![York E4TS030 Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/york/e4ts030/e4ts030_technical-manual_3758844012.webp)
036-21342-002 Rev. E (0505)
12
Unitary Products Group
ACCESSORIES
Refer to Price Manual for specific model numbers.
TXV Kit - Factory specified and required for proper unit per-
formance.
E4TS030 = 1TV0701
E4TS036 = 1TV0702
E4TS048 = 1TV0703
E4TS060 = 1TV0703
Room Thermostat - Matching 2-Stage cooling thermostats
are available to provide features required for any installation.
See list below:
2ET03700624 - Honeywell Programmable
2ET03700524 - Honeywell Non-Programmable
2EP32U70124 - White Rodgers Programmable
Dehumidification Control - Model 2HU06700124 available
for use in areas where a higher level of humidity control is
required.
Fossil Fuel Relay (Model 2FF02700101) - Required for use
with all furnace applications.
SOUND RATINGS*
* Rated in accordance with ARI 270-95 Standards.
E4TS048
P1XDD20V112
G2FD060S24
1
880
21400
-
-
3.30
2
880
43000
23800
7.7
3.34
2
1580
46500
25800
8.0
3.52
G2FD061H24
1
880
22000
-
-
3.38
2
880
44000
24400
7.9
3.42
2
1580
47500
26400
8.2
3.60
P1XUD20V112
24
G1UA060S24
1
915
22200
-
-
3.34
2
915
44000
25000
7.8
3.36
2
1620
47500
27000
8.1
3.54
G1FA060S24
1
915
22200
-
-
3.34
2
915
44000
25000
7.8
3.36
2
1620
47500
27000
8.1
3.54
G2FD060S24
1
915
22200
-
-
3.34
2
915
44000
25000
7.8
3.36
2
1620
47500
27000
8.1
3.54
G2FD061H24
1
915
22600
-
-
3.40
2
915
45000
25600
8.0
3.44
2
1620
48500
27600
8.3
3.62
E4TS060
P1XDD20V112
G2FD060S24
1
1000
23400
-
-
3.38
2
1000
49500
26000
7.5
3.28
2
1800
54000
28400
7.9
3.46
G2FD061H24
1
1000
23400
-
-
3.48
2
1000
50500
26600
7.9
3.35
2
1800
55000
29000
8.2
3.52
P1XUD20V112
24
G1UA060S24
1
990
23200
-
-
3.34
2
990
49500
26000
7.6
3.34
2
1800
54000
28400
8.0
3.52
G1FA060S24
1
990
23200
-
-
3.34
2
990
49500
26000
7.6
3.34
2
1800
54000
28400
8.0
3.52
G2FD060S24
1
990
23200
-
-
3.34
2
990
49500
26000
7.6
3.34
2
1800
54000
28400
8.0
3.52
G2FD061H24
1
990
23200
-
-
3.42
2
990
50500
26600
8.0
3.40
2
1800
55000
29000
8.3
3.58
1. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and
no supplemental electric heat operation.
2. Integrated heating capacities include the effect of defrost cycles in the temperature range where they occur.
3. HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided
by the total electric power input during the same period.
4. COP equals MBH output divided by (total KW input x 3.412).
HEATING CAPACITY - Variable Speed Furnace (Continued)
UNIT
MODEL
VARIABLE SPEED
FURNACE MODEL
W
COIL MODEL
HEATING
STAGE
(# CYL)
RATED
CFM
NET MBH
1,2
HSPF
3
COP
4
@ 47 F
47 OD
17 OD
UNIT MODEL
SOUND RATINGS
(dba)
1 CYLINDER
2 CYLINDER
030
72
73
036
75
78
048
77
79
060
79
81