIONAL LD04181 CONNECTION DIAGRAM FIG 8 CONNECTION DIAGRAM Box Information continued from page 20 ...

Страница 24: ...YORK INTERNATIONAL 24 FIG 9 CONNECTION DIAGRAM CONNECTION DIAGRAM ELECTRICAL BOX YCAS0250 0330 YCAS0693 0953 STYLE F STANDARD REMOTE EVAP UNITS LD04182 ...

Страница 25: ...FORM 201 18 W9 25 YORK INTERNATIONAL FIG 10 CONNECTION DIAGRAM CONNECTION DIAGRAM ELECTRICAL BOX YCAS0250 0330 YCAS0693 0953 STYLE F STANDARD REMOTE EVAP UNITS LD04183 ...

Страница 26: ...YORK INTERNATIONAL 26 ELEMENTARY DIAGRAM DXST DIRECT DRIVE CONTROL CIRCUIT FIG 11 ELEMENTARY DIAGRAM DXST DIRECT DRIVE CONTROL CIRCUIT LD04177 ...

Страница 27: ...FORM 201 18 W9 27 YORK INTERNATIONAL ELEMENTARY DIAGRAM DXST DIRECT DRIVE CONTROL CIRCUIT FIG 12 ELEMENTARY DIAGRAM DXST DIRECT DRIVE CONTROL CIRCUIT ...

Страница 28: ...LEMENTARY DIAGRAM DXST DIRECT DRIVE CONTROL CIRCUIT FIG 13 ELEMENTARY DIAGRAM DXST DIRECT DRIVE CONTROL CIRCUIT DETAIL C SEE INSTALLATION OPERATION AND MAINTENANCE MANUAL FOR JUMPER OF CONDENSER FANS FOR CHILLER MODEL LD04374 ...

Страница 29: ...FORM 201 18 W9 29 YORK INTERNATIONAL CONNECTION DIAGRAM SYSTEM WIRING STANDARD REMOTE EVAP UNITS FIG 14 CONNECTION DIAGRAM SYSTEM WIRING LD04184 ...

Страница 30: ...YORK INTERNATIONAL 30 LD04185 CONNECTION DIAGRAM SYSTEM WIRING STANDARD REMOTE EVAP UNITS FIG 15 CONNECTION DIAGRAM SYSTEM WIRING ...

Страница 31: ...FORM 201 18 W9 31 YORK INTERNATIONAL FIG 16 CONTROL POWER TRANSFORMER KIT CONTROL POWER TRANSFORMER KIT LD04186 ...

Страница 32: ...www york com P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by York International Corporation 2001 ALL RIGHTS RESERVED Form 201 18 W9 601 Supersedes 201 18 W7 700 ...

Отзывы: